The text of a manual · part 7 of 8
Class 8030 Types CRM-230, 232 Local/Remote Transfer Interface System, pages 29 to 37
Pages 29 to 37 of 46
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D 8030-CRM-232 and Schneider 8030-CRM-232
Page 29
B.4.2 ATC STATUS FIELD
30598-251-01
{32 [ 31 | 30 | 29 | 28 | 27 | 26 | 25 | 24 | 23 | 22 { 21 | 20 | 19 [ 18 [ t7 |
Internal Channel Usage Diagnostics Complete Internal i_ - - Channel Usage Initialization Complete Internal Usage Channel Spare Addressing Complete Spare Primary; Backup Spare Transmit loss Spare Receive Loss Spare Backup Loss Spare Startup Transfer
RTC Remote Transter Channel Status
Control Register Bit Name Description 17 Channel Diagnostics Set ON (1) when LTI self-test is successfully completed. Reset OFF (0) when self- Complete tests are in progress. 18 Channel Initialization Set ON (1) when LTI is in RUN with a verified address map and |/O channel is Complete initialized. 19 Addressing Complete Set ON (1) when address map has been loaded and verificd. 20 Primary / Set ON (1) when LTI is Primary. Backup Set OFF (0) when LTI is Backup.
21 Transmit Loss Set ON (1) when matched LTI has its RECEIVE LOSS bit set.
22 Receive Loss Set ON (1) when LTI has not received communication from its matched pair.
23 Backup Loss Set ON (1) in Primary LT]s that do not have a Backup that can become Primary. Reset OFF (0) when a Backup in full RUN is present. Backup LTIs will also set their BACKUP LOSS bit when they are unable to become Primary.
24 Startup Transfer Set ON (1) one scan before a Primary does a Startup Transfer. Reset OFF (0) upon completion of the Startup Transfer.
25 Spare
26 Spare
27 Spare
28 Spare
29 Spare
» Internal Usage
31 Internal Usage
32 Internal Usage
Figure B.5, RTC Contro! Register Status Field
Page 29
Page 30
Page 30 30598-251-01
B.4.3 DETAILED DESCRIPTION OF LTI RTC CONTROL BITS
The LTI RTC contro) register data bits, bits 1-t6, are initially reset OFF (0} when the LTIis installed. This defaultstate of the RTC register data bits puts the Transfer Interface System (TIS) in a strictly “bumpless transfer” mode. Primary and Backup processors must be operating in synchronization with each other or else the Backup will not remainin RUN. In theevent of a failure in the Primary, a bumpless transfer will occur, the Backup wil! pick up exactly where the Primary left off.
The user can alter these data bits via data entry or the ladder program. Once the bits are altered, there states are maintained until changed again by the user or all power (including battery backup) is lost.
RTC FAILURE OVERRIDE Bit (13)
Primarily this bit determines whether the TIS will be restricted to a synchronized bumpless transfer more or, for the sake of maintaining redundant backup, allow unsynchronized operation of the Primary and Backup, thus permitting a “bump transfer“ to occur in the event of a tailure in the Primary.
By leaving the RTC Failure Override bit reset OFF (0) in the Backup, the Backup will not be allowed to RUN out of sync with the Primary: should the Backup fall out of synchronization with the Primary, the Backup will generate an errorand go into HALT.
NOTE: The Backup will fall out of sync if there is a failure in the RTC communication between the Primary and Backup LTIs, if the difference between the Primary and Backup scan times exceeds the sean hold time residing in the Scan Synchronization register or, if the Backup loses communication with one or more drops.
By setting the R1C Failure Override bit ON (1) in the Backup, the Backup is allowed to continue in RUN in the event that it falls out of sync with the Primary. Therefore, if a failure occurs in the Primary, a bump transfer is permitted. A bump transfer is a transfer that takes place when the Primary and Backup are out of sync with each other; thus, their 1/ Oinformation may not be exactly the same. A bump transfer, due to alternate verifica-tion procedures, may take longer to execute than a bumpless transfer.
NOTE: In order to maintain TIS consistency when the Primary and Backup exchange rules, it is recommended that the RTC contro! register bits, in particular the RTC Failure Override bits, be programmed the same in both the Primary and Backup.
