Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 3 of 10

Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor): 1: Introduction

Pages 7 to 9 of 50, from Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor)

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-CRM-565 and Schneider 8030-CRM-565

Page 7 read from a scan by OCR; it may hold reading errors

30598-756-01 Page 1-1

1.0 INTRODUCTION TO THE PNIM

1.1 What !s the PNIM?

The Class 8030 Type CRM565 PowerLogic Network Interface Module (PNIM) allows SY/MAX device communication with Square D PowerLogic Circuit Monitors. Using PNIMs, the transmission media between circuit monitors and SY/MAX devices can be twisted pair cable.

This manual is intended to be used with the Power- Logic Circuit Monitor Instruction Bulletin 63074- 140-XX.

The PNIM provides a communications interface between one active SY/MAX compatible Master device (and/or SY/MAX network of devices), and up to 16 circuit monitors daisy chained (networked) on PNIM Port 0, Data exchange is accomplished by reading from and writing to registers in the circuit monitors.

PowerLogic Network operation is completely transparent, allowing reading and writing of circuit monitor register data and Input and Output Status. No special programming language is required other than standard ladder logic for SY/MAX processors, and advanced BASIC for the SY/MAX D-LOG Data Controller.

The PNIM is all that is required to link Square D PowerLogic Circuit Monitors with the SY/NET local, - - - o area network. Each PNIM communicates with up to 16 circuit monitors using half-duplex single channel communication. Each PNIM may be connected to an entire network of SY/MAX or compatible devices.

The PNIM can be used in conjunction with the SY/MAX Class 8030 CRM510, CRM570 Network In- terface Modules for applications requiring remote commugications to ProVok*] Honeywell or other Modb mpatible (via CRM570) ayatems.

The PNIM may also be used in conjunction with the Class 8030 CRM560 Remote Network Interface Module to obtain Remote Area Networking capability.

1.2 What Are Typical Applications?

The PNIM is useful for any monitoring or control application where PowerLogic Circuit Monitors are integrated with SY/MAX programmable controllers.

The following are typical applications where PNIMs are applied for data gathering and/or control:

» Energy Management * Power factor correction

« Planning system loads

PowerLogic Circuit Monitor =, - - - - - - --- - »} Network

Device 4 PowerLogic PowerLogic PoworLogic PowerLogic Circuit Circuit Circuit Circuit Monitor Monitor Monitor Monitor #16 a5 rir #1 SY/NET Local Aron Network i Personal S¥MAX Computer Device with SY/MATE® Software

* ProVOX is a registered trademark of Fisher Controls. ** MODBUS is a registered trademark of AEG/Modicon Corp.

Page 8 read from a scan by OCR; it may hold reading errors

Page 1-2 30598-756-01

« Internal billings

+ Power distribution system diagnostics

* Preventive maintenance

The following operations are possible:

+ Reading and writing register data

* Reading and writing I/O status

¢ Circuit Monitor Configuration

1.3 Specifications 1.3.1. PNIM Specifications

Mounting Requirements

Current Draw on SY/MAX Power Supply

Operating Temperature

Storage Temperature

Humidity Rating

Connectors: Network Port

COMM Port 0

COMM Port 1

Indicator Lights

Physical Dimensions

One register slot of a Class 8030 Type CAK, DRK, GRK, HARK, or RRK I/O rack assembiy.

950 mA

32 - 140°F (0 to 60°C)

-40 to +176°F (-40 to +80°C) 5-95% noncondensing

Connects PNIM to local (SY/NET) network.

9-pin female D-connector, RS-422 compatible. Selectable baud ratd (see Section 35.1)] Protocol depends on mode setting.

9-pin female D-connector, RS-422 compatible. Selectable baud rate (Section 3.5.1). Uses SY/MAX protocol.

8 LEDs: Network, Rx 0, Tx 0, Rx 1, Tx 1, NET Ax ERROR, NET Tx ERROR, POWER (see

Single-width module Wt: 2.7 Ib. (4.22 kg) W: 1.5 in. (3.8cm,) H: 12.8 in. (32.5cm.)} D: 6.6 in. (16.8cm.}

1.3.2 SY/NET Network Specifications

Topology Bus Media

Bus Connectors

Bus Terminators

Bus Cable Length

Transmission type

Access method

Priority

Error checking

Message routing

Number of devices per bus cable

| (See Section 3.4.1.)

Bus

Baseband twinaxial cable, Belden 9272 or equivalent (for local network only).

Dual concentric twist lock. Teas, cable ends, joints, etc. are available from Square D.

Required on each end of the Local Network cable. (Sea

Section 3.4.1.

Communication baud rate dependent (cable length vs BAUD 2 ee Seton 40) ft./4,572 mi (See Section 3.4.2) Manchester . Time coordinated Access {TCA}, based on time windows. Based both on module number (lower number has higher priority), and on level of network activity.

CRC {cyclic redundancy check) on all network transmissions. Source/destination message routes are placed in the command for each device wishing to communicate.

Up to 100 compatible interface devices (see below} per SY/NET network. Each network interface device supports two additional devices, for a total capacity of 200 devices per network. Networks can be linked to provide access to over 10,000 davices.

Page 9 read from a scan by OCR; it may hold reading errors

1.3.3. Powerlogle Circuit Monitor Network

Specifications Topology Master/slave* (M/S). WS media RS-422 PORT: Dual twisted-pair cable, Belden 8723 or equivalent. Use a modem to adapt to other media such as Telco, radio, or fiber optics. NETWORK PORT; Same as

Local Network | (Refer to 1.3.1)] WS connectors 9-pin D connector, aval from Square D Company.

WS cable length Maximum 10,000 feet of Bekden** 8723, depending on device that is attached. Use of modem allows unlimited jength, depending on madem used.

Transmission type Accass mathod Error checking Message routing Number of devices

Compatible devices

30598-756-01 Page 1-3 RS-422 half-duplex with CRC-16.

Master-initiated. Same as local network. Same as local network.

Maximum 16 circuit monitors.

Same as local network.

* The Master can be any SY/MAX or compatible device (i.e. SY/MAX processor, or SY/MATE software package such as

Screen Ware2 or 234 Link).

** Belden is a registered trademark of Belden Electronic Wire and Cable Inc.