Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor): 8: Troubleshooting
Pages 41 to 44 of 50, from Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor)
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D 8030-CRM-565 and Schneider 8030-CRM-565
Page 41
30598-756-01 Page &-1
8.0 TROUBLESHOOTING
Troubleshooting of the PNIM can be broken into two areas (1) hardware indicating lights and (2) communications errors.
8.1 _ Indicating Lights
On the front of the PNIM are eight indicating lighta, which function as follows:
Light Function
NETWORK ON = Busy/Activity
Tx0 Receive Data Thru port 0
Tx0 Transmit Data Thru port 0
Rxl Receive Data Thru port 1
Txl Transmit Data Thru port 1
NET Rx ERROR Network Receiver Error NET Tx ERROR Network Transmit Error POWER 5 Volta applied to module
During power-up, the NET Tx and Rx lights will flash ON and OFF in a defined sequence. This flashing indicates a self-test is being performed. When both NET Rx and Tx lights are OFF, the self teat is complete and normal module operation can take place. If an internal fault ia found, the power-up sequence will stop and the NET Rx and Tx lights will flash ON and OFF together, pause and then repeat until power is removed. See for error description.
8.1.1 Communications
The Rx0, Tx0 and Rx1, Tx1 lighta indicate communications activity through COMM ports 0 and 1 respectively. Any time the PNIM transmits data out a COMM port the Tx LED will light. Also anytime data is received by the PNIM’s COMM port the Rx LED will] light. During SY/MAX Processor to SY/MAX Processor, or programmer node to SY/MAX Processor communications, these LEDs will flash.
When the PNIM ia set for the SY/MAX Mode, an automatic communications check is made every two seconds. This check ia made when no communica-tione are taking place in other words, during an idle atate. During this idle state, the PNIM will send a small inquiry message to the device connected to each COMM port. If the attached device is a SY/MAX device, it will send a small message back to the PNIM. Thia message exchange occurs every two seconds, and ie independent of the customer program (transparent to the user).
If during the idle communications state, the Rx and
Tx lights do NOT flash, inquiries are not getting through and therefore, normal communications can-pe o isolate the problem.
Possible Cause 1, £X and Tx lights do not 1. Check power on PNIM. jas
2. Is PNIM in SY/MAX or PowerLogic modes. Note: The 1M COMM u signals (CTS-ATS). these signals are jum) allowing the PNIM to communicate when the following cables are a : CC100 ~CC103
3. Is cable into PNIM como?
4. Perform self-test on PNIM device
2. Tx LED flashes ON one 1. Check power on remote second and then turns off device.
2. Check cable to remote device.
3. Check baud rate of PNIM and remote device.
4. Remote device is nota SY/MAX device.
3. Tx and Rx LED's flashing 1. tly similar to #2
Chack baud rates of PNIM and remote device.
2. Perform self-test on PNIM and remote device.
Figure 8.1 - LED Checklist
Page 42
Page 8-2 30598-756-01
Error Code Description Cause 3 jiiegal Address Out of range. Example: Register 150 on Model 300 PC 5 Illegal Operation Parity Error 7 WRITE to protected register WRITE to control register 8100-8192. 9 WRITE to READ only Register or Input =| Write to register in I/O rack that contains an input card. 13 Link Error Loose cable - SY/MAX mode. 15 Communication Overflow Remote device too busy to respond. 17 Remote device inactive No PNIM exists or PNIM COMM port not connected. 19 READ count too large Model 300 maximum count is 15, pre-Senes M Model 500 maximum count is 64, Series M or later model 500 maximum count is 128, model 700 maximium count is 64, ail other devices maximum count is 128. 23 WRITE to fenced register Register is protected by processor and cannot be written into. 20 Iliegal Route - Not enough route numbers. - Connected to wrong PNIM (first number) - Middle route number directed to PNIM which is not set up for circuit monitor mode. » Figure 8.2 - Error Code Summary 8.1.2 Communication Error Codes When power ia reapplied to the PNIM, the Tx1 and
When using READ, WRITE, or ALARM rungs, the status register of these rungs will contain a number which describes the results of the communication. When the number is between 1 and 16,000 the number represents an error code.
Figure 8.2/describes several common error codes and their possible causes. Seq Appendix B]for a complete summary of error codes.
8.1.3 Self-Test
For a more thorough test of the PNIMs memory, COMM ports and network port, use the following procedure.
1. Remove power to the PNIM.
2. Remove any cables from the COMM and Net- work ports,
Remove the PNIM from the rack.
Set switch 7 on switch group S4 to the ENABLE SELF-TEST position. See Section 4.2.2
Replace the PNIM in the rack.
Insert Type CTP11 (Class 8010) test plugs into both COMM ports of the PNIM. The NETWORK port requires no test plug.
7. Reapply power to PNIM.
Tx1 lighta will flash ON and OFF, followed by the Tx0 and Rx0O lights. Thia pattern will repeat approximately 50 times. At the same time the NET Rx and Tx ERROR lights will also flash.