If the Backup loses sync with the RTC Failure Override bit set ON (1), it can be re-synchronized (provided that the RTC communication link is intact) by one of the following three methods: ft. Setting Re-Sync bit [5 ON (1).
2. Pressing the restart button onthe Backup LTI that is in error.
3. Keyswitching the Backup from HALT to RUN.
Note that all three methods wil] cause a Startup Transfer to occur, thereby m ring the processor scan and freezing all 1/0. [See Section 5.4.2.
TEST Bit (14)
This bit only affects a Backup LT! when there is a Primary LTT in RUN, When the TEST bit is set ON (1), the Backup LTI will not request a Startup Transfer of registers upon its HALT to RUN transition. This will allow the Backup system to be tested without initiating a Startup Transfer upon each HALT to RUN transition which would interrupt the Primary scan.
The test bit may be set (via any SY/ MAX programmer) in the Primary or Backup LT]. 4n either case, the Backup will be forced into the test mode.
NOTE: With the TEST bit set, the Backup LTI cannot become Primary. For multiple LTI systems, the TEST bit must be set ON (1) for aff Backup LT] modules ta prevent any Startup Transfers.
To indicate that the TEST bit is ON (|), the PRIMARY and BACKUP LEDs will flash alteruately on the Backup LTI; the Backup CPU LED on the RTI will be off, indicating a ready Backup is of present.
Upon resetting the TEST bit. the Backup will halt uniess the RTC Failure Override bit is set.
RE-SYNC Bit (15)
The re-sync bit is only active ina Backup LTI thatisin RUN. If the Backup loses sync with the Primary, having the Re-Sync bit
ON (t)} will cause the Backup to request a St pTransferinan attempt to re-synchronize the system. SeefSection 5.4.4, For the re-synchronization to take place, the following conditions must be true:
1. Backup TEST bit must be reset OFF (0).
2, Backup’s RTC FAILURE OVERRIDE bit must be set ON (1) if the error originates on the RTC channel; I/O FAIL- URE OVERRIDE bit must be ON (1) if error originates on 1/0 channel.
3. Backup RE-SYNC bit must be set ON (1). 4, Proper RTC communications must cxist.
If the re-sync attempt is successful, the Backup will synchronize with the Primary. If the attempt is unsuccessful, the Backup will continually request a Startup Transfer to attempt to re-synchronize the system as long as the above four conditions are true and re-synchronization hasn't occurred.
NOTE: Whenever a Startup Transfer occurs, the Primary system scan time can be delayed for up to 1/2 second. [See Section 5.4.2]
Certain conditions, suchas broken RTC or 1/O communication wires that make intermittent contact, can cause repeated Startup Transfers to be requested. Even though the operating system firmware only allows one Startup [Transfer to be attempted every 100 scans, the resulting interruptions of the Primary processor's ladder scan must be taken into consideration. Thus, it is recommended that the RE-SYNC bit only be activated occasionally, and then only during non-critical operations (those tha: could be interrupted briefly for a Startup Transfer}. Note the time required to execute a Startup Transfer can be minimized by on) ¢ registers necessary for proper operation. | See Section 5.4.2)
Page 31
If the Backup is already in sync with the Primary when the Re-sync bit is turned ON (1), a Startup Transfer will not be requested.
For multiple LTI systems, all LTI's will perform a Startup Transfer whenever any one LTI requests it.
END OF SCAN (£O0S) TRANSFER REGISTERS Bit (16)
This bit is only active in Backup LTlsin RUN. If this bit is set ON (1), at the end of every scan the Backup LTI will request a transfer of 32 registers from the Primary. The specific registers to be transferred are determined by the value residing in the End of Scan Transter Register, the second register assigned to the
RTC. No n is lost, EOS register transfers will cease. | See Section 5.4.3
PRIMARY /BACKUP Bit (20)
This bit is turned ON (1) when an LTI becomes Primary and turned OFF (0) when it becomes Backup; it can be interrogated to initiate control action based on its Primary; Backup status.
TRANSMIT LOSS Bit (21)
This bit is turned ON (1) in a Primary or Backup LTI when its matched LTI has its receive loss bit turned ON.
