3.4 RTI DIP Switches

The RTI module has six dip switches on the rear of the module near the edge of the circuit board. See Figure 3.3. Each RT1 module must be assigned as one of the eight drops on the LT! 1/O Channel. The swit et correctly for the system to operate properly. Sel Section 4.4] RTI DIP Switch Settings. Alsa, terminator switches mus set for the farthest drop on the channel. A onthe side of the module describes the switch settings. | See Figure 3.4.

Click here to view graphic.

Figure 3.3, RTI DIP Switches

30598-251-01 Page 9

NOTE: The Remote Transfer Interface DIP switches are the only hardware changes to be made by the user.

NOTICE: FOR PROPER OPERATION SWITCHES MUST BE SET CORRECTLY BEFORE INSERTING MODULE

OFF “y_ OFF ov We bas 123456

DROP X=ON-CLOSED-DWN SELECT O=OFF-OPEN-UP x % =NOT USED

+ m zz =

DROP z 9

& TERMINATOR SWITCHES:

A= CPU ACHWL. B- CPU B CHAL.

SET SWITCH ON FOR OROP AT END OF EACH DAISY CHAIN, ALL OTHER TERMINATOR SWITCHES OFF.

30608-406-01 cl cell cell Nace cel acl cell cs lh cel Maced Ncadl Uacel cel call Wael ae oleololo] |<] S/xlo!|«x|/o!| x/|o| = Me | He) Me | | HE] He | HE | He

DPN HN] el wl yo] O/O|x | x)o|/oO|™

Figure 3.4, RTI OIP Switch Labet

4.0 INSTALLATION

CAUTION

To prevent possible equipment damage, remove power from the CPU and all 1/O racks before inserting or removing any component (including the LTI or RTI modules or communication cables).

4.1 Inspection

Although each module is subjected to strict quality control procedures, it is always a good practice to give each module a quick visual inspection before installation, Check for any shipping damage that may have occurred.

Inspect the LEDs to ensure they are visible. Examine the field-wiring terminals for damage. Inspect the hold down screw on the bottom to verify the screw is securely attached to the module. Examine the upper rear of the module to ensure the mounting plate is secure. Inspect the printed circuit edge connector for damage.

4.2 Module Keying

Each register or CPU slot on a rack assembly may be keyed to accept only one type of module. An optional keying pin kit is available for this purpose, Class 8030, Type CBP-104. The keying pin may be inserted manually into the slot using the keying pin insertion too! provided with this kit. The correct positioning eving pin for the LTI module is between pins 92 and 94

) 1 ! ' (see Figure 4.1). uic.

There is no special keying pin location for the won wu ~

| _J, = KEYING PIN uf] nal ~ hs is [9 cs 2] 22 237] 24 es [=] a FI 29 [ a» L_ 334] 35 EAN] 36 KEYING a7 CT) ae 90 LOCATION =, FF oP 93 94 95 {| 36 Keying Pin | S7 98 eying Pin Insertion 99 = 100 ying

Keying Pin Location

Figure 4.1, Module Keying

CAUTION

When inserting or removing the keying pins, use care to avoid touching the contact fingers within the connector, Improper insertion/ removal may damage the connector,

Page 10 read from a scan by OCR; it may hold reading errors

Page 10 30598-251-01

4.3 Module Location 4.3.1 LOCAL TRANSFER INTERFACE

The Locat Transfer Interface (LTI) module must be placed in the same rack assembly as the Model 500 or 700 processor. The first LT] in a Transfer Interface system should be placed in the third stot of the register rack, though any slot is acceptable. Additional LTIs are placed in adjacent register slots.

4.3.2 REMOTE TRANSFER INTERFACE

The Remote Transfer Interface (RTI) module must be placed into the CPU slot (slot #1) of any rack which is to be a drop. Only one RTI is required and allowed for each drop.

4.4 Setting the RTI DIP Switches

Before putting an RTI into a rack assembly, set the DIP switches for correct operation. Fhe bank of six switches is accessible from the rear of the module. The switches are ON when they are set towards the PC board.

and S chauld be set according to the label on the (Figure 3.4)fto specify the drop number of the rack anne.

Switches 3, ¢ RTI module on the 1'O

Switches | and 2 are terminators which must be properly set to minimize the electrical interference on the communications link. For each LT] I/O Channel, the last RTL on the channel {the unit farthest along the link from the LTI) must have the terminator switch ON. Note that because the I/O Channel is sedundantly controiled, it is possible to use different wire routing from processor A and from processor B. Therefore, there are two terminator switches on the RTI, one for processor A (switch 2) and one for processor B (switch 1). All other RTIs on the channel must have the terminator switches OFF.

NOTE: Switch 6 is not used.

CAUTION

Before operating the Transfer Interface System, be sure that al] RTI DIP switches are set properly. Improper switch settings will cause unpredictable system operation,

4.5 installation in Rack Assembly

Power must be removed from the rack assembly before instal-ling or removing the Local or Remote Transfer Interface Modules.

After the removal of power, release the latching clamp and insert the module into the appropriate register slot until firmly seated against the stud located above the socket for the slot. Close the latching clamp and be sure to tighten the captive screw fo insure the module is secured and properly grounded. To remove the module, simply release the latching clamp, loosen the captive screw at the bottom and pull the module out of the slot using the finger tab located on the top of the module.

NOTE: Refer to the Planning and Installation Guide (1.B. 30598-175-XX) for proper grounding procedures.

