Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 5 of 17

RM14K Installation and Programming Manual, pages 39 to 48

Pages 39 to 48 of 164

The original document is the PDF (600 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Square D 8030 CRM-510 and Schneider 8030 CRM-510

Page 39

Table 3-15 PHONE Port Pinout Pin

Function

1

No Connection

2

Switched Line Connection

3

Switched Line Connection

4

No Connection

PHONE

Pin 1 Pin 2 Pin 3 Pin 4

Figure 3-2 PHONE Connector

Multidrop Operation Multidrop operation is not allowed in PSTN mode. If the modem is in PSTN mode and the multidrop bit is set, it will be ignored and Error bit 3 will be set. If the modem is in Multidrop mode (leased line) and the PSTN mode is selected, Multidrop mode is canceled.

Leased Line Operation Leased line operation of the RM14K is available in four wire point to point, two wire point to point, and two wire multidrop.

Warning: The leased line should be "dry", that is to say it should have 0Vdc across the pair. If the line is "wet" and has 48Vdc across the pair, the RM14K’s internal transformers will become saturated leading to communication difficulties and possible damage to the modem. NOTE: The Private Line connection should be made using the LL TX port and the included JM8 connector. LL TX Port The LL TX Port contains connections for audio transmit and audio receive. The port pinout is shown in Table 3-16 and Figure 3-3. The middle pair of pins 2 and 3 provide the Audio Output in Four Wire mode and the bi-directional half-duplex connection in 2 wire mode.

Table 3-16 LL TX Port Pinout Pin

Function

1

RX (Audio IN from external device)

2

TX (Audio OUT to external device)

3

TX (Audio OUT to external device)

4

RX (Audio IN from external device)

LL TX

Pin 1 Pin 2 Pin 3 Pin 4

Figure 3-3 LL TX Connector

RM14K Manual

3

Operation 39

Page 40

LL RX Port The LL RX port contains connections for the Audio Receive lines from the external device for four wire operation. These lines are physically connected to Pins 1 and 4 of the LL TX port to allow option of using both ports or only the LL TX port. Table 3-17 LL RX Port Pinout Pin

Function

1

No Connection

2

RX (Audio IN from external device)

3

RX (Audio IN From external device)

4

No Connection

LL RX

Pin 1 Pin 2 Pin 3 Pin 4

Figure 3-4 LL RX Connector

Four Wire Point-to-Point Operation In leased line operation utilizing a four wire circuit, the TX pair of one modem is connected to the RX pair of the other modem. Four wire mode is selected by setting bit 14 and clearing bit 15 in R[1]. SY/MAX and Transparent modes are both available in four wire, point-to-point operation. Four wire mode is a full duplex configuration. One modem must be set for Originate and the other modem must be set for Auto Answer. As soon as the physical connection is made and the modem is placed in four wire, leased line, point-to-point modes the modems will negotiate for carrier. There is no need to issue the connect command. If carrier is ever lost, the originating modem will immediately try to initiate carrier again.

Two Wire Point-to-Point Operation In leased line operation utilizing a two wire circuit, the TX pair of one modem is connected to the TX pair of the other modem. Two wire mode is selected by setting bits 14 and 15 in R[1]. SY/MAX and Transparent modes are both available in two wire, point-to-point operation. Two wire point-to-point mode is a full duplex configuration. One modem must be set for Originate and the other modem must be set for Auto Answer. As soon as the physical connection is made and the modem is placed in two wire, leased line, point-to-point modes the modems will negotiate for carrier. There is no need to issue the connect command. If carrier is ever lost, the originating modem will immediately try to initiate carrier again.