30598-251-01 Page 31
RECEIVE LOSS Bit (22)
This bit is turned ON (1) in a Primary or Backup LTI when it is no longer receiving RTC communications.
BACKUP LOSS Bit (23)
This bit is turned ON (1) in Primary LTI modules that do not have a Backup that can become Primary, The bit is turned OF F (0) when Backup LTI modules are in RUN and are able to become Primary.
Backup LTIs set their BACKUP LOSS bit ON (1) when they are unable to become Primary.
STARTUP TRANSFER Bit (24)
This bit is turned ON (1) one scan before a Primary performs a Startup Transfer and is cleared at the completion of the Transfer. For multiple LTI systems, only the LTI that is initiating the Startup Transfer will turn on its Startup Transfer bit, even though all LTIs perform a Startup Transfer when any one requests it.
APPENDIX C, PRIMARY /BACKUP DETERMINATION
C.1 General Information
In order for the Transfer Interface System to work properly. rules exist to determine which system assumes Primary status. Figure C.1 lists the different possible states of each processor and an associated state priority number.
Primary Beckup CPU CPU
Priority Priority
CPU State Number Number RUN 7 6
RUN (I/O Failure Override bit set and drop error present) 3 6 DISABLE OUTPUTS 4 3 HALT 2 1 NO POWER 0 0
Figure C.1, Processor State Priority
The RTC continuously tests the state of each processor rack. The processor that has the highest state priority will be declared as Primary. If both processors are in the same state, the system that was most recently Primary {indicated by the Primary/ Backup history bit 20) will retain its Primary status. Should both processors have identical history bits, the processor which attains a higher priority state first will be declared Primary. In the event of a total tie, the LTI connected to the CPU A channel] of the RTIs will become Primary.
C.2 Primary Determination at Power Up
At power up, A Backup system with no RTC communication will wait five seconds before making Primary determination. This is to allow the last Primary to have the first change at controlling the 1/O system. If after five seconds the Backup finds no Primary, it will interrogate the I/O drops to see if they are communicating with a Primary processor. If they are, the Backup will assume a RTC fault, generate an error, and go into HALT (depending on the status of its RTC Failure Override bit}. If the Backup finds that no RTIs are communicating witha Primary, it will assume Primary status when it goes into RUN.
If the Backup rack is powered up exactly five seconds before the Primary rack, it is possible for different LT1s in the same rack to have different Primary/Backup statuses. To prevent this ambiguous situation, at the end of every scan each processor will check to see that all LTIs in its rack have the same Primary / Backup status. If different Primary/ Backup statuses exist, the processor will declare an error and go into HALT. The usercan clear this error by power cycling and making sure that the rack to be designated as Primary is powered up at least ten seconds before the Backup rack.
If both systems power up as Primary at exactly the same time, they will both switch to Backup status. If one switches to Backup status before the other, the lagging system will remain Primary. If both systems become Backup at the same time, the processor connected to the CPU A channel will become Primary.
Page 32
Page 32 30598-251-01
C.3 Primary Determination After Power Up
As described in Section C.1 of this appendix, during normal operation the Primary rack will be the rack with the highest state priority. If both racks are in the same state priority, the Primary rack will be the one with the Primary/ Backup history bit set ON (1).
If a Backup does not have valid communication from the Primary RTC, it must determine from the RTIs whether or not to become Primary. This is possible since all RTI communication contains Primary; Backup status information. If it is determined from the RTls that there is no Primary control, the Backup LTI will assume the Primary system is powered down and become Primary. If the Backup determines from the RTIs that there is Primary control, it will assume an RTC communication error, and follow action in accordance with the status of the RTC FAILURE OVERRIDE and TEST bits.
If a Primary in full RUN detects a communication problem with an I/O drop, it will tst to see if there is a Backup in full RUN able to become Primary. Ifso, the Primary will declare an 1/O error and go into HALT, forcing a transfer to the Backup. Therefore the Backup becomes the new Primary. If a ready Backup is not found, the Primary will act in accordance with the 1/O Faiture Override bit ($8162-13).
