Page 1

RM14K Manual

RM14K Installation and Programming Manual

This Manual describes the RM14K Industrial Modem, its uses and set up. It also describes the use of the RM14K configuration software.

Effective: 31 July, 2001

Niobrara Research & Development Corporation P.O. Box 3418 Joplin, MO 64803 USA Telephone: (800) 235-6723 or (417) 624-8918 Facsimile: (417) 624-8920 Internet: http://www.niobrara.com

Page 2

SY/MAX, SY/NET, and Square D are registered trademarks of Square D Company. PowerLogic is a trademark of Square D Company. Allen-Bradley, A-B, and Data Highway are trademarks of Allen-Bradley Company. MODBUS is a trademark of AEG Modicon Company. PanelMate is a trademark of EATON IDT. Subject to change without notice.

© Niobrara Research & Development Corporation 1995-2001. All Rights Reserved.

Page 3

Contents

1 Introduction ....................................................................................................................... 13 Specifications ............................................................................................................... 14 Module Specifications ........................................................................................... 14 Modem Specifications ........................................................................................... 15

2 Installation ........................................................................................................................... 17 Module Installation ....................................................................................................... 17 RM14KSW Software Installation ................................................................................ 18 Serial Connection to the RM14K ................................................................................. 18 LINE Connection to RM14K ....................................................................................... 21 Dial-up Connection ............................................................................................... 21 Four Wire Connection ........................................................................................... 22 Two-Wire Connection ........................................................................................... 22

3 Operation ............................................................................................................................. 23 Memory Configuration ................................................................................................. 23 Command and Status Bits ............................................................................................ 24 Bit 1 (Dial, DCD) .................................................................................................. 24 Bit 2 (RTS, CTS) ................................................................................................... 24 Bit 3 (P-T-P, Multidrop) ........................................................................................ 25 Bit 4 (SY/MAX, Transparent) ............................................................................... 26 Bit 5 (Auto Answer) .............................................................................................. 26 Bit 6 (Push to Talk) ............................................................................................... 26 Bit 7 (Watch Dog, Dial Input) ............................................................................... 26 Bits 8 and 9 (Port Parity) ....................................................................................... 27 Bit 10 and 11 (Line Parity) .................................................................................... 27 Bit 12 (Port Checksum) ......................................................................................... 27 Bit 13 (Line Checksum) ........................................................................................ 28 Bit 14 (Dial-up, Leased Line) ............................................................................... 28 Bit 15 (Leased Line 2 or 4 Wire, PSTN Off Hook) .............................................. 28 Bit 16 (Ring Indicator) .......................................................................................... 28 Baud Rate ..................................................................................................................... 29 Phone Number Storage ................................................................................................. 30 Error Register R[6] ....................................................................................................... 32 Rack Addressing ........................................................................................................... 32 I/O Direction ......................................................................................................... 33 Configuration in SY/MAX Mode ................................................................................. 33

3

Page 4

Drop 201 ................................................................................................................ 34 Drop 202 ................................................................................................................ 34 Drop 206 ................................................................................................................ 34 Configuration in Transparent Mode ............................................................................. 34 AT Commands (PSTN mode only) ....................................................................... 34 Dialing String Characters ...................................................................................... 35 S Registers ............................................................................................................. 36 Front Panel Control Inputs ........................................................................................... 36 Hayes Switch ......................................................................................................... 36 SY/MAX Switch ................................................................................................... 37 Orig Switch ........................................................................................................... 37 Ansr Switch ........................................................................................................... 37 Cnct Switch ........................................................................................................... 37 Hangp Switch ........................................................................................................ 37 DIAL Input ............................................................................................................ 37 Push-to-Talk Relay Output ........................................................................................... 38 PSTN Operation ........................................................................................................... 38 PSTN Connector ................................................................................................... 38 PHONE Connector ................................................................................................ 38 Multidrop Operation .............................................................................................. 39 Leased Line Operation ................................................................................................. 39 LL TX Port ............................................................................................................ 39 LL RX Port ............................................................................................................ 40 Four Wire Point-to-Point Operation ...................................................................... 40 Two Wire Point-to-Point Operation ...................................................................... 40 Multidrop Operation .............................................................................................. 40 Multidrop Tuning Parameters ............................................................................... 41 Radio Operation ........................................................................................................... 41 Password Security Operation ....................................................................................... 41 Caller Station Identification .................................................................................. 43