Multidrop Operation Multidrop operation is only available in Transparent leased line mode. Multidrop mode is selected by setting bits 3, 4, 14, and 15 in R[1]. The modems are connected together by means of an audio hub, usually provided by the telephone company. This hub will provide proper termination for each modems on the network. Multidrop mode is a half duplex configuration. Each modem will automatically be set to Originate mode once Multidrop is selected.. The modem which receives RTS (from the RS-422 port or bit 2 of R[1]) first will initiate carrier. Once carrier is achieved, CTS on that modem will be asserted to allow the attached device to transmit. All other modems on the multidrop network will receive the data and pass it out their RS-422 ports. Once the originating device finishes sending its data, it must negate its RTS, causing all modems to drop carrier. Active RTS/CTS push-to-talk handshaking lines are required on the attached devices. It is not possible to SY/MAX processors directly to multidrop RM14Ks; devices such as an RNIM, SPE4, EPE5, or UCM4 with push-to-talk handshaking must be employed. There must not be a PSTN connection while in Multidrop, Two Wire configuration. The PSTN connection will be OFF HOOK at all times.

40 Operation

3

RM14K Manual

Page 41

Multidrop Tuning Parameters The Multidrop mode has special registers for tuning parameters that may require adjustment. These registers are listed in Table 3-18, and may only be monitored and modified by setting the RM14K to SY/MAX mode and routing with the 201, 202, or 206 drop. Table 3-18 Multidrop Tuning Registers Register

Function

2049

Carrier Detect threshold

2050

CTS turn on delay

2051

CTS turn off delay

Unit

Valid Range

Default Value

0..3

2

277uS

0..255

100

277uS

0..255

100

Increase the carrier detect threshold if carrier detect goes active when no unit is transmitting. Increase the CTS turn on delay if data is lost at the beginning of the packet. Increase the CTS turn off delay if data is lost at the end of the packet.

Radio Operation Radio operation is accomplished with Multidrop mode. The LL TX is connected to the Audio IN on the radio and the LL RX is connected to the Audio OUT of the Radio. The RM14K’s PTT relay is connected to the Radio’s PTT input. The RM14K is designed for use in a 600 ohm impedance circuit. All units on the network are in originate mode. The unit that gets its RTS asserted first will enable its PTT relay, wait for a specific time to allow the radio to obtain carrier, and then assert CTS to allow the device to transmit. Once the device is finished transmitting, it drops RTS and the modem opens the PTT relay allowing the radio to drop carrier. All units on the network receive the data transmitted from each other modem. This feature, as well as the needed RTS/CTS functionality, usually requires some additional networking equipment such as an RNIM, EPE5, or SPE4 module. The multidrop tuning parameters in Table 3-18 may be used for fine tuning radio applications.

Password Security Operation There are people out there with computers programmed to dial numbers sequentially, searching for modems and other automated system. When they find something, the computer repeatedly tries passwords. This is especially a problem when a phone line can be reached by calling a toll-free number. Although chances of such a person figuring out how to program a SY/MAX PLC by trial and error are probably low, a little caution can’t hurt anything. Password security allows PSTN access to a system via the RM14K to be restricted to authorized users. The modem can be programmed to require a four digit password to be dialed before it will emit answer tone and connect to the originating modem. The password can be supplied either manually with a tough-tone phone or as part of the origination modem’s dial string. Dial-up password security is enabled by setting register 7 to a non-zero number. When enabled, this register is interpreted as a four digit hex password. When the RM14K receives an inbound call and password security is enabled, it answers with a beep and then waits for the four digit password to be dialed. If the password matches, the modem proceeds with the data answer tone and handshake sequence. If a mistake is made in manually dialing the password, enter the correct number. The modem looks at the last four digits keyed. DTMF digits 0 through 9 are encoded as hex digits 0 through 9 respectively. DTMF digits * and # are encoded as hex A and B respectively. DTMF digits A, B, C, and D are encoded as hex digits C, D, E, and F respectively. Register 8 holds the digits as they are received in real time. Therefore it will show the last password dialed. The DTMF digit D is a special digit that will cause the RM14K to immediately go on-hook when it is received. This is a special feature to allow daisy chaining of multiple modems to a single telephone line.