A transfer from Primary to Backup will not occur in the event that an RTI declares a remote drop bus error. In this case, the Backup will go into HALT with an 1/O error, regardless of the status of its 1/O Failure Override bit while the Primary will either remain in RUN or not, in accordance with the status of its 1/O Failure Override bit. This insures the safest and quickest manner of handling this type of fault.
C.4 Primary Determination Examples
The following examples illustrate several situations in which the TIS determines Primary/ Backup status.
Example |: Both Primary and Backup are in RUN when an LTI in the Primary generates an error: When the PRimary processor detects the error, it will declare an error and HALT. Since the Backup system is now in a higher state priority, it will assume Primary status and the system will continue to RUN.
Example 2: Primary processor in RUN, Backup in DISABLE OUTPUTS, when an LTI inthe Primary generates an error: This is identical to Example | except the Backup will assume Primary status and the system will go into DISABLE OUTPUTS.
Example 3; Primary processor in RUN, Backup in HALT, when an LTI in the Primary generates an error: When the Primary processor detects the error, it will HALT the system. Since the Primary processor is still in a higher state, the Primary system will not switch to Backup status. The Backup will assume Primary status in the event the Backup processor is placed in DISABLE OUTPUTS or RUN.
Example 4: Primary in RUN, Backup powered down, when an LTI in the Primary generates an error: Since no Backup is present, the Primary processor witl HALT with an error (unless the I/O failure override bit is set). If the Backup processor is powered up with its keyswitch in RUN or DISABLE OUT- PUTS, it will first come up as a Backup, and then a transfer will take place, converting the Backup to the Primary.
Example 5: Primary processor in DISABLE OUTPUTS, when the Backup is placed in RUN: This is an illegal and inconsistent condition which should not be allowed to occur. Depending on rack addressing, program length, and other factors, the Backup may either HALT with anerror or gointo RUN. If the Backup goes to RUN, a transfer will result in real world outputs becoming active.
Example 6: Primary in RUN with 1/O FAILURE OVER- RIDE bit set ON (1), Backup in HALT, when the Primary experiences a communication failure with an 1/O drop: Because the Primary (state 5) is ina higher state than the Backup (state 1), no transfer will take place, and the Primary system will remain in RUN with the bad drop shutdown, If the Backup is placed into RUN, the Primary will go into HALT with an error, and the Backup will become Primary.
Example 7: Primary and Backup processors in full RUN, both have the 1/O FAILURE OVERRIDE bit set when an RTI declares a remote drop bus error: No transfer will take place. When the Backup detects a remote bus error, it immediately goes into HALT with an error, ignoring the 1/O FAILURE OVER- RIDE bit. The Primary continues to RUN, shut-ting down the bad drop.
Example 8: Primary processor is in RUN with 1/O FAILURE OVERRIDE bit set ON (1) while the Backup processor is in RUN with I/O FAILURE OVER- RIDE bit reset OFF (O): If the Primary system's 1/O channel cable is severed, the Primary will recognize the communication error. Because a full Backup is present, the Primary will ignore its 1/0 FAILURE OVERRIDE bit and go into HALT with an error. When the Primary processor HALTs, all LTIs in the Primary rack will simu!- taneously go to Backup status, while the Backup becomes Primary.
Example 9: Both Primary and Backup systems are in full RUN, only the Primary I/O FAILURE OVER- RIDE bit is set, and the Transmission Fault Tolerance bit (TXFT) is cleared: At this time, a noisy communication channel causes an RTI to miss three successive data blocks (which exceeds the fault tolerance determined by the TXFT bit). The RTI declares a communication error and the Primary generates an error and goes into HALT. When the Primary processor HALTs, all LTIs in the Primary rack go to Backup status and the Backup becomes Primary.