4 Configuration Software RM14KSW ................................................................ 45 Data Entry Keys ........................................................................................................... 45 Main Menu ................................................................................................................... 46 oNline ........................................................................................................................... 46 Communication Mode ........................................................................................... 47 Connection Type ................................................................................................... 48 Auto Answer ......................................................................................................... 48 Answer on ring ...................................................................................................... 48 Wait for Dial Tone ................................................................................................ 48 Wait for Carrier ..................................................................................................... 48 Port BPS ................................................................................................................ 48 Port Parity .............................................................................................................. 48 Port Error Check .................................................................................................... 49 Line BPS ............................................................................................................... 49 Line Parity ............................................................................................................. 49 Line Error Check ................................................................................................... 49 Watchdog mode ..................................................................................................... 49 Number Pointer ..................................................................................................... 49 Dial String ............................................................................................................. 50 Comma pause time ................................................................................................ 50 DTMF digit length ................................................................................................ 50 Hayes Escape char ................................................................................................. 50 Guard Time ........................................................................................................... 50 Hayes CR char ....................................................................................................... 50

4

Page 5

Hayes LF char ....................................................................................................... 50 Hayes BS char ....................................................................................................... 50 CTS On delay ........................................................................................................ 50 CTS Off delay ....................................................................................................... 50 Carrier detect ......................................................................................................... 51 Answer password .................................................................................................. 51 Last password received ......................................................................................... 51 Status Displays ...................................................................................................... 51 Error Displays ....................................................................................................... 51 Hot Keys ................................................................................................................ 52 oFfline .......................................................................................................................... 52 Read from disk to memory .................................................................................... 53 Write from memory to disk ................................................................................... 53 Edit configuration in memory ............................................................................... 53 Send configuration to module ............................................................................... 53 Fetch configuration from module .......................................................................... 53 Print configuration in memory .............................................................................. 53 Delete configuration file ........................................................................................ 54 Quit offline functions ............................................................................................ 54 Utility ............................................................................................................................ 54 View registers ....................................................................................................... 54 Signal Strength ...................................................................................................... 55 Terminal Emulator ................................................................................................ 55 Lead Monitor ......................................................................................................... 56 Connect or Hangup ................................................................................................ 57 SETUP .......................................................................................................................... 57 SY/MAX SETUP .................................................................................................. 57 Personal Computer COM: port ............................................................................. 58 SY/LINK Connection ............................................................................................ 59 SFI-610 Connection .............................................................................................. 60 Terminal Emulator SETUP ................................................................................... 60 Command Line Parameters .......................................................................................... 61 Other Included Software ............................................................................................... 61 DIAL.EXE ............................................................................................................. 61 HANGUP.EXE ..................................................................................................... 62 NRDMODE.EXE .................................................................................................. 62 NRDTERM.EXE ................................................................................................... 62 ZAPREG.EXE ....................................................................................................... 63 ZAPREG SY/LINK Connection ........................................................................... 64 ZAPREG SFI-610 Connection .............................................................................. 65

5 Dial-up 11 Bit SY/MAX Examples .................................................................... 67 PC RM14K to Processor RM14K ................................................................................ 67 Dialing from the Cnct Switch ................................................................................ 69 Dialing with a Telephone ...................................................................................... 70 Dialing from the PC .............................................................................................. 70 Online Operation ................................................................................................... 70 Manual Hang-up .................................................................................................... 70 Hanging up from the PC ........................................................................................ 71 PC RM14K to NIM RM14K ........................................................................................ 71 Dialing ................................................................................................................... 71 Online Operation ................................................................................................... 71 Disconnecting ........................................................................................................ 72 PC SY/LINK RM14K to NIM RM14K ....................................................................... 72 Dialing ................................................................................................................... 73