RM14K Manual

3

Operation 41

Page 42

Register 8 is initialized to hex FFFF when the modem goes off hook. Because of this, the modem may be configured to accept fewer than four digits by setting the leading digits of register 7 to hex F. The modem waits 10 seconds for a valid password before hanging up. The ring to answer on (register 8000) can be set to a large number to restrict how often a break-in attempt is allowed to be repeated. The hex character F can be used as a wild-card character to allow multiple remote units to gain access to a local site and still retain unique identification. For example, if the local RM14K has a password set for 00FF (hex), up to 255 remote units could call in and get carrier. Units such as: 0000, 0001, 0002, 001A, 00CC could call in. This feature is very useful for PowerLogic applications where the remote Circuit Monitor has an alarm and dials up a central station where System Manager is online with its own RM14K. It should be noted that, even with this feature, it is possible to break into a remote system by repeated calling and iteration passwords. If desired, additional security can be implemented in the PLC ladder program. For instance, the PLC could monitor unsuccessful calls and disabling the modem’s autoanswer if a certain count is exceeded. If an RM14K is doing the dialing, there are four more DTMF digits available. RM14K dialing digits A, B, C, and D translate to password hex digits C, D, E, and F respectively. These digits do not appear on most telephone dials. A password should not start with hex F (DTMF D) since the last three digits alone would be also recognized. Also note that the DTMF D character will cause the RM14K to hangup when it receives that character. The RM14K includes a special character "W" in the dialing string that waits for the beep from the answering RM14K before sending the password. In the following example the number to dial is (417) 555-4189 and the password is DTMF 30A*. This information will be stored starting in R[10] in the RM14K. The dialing string would be as follows: 14175554189W30A* and the RM14K registers would look like Table 3-19.

Table 3-19

Password Dialing Example

RM14K Register

Value (hex)

Value (decimal)

Value (ASCII)

R[10]

3134

12596

14

R[11]

3137

12599

17

R[12]

3535

13621

55

R[13]

3534

13620

54

R[14]

3138

12600

18

R[15]

3957

14679

9W

R[16]

3330

13104

30

R[17]

432A

17194

C*

R[18]

0000

0

If the automatic call continuation feature is used in the dialing string, it is simply added to the beginning of the dialing string. If in the above example, the alarm condition warranted the continued dialing of the remote site until a connection is established the string would appear as follows: [10]14175554189W30C* and the RM14K registers would look like Table 3-20. The RM14K would dial the above number over and over until carrier is obtained.

42 Operation

3

RM14K Manual

Page 43

Table 3-20 Password Dialing with Continuation RM14K Register

Value (hex)

Value (decimal)

Value (ASCII)

R[10]

5B31

22345

[1

R[11]

305D

12381

0]

R[12}

3134

12596

14

R[13]

3137

12599

17

R[14]

3535

13621

55

R[15]

3534

13620

54

R[16]

3138

12600

18

R[17]

3957

14679

9W

R[18]

3330

13104

30

R[19]

432A

17194

C*

R[20]

0000

0

Caller Station Identification The password security feature may also be used for caller identification. Consider a master station with an RM14K and several remote stations, each with an RM14K. The master station’s RM14K is programmed for the password AAAA. Each remote station’s dialing string is programmed with the phone number of the master station, a comma, and a unique four digit password, say, 1001, 1002, 1003, 1004, etc. If an alarm condition occurs at a remote station causing it to dial the master station, the PLC at the master station will be able to look at the Last Password Received register, R[8], and immediately know which remote station is calling. If the incoming password matched one of its known stations, the PLC could copy R[8] to R[7] and the RM14K would immediately answer the call. This type of caller identification is especially useful in Transparent application where the remote device is disabled and the Watchdog feature of the remote RM14K is used to call in the alarm. A more convenient method for caller ID is to use the F wildcard character in the password string. In the above example, the local RM14K could have the password 100F. This would allow units 1000, 1001, 1003,...100B, 100C to be able to dial in and connect without PLC interference. If more remote units were present, simply change the local password to 10FF or 1FFF. Note: If the password is set to FFFF, the RM14K will answer regardless of the incoming password. So be careful.

RM14K Manual

3

Operation 43

Page 44

This page is a scan with no text; see it in the PDF.