Page 33
30598-251-01 Page 33
APPENDIX D, EXAMPLE TRANSFER INTERFACE SYSTEM
D.1 General Information
This appendix illustrates a complete Transfer Interface System. To help stress fundamentals of the TIS. this example uses a simple configuration. Aciual applications may be more involved (i.c., with multiple LTIs). but the basic pringip 2 be same. The example system is
CPU A Rack CPU B Pack Siat # 1 2 3 4 5 4 2 3 4 6 Start -|- 1 - | - 1 Aatdress LTi LT} CPU A CRM CPU B CRM Model 7 Model 20 500 $00 Ead | | Address |, |, | 2008 ~ |, | 2008 ] RTC _| vo 2 I OROP #1 tO CHANN EL ) I CHANNEL RTI 123 Digital WO RIM) CRM (8 registers) 121 232 ‘l +1 n 8 1-1 thru 8-16 CPU A | CPU B
Figure 0.1, Example TIS
The above example consists of Model] 500 processors, one set of LT! modules, and one 1/O drop (with an RTI, Analog Input Module, and Digital 1/0).
D.2 Rack Addressing
Refer to] Figure D.]]and observe address assignments made, NOT™rarmtte matched LT] modules {connected by their RTCs) must have identical rack addressing.
CPU Rack
SLOT 1, The Model has not been assigned any internal registers. Recall that only LT] registers are transferrable.
SLOT 2, Slot 2 of a Model 500 is not allocated any address assignments.
SLOT 3, Although the LT! has 4096 registers available, the Model 500 can only address 2008 registers (Sl through $2008).
SLOT 4, §, No modules reside in these slots, address assignments are not required.
Addresses are now assigned to the I/O drop.
Channel 1, Drop #1
SLOT 1, To accommodate 128 digital 1/O points, eight 16-bit registers are required and assigned for the RTI (SI-! through S8-16).
SLOT 2, The analog input module requires four registers, therefore addresses S9 through $12 are assigned.
RTC (Channel 2, Drop #1)
Now that all external registers are assigned, the Register ‘Transfer Channel must be addressed.
Channel 2, Drop #1
SLOT 1, The next successive four registers ($13 through SI6) are assigned to the RTC.
The individual function of these four regisiers is defined as follows:
S13. Startup Transfer Register
$14, End of Scan Transfer Register
$15 -. Sean Synchronization Register
$16, Primary’ Backup Read. Write Bit Exchange Register
Internal Registers
The remaining registers assigned to the LT1 (S17 through $2008), are internal registers that may be used as timers, counters, interna] relays, etc. It is recommended that internal relays be located at addresses $17-S256 since only these are forceable.
If future expansion is a possibility, the registers expected to be required (beginning with Si?) should be set aside in the program in anticipation of their future use as externa] rgisters,
D.3 Programming
To operate the TIS, no special programming or register presetting is necessary, the TIS will default as follows:
*Startup Transfer Register All 4096 registers of the LT! (S13), (register default value of ©
*End of Scan Transfer Register (S14), No block of 32 registers designated due to register default value of 0. (Registers cannot transfer anyway un- less EOS TRANSFER
REGISTERS bit is set ON
Q)
Scan Synchronization Time- out Register (S15), 100 ms (register default value of 0)
FREEZE (S8162-9), OFF
TXFYT (88162-10), OFF (three transmission errors will be tolerated)
1/0 FAILURE OVERRIDE (S8162-13), OFF
1/0 AUTO RESTART (S8162-15}, OFF
RTC FAILURE OVERRIDE (S8161-13), OFF
TEST ({S8161-14), OFF
RE-SYNC (S8161-15), OFF
EOS TRANSFER REGISTERS (S8161-16}, OFF
*Cleared upon any LT] power-cycle. Other registers and bits are battery-backed.
Page 34
Page 34 30598-251-01
The LTI will default to the above conditions when it is initially powered up. If other than the default conditions are desired, the user must change the control register bits and the contents of the RTC registers. This can be done with the DATA mode of a programmer or through the ladder program itself.
For example, assume the TIS application requires the following conditions:
Startup Register Transfer, S! through S500
End of Scan Register Transfer, S?!7 through S48
Scan Synchronization Fimeout, i535 ms
RTC _ registers (Section 5.4)
FREEZE, OFF TXFT - OFF (Three transmission errors) I/O FAILURE OVERRIDE, ON LTI Control 1;O AUTO RESTART, ON Registers RTC FAILURE OVERRIDE -- OFF | (Appendix B)
TEST, OFF RE-SYNC, OFF EOS TRANSFER REGISTERS, ON |
Assuming the above functions are to be set by the ladder program (recommended method), the rungs listed in Figure [b.2Jar entered into both Primary and Backup programs.
e first three rungs enable the 1/O FAILURE OVER- RIDE, 1{O AUTO RESTART, and EOS TRANSFER REGISTERS functions. The last rung sets the RTC relative registers to obtain the desired number of START- UP TRANSFER registers. the correct range of END OF SCAN TRANSFER registers, and the desired SCAN SYNC TIMEOUT value.