4.6 Field Wiring

4.6.1 1/0 CHANNEL CONFIGURATION

The LTI's 1/O Channel mus_be wired ina daisy chain configuration to the RTS modules] Figure 4.2 illustrates this typical configuration. A “star” wiring configuration is not allowed any-where along the {{/O channel with the Transfer interface System.

Note that all LTIs in the CPU rack selected as CPU A must be connected to the CPU A channel of the RTIs. Likewise, LTIsin CPU B rack must be connected to the CPU 8 channel of the RTIs. There can be no intermixing: wiring from CPU A LTIs must nor be connected to any of the CPU B RTI terminals and vice versa,

NOTE: “CPU A” and “CPU B” terminals must be wired con-sistently for each drop (A to A and B to B). Otherwise the RTI will generate error code 29510 and not go to RUN, regardless of the state of the 1/O Failure Override bit. cPu | LT? cPu} UTI A 8 y y ake) to R R T AT Cc Cc l g ‘sy Py LRTI s l 4A ‘o > la ' fi A Oo ry t

'

Figure 4.2, 1/0 Channel Wiring Configuration 4.6.2 COMMUNICATION CABLE

The communication between modules of a Transfer Interface System takes place via a two pair, twisted, shielded cable. In order to minimize the potential of electrical interference:

1. Route communication cable in separate wire ducts, away from power wiring and electro-magnetic devices.

2. Connect each end of the communication cable shield to the SHD terminal on each device. Do not connect this shield to an external ground point since the SHD terminals are capacitively coupled to ground.

Follow all applicable electrical codes for wiring and communication cable routing.

Page 11 read from a scan by OCR; it may hold reading errors

Communication cable should be equivalent to Belden 8723. Using a cable with different specifications may cause unreliable operation.

The maximum communication distance for the Belden 8723 or equivalent cable is as follows:

Maxkmnum Length

2500 feet (762 m.)} 25 feet (7.6 m.)}

Communication Channe!

[/O Channel Register Transfer Channel

Because the Transfer Interface System uses redundant LTI-to-RTE communication cables, it is possible {and probably desirable) to route the two cables separately or in different wire ducts. This practice will minimize the chances of both communication cables being broken or damaged simultaneously.

NOTE: ADDITIONAL DATA LINE PROTECTION.

In environments where lightning or induced transients over communication lines are likely to cause communication fail-urés, signal line protection devices are recommended. Even though transient protection is designed into SY/ MAX communication circuits, additional specialized protection devices are suggested for communicati aLare exposed to the outside environment. Refer to Appendix G] Additional Data Line Protection, for recom Wiring scheme and protection devices.

Authoritative reference material which discusses the art and science of noise reduction and data line protection includes the ANSI/IEEE Std. 518-1982 as well as a book entitled Noise Reduction Techniques in Electronic Systems by Henry Ott (Wiley-Interscience 1976).

4.6.3 LTI/RTI CONNECTIONS

There are five terminals on the LT] and RTI modules for each communication link connection. These terminals are labeled 1, 2, 3, 4, and SHD.

The twisted-pair continuity of the communication cables must be maintained in the communication links {i.e.. Black with Red and Green with White for Belden 8723 cable). The RTC communication lip ach pair of LTI modules are connected together as in This distance is restricted to a maximum of 25 feet

*Note that for the RTC communication link, the wiring criss-crosses: terminals 1 & 2 of one LT] connect to terminals 3 & 4 of its matched LTI, and vice versa.

one twisted pair

LTLA tte *

R 16 bf 1 a c| 74 ae: 5] 3A ya |e N N L 4b Lf 4 L

Z / af sHD/ fsx |,

Z ome twisted pair

Figure 4.3, RTC Channel: LTI-to-LTI Connections

30598-251-01 Page 11

The 1/O communication link betwen the LT1s and RTIs is wired as shown in [Figure 44] A maximum of two communications wires SWoula oe connected to each RTI terminal since each RTI in the daisy chain should be wired to the next RTI “straight through.”

Note that for the }‘O communication link, the wiring is direct: there is no crisscrossing.

one twisted pair

Ltt ATI RTI 1 u / $4 ‘ 7 } 22 () 2 / yg Up to 0 Ay 7 2 Eight c "Dro af 3 “a / Ps tN id / () 7 3 Total L 4 af 4 / 7 Jj 4 Z SHD / 1 | sHOS / SHO if : une twisted pair

Figure 4.4, RTC Channel; LTI-te-RTI Connections 4.7 Power Supplies

The Transfer Interface System (TIS) will continue to keep the programmable controller system running if there is a fault in either the Primary or Backup CPU rack power supplies. To enable the TIS to withstand such a fault, each CPU rack must be powered by a separate power supply. To further insure redundancy, power supplies can be connected to separate branch circuits. In addition we recommend that a CPU rack power supply should mor be used to power any other rack assemblies,

Ideally, to promote redundancy the processors and I/O racks should be on three (or more) separate branch circuits; otherwise they should all be on the same circuit. If one processor is on the same circuit as some of the remote racks and that circuit should lose power, this will defeat the purpose of redundant processor control.

For additional reliability, redundant SY / MAX power supplies may be used to power each respective rack. This feature is available by utilizing two PS-1], -21, or -31 Power Supplies with a CC-51 redundant cable. Refer to Power Supply instruction bulletin 30598-159-01 or later for additional information.