Page 45

4 Configuration Software RM14KSW

The RM14KSW software program is provided free of charge to RM14K users. This software is used to help configure the operation of the RM14K. RM14KSW is primarily intended for use with the RM14K in SY/MAX mode. With the proper routing, an RM14K may be configured from the RS-422 port as well as through the Line port. For Transparent applications (Hayes mode) the included Terminal Emulator may be used for sending Hayes "AT" commands.

Data Entry Keys Whenever data entry is allowed by the program, certain keys can be used to facilitate data entry. They are: BACKSPACE

Move cursor left and remove character there

LEFT ARROW

Move cursor to the left one character

RIGHT ARROW

Move cursor to the right one character

DEL

Remove the character under the cursor

INS

Change between insert and overstrike modes of entry

HOME

Move cursor to the left edge of the field

END

Move cursor to the end of the data

Control-F

Move cursor right (Forward) one word

Control-R

Move cursor left (Reverse) one word

Control-D

Delete from the cursor to the end of the field

Control-U

Delete from cursor to the beginning of the field

Control-Y

Delete all characters in the field

ESC

Exit the field without modifying it

ENTER

Accept the contents of the field

When a field is opened for input, the cursor is positioned at the left side of the field. If data is already present in the field, typing any character other than those listed above will cause the field to be blanked allowing entry of new data without first deleting the old. If it is desired to retain the previous data for editing, make sure the first key you type is an editing key such as a left or right arrow.

RM14K Manual

4 Configuration Software RM14KSW 45

Page 46

Main Menu The startup screen of RM14KSW is shown in Figure 4-1. The operational modes are selected by the highlighted menu bar on the fourth line. Selection can be made by moving the cursor to the desired option using the arrow keys and pressing ENTER. A short cut is provided, simply type "N" for oNline, "F" for oFfline, "U" for Utility, "S" for setup or "Q" to quit.

Figure 4-1 Main Menu Screen oNline The oNline selection provides a direct connection to the settings in an RM14K modem. Upon selection of oNline, RM14KSW attempts to connect to the RM14K using the Setup parameters defined in the Sy/Max Setup menu. For oNline to function properly, all setup parameters must be correct for the equipment used including the baud rate, parity, checksum, and route. It is very important that the route be set with the last drop to be 201 if connected to the RS-422 port of the RM14K or 202 if the connection is to be made via the Line port, or 206 if traveling through multiple RM14Ks.. The RM14K must also be set for SY/MAX mode to function with the oNline routine. For more information on the Sy/Max Setup parameters see page 45. Once RM14KSW has been able to connect to an RM14K, the screen should look something like Figure 4-2. The TX and RX lights under the RS-422 port will be flashing an the small line in the upper right corner of the screen should be spinning. While oNline, RM14KSW is continuously polling the RM14K and displaying the parameters on the screen. If any parameters are changed, the effect will be immediate and the modem will react according to the change. It is important to realize this, as changes made to parameters such as the mode, parity, baud rate, etc. may result in the loss of communication to the modem. The device connected to the modem will then need to be adjusted to match the new setting on the modem. Notice - The values displayed while oNline relating to the Command Register (Parity, Checksum, Connection type, Watchdog, Communication Mode, etc.) are the values that the RM14K presents in its Status Register R[2]. Certain mode settings do not take immediate effect upon issuance of the command. For instance, if the modem is connected (has Carrier) on PSTN, changes made to the Line Baud, Parity, and Checksum will not take affect until the connected is broken and re-established.

46 Configuration Software RM14KSW

4

RM14K Manual

Page 47

Figure 4-2 oNline Screen The block cursor is moved about the screen using the arrow keys on the keyboard. Individual parameters may be modified by toggling through the permitted parameters using the -. +, and space bar. Parameters requiring direct value entry, such as the Dial string, may be edited with the commands listed on page 45. The various commands are described as follows. Notice - The RM14K command register responds to changes of state from its various inputs: RS-422 port, Line port, backplane, toggle switches, and Dial input. If for instance the oNline screen F7 hot key is used to dial the modem bit 1 of the command register will be set. If the hang-up switch is toggled from the front panel, the modem will go on hook but bit 1 will remain set. If F7 is pressed again from oNline, the modem will not go off hook as bit 1 is already set. Bit 1 must be cleared before F7 will work again. This may be accomplished by pressing F8 for hang-up while oNline, or using the Hangup Utility, or by manually clearing the bit in the View Registers Utility. This "change of state" latch will be apparent in other command register parameters such as the SY/MAX-Transparent mode bit.