APPENDIX E
E.1 Introduction And Description E.1.1 GENERAL INFORMATION
Errors detected by the processor and error codes annunciated on the CRT provide the operator with information useful in isolating problems.
Some errors are indicated as messages on the screen display while other error indications involve error code numbers. Since the messages are self explanatory, this appendix deals directly with the numbered error codes.
These error code numbers can be broken into two general] categories and are indicated in different locations on the CRT screen.
In the first category are the peripheral to PC system interaction errors of which three classifications of error codes exist. These errors are indicated at the bottom of the screen display or for some special cases, in the status register of a communications rung.
8162-13 ,\ | \ / }
+
1/0 FAILURE OVERRIDE 8162-15 _~ mers AUTO RESTART
8161-16
{i \ YF
EOS TRANSFER REGISTERS
-
Figure 0.2, Programming Rungs for TIS Requirements
LET $13 = §00;/17;15
D.4 TIS Startup
Once the TIS has been rack addressed and any special function rung ammed, the system is ready to RUN. [See Section 6.0] System Startup,
NOTE: When initially testing TIS hardware, we recommend the 1/0 AUTO RESTART and 1/0 FAIL- URE OVERRIDE BITs be reset OFF (0) If these bits are programmed ON as cails within the ladder program, the insertion of an OPEN circuit function will reset {turn OFF) the coils.
Assuming CPU A is required to be Primary, CPU B should be powered up first and tested. If the CPU B system tests OK, power it down and then apply power to CPU A. After the CPU A system has been powered up and running for at least ten seconds, reapply power to CPU B., ERROR CODES
In the second category are the PC system operational errors which are errors detected within the processor or any one of the modules contained in a programmable controller system. These errors are indicated in the STATUS Mode display next to the label ERROR NUMBER. The number displayed is also the number contained in the error code control register 8175 or possibly in a Locat Transfer Interface Module error code contro] register (when using remote 1/0).
E.1.2 PERIPHERAL TO PC SYSTEM INTERACTION ERRORS
These types of errors are associated with attempts to perform illegal operations with the processor or the communication hardware is not functioning properly. This category of error will only be generated when using the keyboard to command processor operations or when the processor is attempting communication with other re-sponding devices.
Page 35
The three classifications of peripheral to PC system interaction error codes are; Processor, Transmission, and Tape. When an error occurs while a programmer is connected to the processor, one of these messages will be shown on the display along with a number. Should an error occur during the execution of a processor communication rung a Processor Error will be used to indicate the fault. The number code will be shown when the status register of the communication rung is displayed.
Processor Errors
These errors indicate that the operation attempted was not successfully completed. The error code numbers range from 01 thru 99. To resolve the error situation, check the error code description in the following table, use the CLEAR key to clear the error indication if the error has been displayed on a programmer, and take the appropriate recourse action. Error codes indicated by an asterisk (*) in the following Error Code Table, may also be displayed in the status register of a communications rung.
30598-251-01 Page 35
PROCESSOR ERROR CODE TABLE
Error Code Error Description
No.
Ol* Mega] protocol opcode, the device does not recognize the instruction. Re-enter the desired operation.
02 Hlegal intermediate code format. Re-enter the desired operation.
03* An illegal address has been attempted.
04 Nlegal rack addressing has been attempted.
05* An instruction has been attempted which is not allowed in the processor. (Example: Square root in Model 300 processor.)
06 Item being searched for cannot be found.
07* An attempt has been made to alter data in a protected register. Check Contro! Register 8176.
08 An attempt has been made to access protected memory. Check Control Register 8176,
09* An attempt has been made to alter data ina READ only register or a register containing external inputs.
10 An attempt has been made to exceed memory limitations.
11* Communications error (receiver overflow). Re-enter the desired operation.