5

Page 6

Online Operation ................................................................................................... 73 Disconnecting ........................................................................................................ 73 Processor RM14K to Processor RM14K ...................................................................... 74 Local RM14K Setup .............................................................................................. 75 Remote RM14K Setup .......................................................................................... 75 Model 400 Dialing ................................................................................................ 76 Model 400 Initiated Communication .................................................................... 76 Model 400 Disconnecting ..................................................................................... 76 Model 300 Dialing ................................................................................................ 76 Model 300 Initiated Communication .................................................................... 77 Model 300 Disconnecting ..................................................................................... 77 NIM RM14K to NIM RM14K ..................................................................................... 77 Originating RM14K Configuration ....................................................................... 77 Answering RM14K Configuration ........................................................................ 78 EPE5 RM14K to EPE5 RM14K .................................................................................. 78 Originating RM14K Configuration ....................................................................... 79 Answering RM14K Configuration ........................................................................ 79 RM14K to 2496X ......................................................................................................... 80 2496X Configuration ............................................................................................. 80 RM14K Configuration .......................................................................................... 81 RM14K to 1296X ......................................................................................................... 82 EPE5 (SPE4) PLOGIC to PowerLogic CM ................................................................. 82 Local RM14K Setup .............................................................................................. 82 Remote RM14K Setup .......................................................................................... 82 Personal Computer to PowerLogic CM ....................................................................... 83 Personal Computer SMS-770 Setup ...................................................................... 83 Local RM14K Setup .............................................................................................. 83 Remote RM14K Setup .......................................................................................... 84

6 Dial-up 10 Bit SY/MAX Examples .................................................................... 85 PC Hayes to Processor RM14K ................................................................................... 85 Hayes Modem Setup ............................................................................................. 86 Remote RM14K Configuration ............................................................................. 86 Dialing from the PC .............................................................................................. 87 Online Operation ................................................................................................... 87 Hanging up from the PC ........................................................................................ 87 PC RM14K to NIM RM14K ........................................................................................ 87 Dialing ................................................................................................................... 88 Online Operation ................................................................................................... 88 Disconnecting ........................................................................................................ 88 PC SY/LINK RM14K to NIM RM14K ....................................................................... 88 Processor RM14K to Processor RM14K ...................................................................... 88 Local RM14K Setup .............................................................................................. 89 Remote RM14K Setup .......................................................................................... 89 Model 400 Dialing ................................................................................................ 89 Model 400 Initiated Communication .................................................................... 91 Model 400 Disconnecting ..................................................................................... 91 Model 300 Dialing ................................................................................................ 91 Model 300 Initiated Communication .................................................................... 91 Model 300 Disconnecting ..................................................................................... 91 NIM RM14K to NIM RM14K ..................................................................................... 91 EPE5 RM14K to EPE5 RM14K .................................................................................. 91 RM14K to 2496X ......................................................................................................... 91 2496X Configuration ............................................................................................. 91 RM14K Configuration .......................................................................................... 92

6

Page 7

RM14K to 1296X ......................................................................................................... 93 1296X Configuration ............................................................................................. 93 RM14K Configuration .......................................................................................... 93

7 Dial-up Transparent Examples ............................................................................ 95 PNIM to PowerLogic CM ............................................................................................ 95 Local RM14K Setup .............................................................................................. 95 Remote RM14K Setup .......................................................................................... 96 EPE5 (SPE4) PNIM to PowerLogic CM ..................................................................... 96 Local RM14K Setup .............................................................................................. 96 Remote RM14K Setup .......................................................................................... 97 EPE5 (SPE4) to Micro-1 .............................................................................................. 97 Local RM14K Setup .............................................................................................. 97 Remote RM14K Setup .......................................................................................... 98 EPE5 (SPE4) to Model 50 ............................................................................................ 98 Local RM14K Setup .............................................................................................. 98 Remote RM14K Setup .......................................................................................... 99 PC to Micro-1 ............................................................................................................... 99 PC to Model 50 ........................................................................................................... 100 PC to BBS .................................................................................................................. 101