Communication Mode This value controls the protocol to which the modem responds. The two options are SY/MAX and Transparent. The default value is SY/MAX. In order to use RM14KSW to configure the modem, SY/MAX must be selected. If the mode is toggled to Transparent, a warning is issued to notify that a loss of communication will occur if Transparent is selected. If Transparent mode is the desired mode of operation, this value should be the last parameter changed. If Transparent mode is selected accidentally, the modem may easily be returned to SY/MAX mode by toggling the Hayes/SY/MAX switch on the front panel to SY/MAX, or if a direct connection from the personal computer exists and the RM14K is in PSTN mode, the terminal emulator may be used to issue the "AX" command. This may be performed with the following procedure:

RM14K Manual

1

Press Esc to return to the Main Menu of RM14K.

2

Select the Setup menu.

3

Select the Terminal Emulator menu item.

4

Set the Terminal Emulator to the same COM port, baud rate and parity as the SY/MAX connection.

5

Select Yes or No to save the settings to file.

6

From the Main Menu, select Utility.

7

Select the Terminal Emulator menu item.

8

If the modem has Carrier Detect, press +++ to return to the Command State.

4

Configuration Software RM14KSW 47

Page 48

9

Type the characters AT followed by the Enter key. The modem should respond with the letters OK<0D><0A>. This means that the Hayes interpreter has automatically adjusted itself to the current port settings.

10

To return to SY/MAX mode, type the characters AX followed by the Enter key. The Hayes Interpreter will not respond with an OK since the RM14K is immediately returned to SY/MAX mode. The RM14K may respond will a series of hexadecimal characters. These may be ignored as they are part of the reply to the SY/MAX message that was interrupted by changing to Hayes mode.

11

Exit the Terminal Emulator by pressing Ctrl and End at the same time. It should now be possible to go oNline from the Main Menu.

As indicated in the Notice above, once the Transparent command bit is set while oNline, subsequent attempts to set it again from oNline will not be effective until that bit is first cleared. This may be accomplished by using the Utility Register Viewer to write a zero to R[1], or by using the oFfline Send command to download a new configuration to the RM14K.

Connection Type The Connection Type sets the audio connection to PSTN, Four Wire, Two Wire, and Two Wire Multidrop. The Two Wire Multidrop is not permitted in SY/MAX mode. The default value is PSTN.

Auto Answer The Auto Answer selection offers the possibility of Enabled or Disabled. The default value is Enabled. In PSTN mode, Disabled prevents the modem from ever answering in incoming call; while Enabled allows the modem to go Off Hook after the Answer on ring limit is enabled. In Leased Line modes, Disabled selects Originate mode for the modem; Enabled selects Answer mode. In Two and Four Wire Point-to-Point modes, one modem must be set for Originate and one modem must be set for Answer.

Answer on ring The Answer on ring value determines the number of rings that the modem will wait before going Off Hook while in PSTN mode. For this value to be effective, Auto Answer must be Enabled. The default value is 3.

Wait for Dial Tone This setting provides the number of seconds that the modem will wait between going Off Hook and dialing the programmed number. The default (and minimum) value is 2 Seconds.

Wait for Carrier The Wait for Carrier setting determines the number of seconds that the modem will spend trying to establish carrier upon completion of the dialing sequence. The default value is 30 Seconds.

Port BPS This value controls the baud rate of the RS-422 port. The possible settings in SY/MAX mode range from 300 to 19200 baud. A complete listing of baud rates is given in Table 3-3 on page 29 as well as in Appendix D. The default value if 9600.

Port Parity This setting controls the parity setting on the RS-422 port. Possible values are: EVEN, ODD, and NONE. The default value is EVEN.

48 Configuration Software RM14KSW

4