12 Ilegal CPU rack addressing; register assignments must be divisible by four.
13* Communications error (link error). This errer is generated by the processor. Check Control Register 8175 or the status register of the communication tung. Check cabie connections between devices.
14 The operation that has been attempted is not allowed in RUN.
15* Communication overflow. Check the baud rate for compatibility between communicating devices. Re-enter the desired operation.
16 The register count in a communication run is too large for the processor,
17* The remote device is inactive. This error cade is generated by the Network Interface Module, Check cable connections between devices.
18 The rung number used is not allowed.
{9* An illegal] READ parameter has been assigned.
20 An illegal channel number, or no channel number has been assigned.
2)* Trying to change a forced bit or WRITE to an external output while the processor is in HALT.
22 The forcing function is inhibited from the processor COMM port.
23* An attempt has been made to alter data in a fenced register.
Page 36
Page 36 30598-251-01 Error ] Error Code | Error Description Code Error Bescription No. | No. 24 An attempt has been made to force a nonforceable 56 Unused. _register. 57 Unused. 25* CPU error, check Contro! Register 8175. Refer to : . : 58 Unused. the following section on CPU; LI errors. ; U . 26 Rack Addressing and user memory overlap. 59 nused . 60 Iegal MARK number. GOTO or GOSUB with 27* Memory error, A CLEAR ALL operation is numbers above 8189 not allowed. required. - 2B An illegal baud rate was selected. 6l MARK ST. SUB rung cannot be inserted-append only allowed. 29* An attempt has been made to send a message with 62 RTN (return) rungs are not allowed in ladder area. an illegal route. 30 An attempt has been made to alter PROM memory 63 MAR K cumber previously uscd in the ee after the PROM inhibit coil wasentered in memory. ; . siruen ave a UniGU number assigned. * . 31 See Tape Errors. 64 Operation is no: allowed while the processor is in 32 Operation is not allowed in PROM memory (such RUN. Cannot delete a RTN if any GOSUB as inserting, deleting, or replacing a rung). contains the same MARK nember. 33* See Tape Errors. 65 Operation is nat allowed. Cannot delete MARK 34 For UVPROM processors only: Read after Write ST. SUB rung unless al] subroutines are deleted. error, parity error, or security jumper was removed 66 Operation is not allowed, cannot delete MARK and no UVPROM inhibit coil was programmed having an associated RTN (return). into memory. ~ G 67 Operation is not allowcd, RTN rungs must have 35* See Tape Errors. an associated MARK number. 36 Replace rung operations are not allowed on this 68 Operation is not allowed - only one RTN per rung. Use delete and insert operations only. MARK number is allowed. 37* See Tape Frrors. 69 Operation is not allowed while the processor is in 38 Unused RUN GOSUB cannot invoke a subroutine - “ having no RTN,
* d d > i i = * . * . . 39 Alarm already set within the D-LOG Module. 70 Operation is not allowed while the processor is in 40 Unused. RUN, GOTO rung cannot jump to a MARK 41* | An illegal register WRITE. The D-LOG Module having an associated RTN.
does not accept a register WRITE into certain 7] Operation is not allowed while the processor is in registers. RUN, cannot delete MARK untilal! GOSUBs or GOTOs with the same number are deleted. 42 Unused. ; ; ; ; 72 Operation is not allowed while the processor is in 43* N. ea ooeeted. has been attempted. D-LOG RUN, rung cannot have unused MARK number. oeule pre A GOTO or GOSUB with an undefined MARK is 44 Unused. not allowed. The MARK must be programmed 45* Operation is not allowed. D-LOG Module tape before the GOTO or GOSUB is programmed, Operation is in progress. 73 Unused. 46 Unused. 74 Unused. 47* Operation is not allowed due to keyswitch position. 75 Unused. 48 Programming of an MCR in subroutine area is not 76 Unused. allowed. 77 Unused. 49 1; Q, Register or Channel is safeguarded. | 78 Unused. 50 Rack Addressing is not alterable when forcing ts 79 Operation is not allowed when the processor 3s in : RUN while the Timed Interrupt is enabled. S1* A module is not seated properly or missing, or nu rack address assigned to the module, or the address exceeds the capability of the processor. $2 Unused. 53* See Tupe Errors. 54 legal MARK number. 55 See Tape Errors,
Page 37
Tape Errors
These errors are generated when performing tape operations. When the processor is operating with a Loader; Recorder through the use of communications rungs. the status register of that rung can be checked for the presence of an error condition.