8 Leased Line SY/MAX Examples ....................................................................... 103 Processor to Processor ................................................................................................ 103 Local RM14K Setup ............................................................................................ 103 Remote RM14K Setup ........................................................................................ 104 Model 400 Initiated Communication .................................................................. 104 NIM RM14K to NIM RM14K ................................................................................... 105 Originating RM14K Configuration ..................................................................... 105 Answering RM14K Configuration ...................................................................... 106 EPE5 RM14K to EPE5 RM14K ................................................................................ 106 Originating RM14K Configuration ..................................................................... 107 Answering RM14K Configuration ...................................................................... 107 EPE5 (SPE4) PLOGIC to PowerLogic CM ............................................................... 108 Local RM14K Setup ............................................................................................ 108 Remote RM14K Setup ........................................................................................ 109 RM14K to 2496X ....................................................................................................... 109 RM14K to 1296X ....................................................................................................... 109

9 Leased Line Transparent P-T-P Examples ............................................... 111 PNIM to PowerLogic CM .......................................................................................... 111 Local RM14K Setup ............................................................................................ 111 Remote RM14K Setup ........................................................................................ 112 EPE5 (SPE4) PNIM to PowerLogic CM ................................................................... 112 Local RM14K Setup ............................................................................................ 112 Remote RM14K Setup ........................................................................................ 113 EPE5 (SPE4) to Micro-1 ............................................................................................ 113 Local RM14K Setup ............................................................................................ 113 Remote RM14K Setup ........................................................................................ 114 EPE5 (SPE4) to Model 50 .......................................................................................... 114 Local RM14K Setup ............................................................................................ 114 Remote RM14K Setup ........................................................................................ 115

7

Page 8

10 Multidrop Examples .................................................................................................. 117 Carrier Control ........................................................................................................... 117 RTS/CTS Push to Talk ........................................................................................ 117 Backplane Carrier Control .................................................................................. 118 RNIM Example .......................................................................................................... 118 RM14K Configuration ........................................................................................ 119 RNIM Configuration ........................................................................................... 120

11 Connector Pinouts ....................................................................................................... 121 RS-422 ports on RM14K (DE9S with slide lock posts) ...................................... 121 PSTN RJ11 Connector ........................................................................................ 122 PHONE RJ11 Connector ..................................................................................... 122 LL TX RJ11 Connector ....................................................................................... 122 LL RX RJ11 Connector ....................................................................................... 122

12 Recommended Cabling ............................................................................................ 123 Cabling required to configure an RM14K .................................................................. 123 RM14K to personal computer cabling ................................................................ 123 Cabling required to connect the RM14K port to an external device .......................... 124 RM14K RS-422 to SY/MAX RS-422 port (Without Handshaking) .................. 124 RM14K RS-422 to SY/MAX RS-422 port (With Handshaking) ....................... 124 RM14K RS-422 port to PowerLogic RS-485 (4-wire Multidrop Master) .......... 125

13 Troubleshooting ............................................................................................................ 127 Step 1 - RM14K Lights and Sounds .................................................................... 127 Step 2 - Communicating to the Modem .............................................................. 128 Last Step - Reset the Modem .............................................................................. 129 Statistics Registers ...................................................................................................... 129 General Module Information ............................................................................... 129 Port and Line Information ................................................................................... 132

Appendix A Federal Communications Commission Radio Frequency Interference Statement ............................................................................. 135 FCC Requirements: .................................................................................................... 135 Service Requirements ................................................................................................. 136 DOC Notification and Repair Information ................................................................. 136

Appendix B Serial Communication Overview ................................. 137 Hardware Overview .................................................................................................... 137 RS-232 ................................................................................................................. 137 RS-422 ................................................................................................................. 142 RS-485 (four wire) .............................................................................................. 143 RS-485 (two wire) ............................................................................................... 143 20mA Current Loop ............................................................................................ 144 Hardware Handshaking .............................................................................................. 145 Software Overview ..................................................................................................... 146

8