After approximately 75 seconds the NETWORK LED will turn on and off indicating data ia being tranamitted/received out the network port. This pattern will repeat four times. The above pattern will then repeat until power is removed. The total test takes approximately 90 seconds.
If an error ia detected in the PNIM, the NET Rx and Tx LEDs will flash ON and OFF together, pause and then repeat the same flashing sequence until power is removed. Refer to/Figure 8.3
Self Test Errors {Indicated by both Net Ax and Tx LEDs Flashing)
One flash ROM checksum error.
Two flashes RAM error
Three flashes Serial port 0 or 1 error.
Fours flashes Network port error.
Figure 8.3 - Network Error Lights
To turn the self test mode OFF, set switch 7 of switch group S4 DOWN,
8.2 System Troubleshooting
After determining the PNIM is operating properly, and that the devices connected to it are functioning correctly, the following procedure can be used to isolate any network system fault.
Page 43
Assumptions
Before troubleshooting can begin, several asaump-tions have to be made. They are:
¢ SY/MAX Family devices are involved. (PC, CRT, D-LOG)
* Power is applied to rack and Network Interface Modules.
¢ No error lights are illuminated on the PNIMa.
Baale Tools
For troubleshooting, several basic pieces of hardware will be required. These include:
* One SPR2650 or SPR300 CRT Programmer, or IBM compatible computer with SY/MATE programming software
* Qne PC Model 300, 400, 500, 600, 700
« Two CC100 Series Cables
¢ Two PowerLogic Network Interface Modules * Appropriate Network Cables
Basic Layout
Figure 8.4 shows a basic minimum network layout that will be used for troubleshooting. It is suggested that the two PNIMs be isolated from the overall network. This removes the possibility of a defective network cable, duplicate PNIM numbers, or conflicting network communications.
Lio oC] D I 2)
Figure 8.4 - Basic Network Layout
Basic Operation
The basic system layout shown in| Figure 8.4, contains a SY/MAX Processor, a CRT (or similar programming device) and two PNIMs. Two PNIMs have been connected together using tee connectors and terminators. The intent is to start with a smail network and expand to the full system. The following is a step by step procedure for network system troubleshooting.
30598-756-01 Pages-3
STEP 1. Verify correct operation of SYMAX Processor and CAT.
A. Connect CRT directly to the processor using CC100 series cable.
B. Turn on CRT (SY/MAX menu must be die- played). C. Depress STATUS soft key (leftmost key).
The CRT should be showing the status of the processor. If an error is indicated, correct before continu-ing. Possible errors could reflect a bad CRT, SY/MAX Processor or cable.
STEP 2. Check SY/MAX Processor to PNIM operation.
(Proper non-network operation has been verified at this point)
A. Connect the processor to either PNIM using a CC100 series cable.
B. Turn the processor key to HALT.
C. Apply power to the processor and the PNIM.
D. Monitor the PNIM RX and TX LEDs for the COMM Port the processor is connected to.
The RX and TX LEDs should flash ON, the OFF, once every two seconds - this is normal. If there is not proper LED indications, correct before continu-ing (See Section 8.1.2 for LED operation),
STEP 3. Check CRT to PNIM operation.
A. Connect the CRT to the PNIM.
B. Apply power to the CRT and PNIM (SY/MAX menu must be displayed).
C. Monitor the RX and TX LEDs as in step 2 above and verify proper operation.
STEP 4. Route CAT to SY/MAX Processor over the Network.
A. Depress the ROUTE soft key on CRT.
B. Enter network device numbers of CRT and proceasor (DO NOT use special route addres- ses 200 and above).
C. Depress the STATUS soft key on CRT to dia-play processor status.
Page 44
Page &-4 30598-756-01
If the CPU status is displayed, the network system is working. Next, connect the network modules to the overall network syatem and again verify proper CRT to processor operation.
Common Errors
The most common errors that occur on the network are error code numbers 29 and 17.
Error 29 - Illegal Route. This error occurs when the network device number of the CRT does not match the thumbwheel number on the PNIM where the CRT is connected.
Error 17 - Inactive Device. This error refers to a failure to communicate with a remote device. Common causes of this error are:
1. The network device number does not exist, because:
Route number is incorrect.
No PNIM on the network has this num- ber.
PNIM does not have power.
PNIM network port is not connected, or is loose.
9a wp
2. PNIM COMM Port apecified by route is net working, because:
A. No cable is attached to the COMM Port.
B. Attached device ia not working.
C. Attached device is not a SY/MAX Family device.
HELP
If the above step by step troubleshooting procedure has not been effective, local field support or head-quarters support may be required. Before the call is made, several important pieces of information should be obtained. These are:
PNIM series number (A,B,C,D),
2. Was system on-line before failure occurred, or is thia a new system (start-up) problem?
3. What are the switch settings for the Power- Logic Network Interface Modules involved?