Error Code Error Description No.
31* The end of the tape was encountered before the operation could be completed.
33* Tape Data Error detected, the block of data involved in the Read or Write operation was faulty.
35* The tape cartridge is not seated properly or is missing, or the “Record” tab on the cartridge has been set to the Write Inhibit position.
37* An attempt to Skip or Read a file was made when already past the last fle on the tape.
53* Illegal Tape Format, Erase Track Required.
55* Tape operation has been aborted. Retry the Operation,
Transmission Errors
Communication errors due to hardware problems are annunciated on the CRT screen by the message “Transmission Error” followed by a number.
The error code numbers that appear most frequently are numbers 1, 72, and 74. When an error such as this occurs, check al] cable connections and BAUD rates (Register $169), then use the CLEAR key to clear the error indication. When all connections are secure, retry the operation.
£.1.3 PC SYSTEM OPERATIONAL ERRORS
These error codes indicate PC system operational errors and consist of a five digit decimal value. These error codes or (ERROR NUMBERS) are the contents of the Control Register 8175 data field (bits 1-16). Seven possible classifications of operational error codes exist and they are:
30598-251-01 Page 37
The same operational errors are used by the Transfer Interface System to indicate errors in devices under its control. In this case, Register 8175 or the ERROR NUMBER in the CRT Status display will indicate the starting address of the I.ocal Transfer Interface which has the problem. Once located, inspection of the error control register inside the Local Transfer Interface will reveal which of the remote devices contains the error.
Refer to] Section E.2]for greater detail on using the error codes 10 isolate system faults.
CPU/LTI Error (30000-32700)
This error indicates a problem with either the processor (CPU) or Local Transfer Interface Module.
Ls{r[rlclo]| 4h 4 4
_ - - _ Drop Number Drop #0 indicates CPU or LTI error. Drop #>0 indicates Remote Interface Error
Channel Number
Channel 0 indicates CPU or LTI Error
Channel #>0 indicates
Remote Transfer Interface Error Type Error: 00 - 27
TT ERROR DESCRIPTION
ERROR
NUMBER TYPE OF ERROR 30000 - 32700 | CPU/LT] ERROR 29000 - 29999 | MISCELLANEOUS ERROR 20000 - 28192 | SLOT REGISTER ERROR 19000 - 19016 | SLOT ERROR 10000 - 18192 | READ AFTER WRITE ERROR 01000 - 09999 | PROCESSOR COMMUNICATION
PORT ERROR
00001 - 00999 | GENERAL ERROR
When an error condition occurs, the appropriate error code is loaded into Control Register 8175 only if the register contains zero or if it presently contains an error code of lower priority (a smaller number). The previous error code is then lost (if a Model 300) or moved to Register 8183 (if a Model 500 or 700).
00 Status Register Read} Write Parity Error 0) Image RAM Read; Write-Panty Error
02 Interna) Register Data Error
03 Iliegal PROM Format
04 Illegal Opcode Encountered in RUN
0s Bus Error Signal Error (Interrupt detected on Bus)
06 Software Watchdog Error
07 Not Used
08 Software Diagnostic Error
09 User Memory Read Write-Parity Error 10 Illegal Data in User Memory
H PROM Memory Corrupted
12 Illegal Addressing Map Code 13 Transmission Error Exceeds Tolerance 14 Loss of Transmission
15 More External 1.O Registers Assigned Than Module Can Handle
16 Too Many Registers Assigned to the Drop
17 Addressing More Drops than Channel can handle 18 Addressing Number of Channels Exceeded Module Capabilities
19 Addressing Map Checksum Error
20 Bus Error, Watchdog Time Out
2t BPU Diagnostic Error
22 Parity Circuit non-functional
23 Clear Line Error
24 Executive Scratch RAM Error
25 Watchdog Tolerance Error
26 Hardware Diagnostic Error
27 Module Inactive