For the Square D 8030-CRM-565 and Schneider 8030-CRM-565
Page 45
30598-756-01 Page A-1
Appendix A - Installing a Network Cable End
The network cable end (Class 8030 Type CCK-221) consists of ten parts.
Wrench Washer in
Crimp Cone | ned] Pin Shield | Body im] t t 5 6 7 4
The twinaxial network cable (Belden* 9272 or equivalent) consists of seven parts.
Outer Jacket praig Diejectric {Blue) Filters e
White
The following is a procedure for assembling a network cable end on the twinax cable.
eae) 5 oP, >
2 ht -t - ~1.00"
Twinax Cable
1. Place WRENCH CRIMP NUT (1) onto net- work cable; threaded part of nut should face right.
2. Strip approximately one inch (2.5 cm) of insulation from end of cable, being careful not to damage shield wires.
3. Cut back BRAIDED shield to within 0.2 in- ches (0.5 cm) of the cable jacket.
Cut off filler corda to cable jacket.
Thread blue and white wires through amall end of CONE (2) and preas cone into cable until recessed into cable jacket (cable end will flare out).
6. Place red WASHER (38) over wires and against CONE/DIELECTRIC ASSEMBLY(2).
7. Cut blue and white wires to a length of 0.35 inches (0.9 em) measured from red washer
(3).
8. Strip insulation off blue wire 0.2 inches (0.5 em).
10.
11.
12.
13.
14.
15.
16. 17.
Note:
18.
19.
20.
Note:
Tin the BLUE wire.
Bend the WHITE wire at a right angle away from the BLUE wire.
Place white NOTCHED INSERT (4) over BLUE wire and presse until flush with red WASHER (3). (WHITE wire should fit into notched insert.)
Place PIN (5) over BLUE wire. Pin should be flush with NOTCHED INSERT (4).
Carefully solder pin (5) to BLUE wire (apply solder bead to hole in side of pin).
When solder cools, teat connection by lightly pulling pin (5) with pliers - a common prob- lem found with cable ia cold solder joints.
Place shield (7) over PIN assembly and seat against red WASHER (3). Thread WHITE wire through notch in SHIELD (7).
Strip WHITE wire back 0.25 inches (0.6 cm).
Wrap WHITE wire around shield (8) and solder. Let cool.
Solder and wire must not extend beyond shield ridge - otherwise WHITE wire could come in contact with connector body.
Place BODY ASSEMBLY (8) over shield as- sembly.
Thread WRENCH CRIMP NUT (1) into BODY ASSEMBLY (8).
Perform continuity check on cable - you should have 10K ohms or greater resis- tance between blue wire and white wire and either wire and shield. If a lower resistance is found, check for short in cable end, cable, or opposite cable end.
Resistance measurement should be made WITHOUT network terminator or interfaces attached.
* Belden is a registered trademark of Belden Electronic Wire and Cable Inc.
Page 46
30598-756-01 Page B-1
Appendix B - Communication Error Codes
The following is a list of the most common error codes that may be displayed during communications. All COMM error codes are odd numbers (1,3,5,etc). For a complete list of error codes, consult a SY/MAX processor instruction bulletin.
Error Code Deacription
01 illegal protocol opcode, the device does not recognize the instruction.
03 An Wega! address has been attempted.
05 An illegal instruction has been atternpted which ts not allowed. (Example: Write to NIM set to peripheral moda.)
07 An attempt has been made to alter data in a grote register. Check Control Register og fn anmampt haa been made w aher data ina READ only register or input.
1 Communications error (receiver overtlow).
13 Communications error (link error). This error is the processor. Check Contral Reners 8175 or the COMMs status register. Check cable connections between devices.
15 Communication overflow.
17 The remote device is inactive. This error code is generated by the network interface module. Check cable connections between devices.
19 An ihegal READ parameter has been assigned
21 Trying to change a forced bit or WRITE to an extemal output while the processor is in HALT.
Error Code Description
23 An attempt has been made to alter data in a fenced register.
23 An attempt has been made to send a message with an illegal route.
31 The end of the tape was encountered before the operation could be completed.
33 Tape Data Error detected, the block of data involved in the Read or Write operation was faulty.
35 The cartridge is not seated properly or missing, or the “Record* tab on the has been set to the Write Inhibit bebo
37 An attempt to Skip or Read a fle was made when already past the last file on the tape,
39 Alarm already set within the D-LOG Module.
4 Communication error with D-LOG Module was encountered.
43 An illegal operation has been attempted, D-LOG Module protected.
45 Operation is not allowed, D-LOG Moduie's tape operation in progress.
47 Operation is not allowad, keyswitch violation
49 \/O, Register or Channel is uarded: used in Type SCP-344, 444 and 544 RAM/PPROM Processor.
§1 Undefined register, a modula is not seated properly or missing.
53 Ihegal tape format, erase track required.
Page 47
30598-756-01 Page C-1
Appendix C - Cable Wiring Diagrams
1 41 1 6
2 2 2 24
3] 3 3 4 4 4 4 22 5 5 5 y=) ao) Co], : n
? ? 7 7
9 9 8 1 19
9-Pin (Male) 9-Pin (Male) #Pin (Male) 97 Type CC100 Series Cable Wiring Diagrams 20 25 Pin (Male)
Type CC130 Series Cable Wiring Diagrams
DB-9 Pin Connections at Circult Monitor SY/MAX (S¥/LINK) End Terminal Strip
20 (iN+)
21 (Wy)
22 (OUT+)
23 (OUT-)
24 (SHIELD)
oa a wn nme &@ He = o awn th He HG BD =
9-Pin (Mate} 9 in (Mala) on 9 pin Connector
Type CC104 Serles Cable Wiring Diagrams
Page 48
30598-756-01 Page D-1
Appendix D - Summary of DIP Switch Settings
Baud Baud SYMAX Mode (SY/MAX Mode)
456 466
~~ B- =o
Disable Recewe Broadcast
Enable Receive Broadcast
SOOK fl
1234567
Ho Selt-Test | VY | { Wavy a
84 COMM Port 1 COMM Port 0
= Switch Handle Up = Switch Handle = Open
DIP Switch Setting Summary
Page 49
NET WORE
INTERFACE
Figure 2.2 - Thumbwheel Switches
Figure 2.3 - DIP Switches
Page 50
Figure 2.4 - Network Port
Figure 2.5 - COMM Ports Figure 3.2 - Network Interface Module