Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor): 2: Hardware Description
Pages 10 to 12 of 50, from Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor)
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D 8030-CRM-565 and Schneider 8030-CRM-565
Page 10
30598-756-01 Page 2-1
2.0 PNIM HARDWARE DESCRIPTION
2.1 General
The PNIM consists of a module that mounts in, and draws power from, a register slot in a SY/MAX I/O rack. Located on the front of the PNIM are eight indicator lights, two thumbwheel switches and two communication ports (COMM ports). On the bottom front of the module ia a high speed network port. On the module circuit board are configuration DIP switches.
2.2 Indicator Lights
The PNIM has eight indicator lights (see Figure 2.1) which aid in troubleshooting. The lights are:
C) NETWORK
() NET Rx ERROR () NET Tx ERROR
C) Power
Figure 2.1 - PNIM LEDs
NETWORK - This AMBER light, when on, indicates activity on the Local Area Network. Typically this light ia very dim; this is normal. As more and more devices communicate over the Network, this light will glow brighter.
Rx 0 - This AMBER light indicates that the PNIM is receiving data from the device(s) connected to COMM Port 0.
Tx 0 - This AMBER light indicates that the PNIM is transmitting data to the device(s) connected to COMM Port 0.
Rx 1 - Same as Rx 0 except for COMM Port 1. Tx 1 - Same as Tx 0 except for COMM Port 1.
NET Rx ERROR - This RED light indicates that a communication error has occurred on received data. This light indicatea an overflow condition (PNIM buffer is full), or an erroneous message has been received.
NET Tx ERROR - This RED light indicates that an error has occurred when the PNIM attempted to send a message on the Network. Typically this occurs when a message is routed to a NIM that does not exist, or an acknowledge to a message has not been received.
POWER - This GREEN ight indicates that the PNIM has power applied. The Power LED is wired directly to the incoming 5 VDC power on the module.
Note: Sed Section 8.0}for additional information on ig operation o ta.
2.3 Network Address Thumbwheel Switches
On the front of the P. humbwheel switches. These switched (see Figure 2.2}are used to assign a Network Interface Number (address) to the CRM5665, and in turn a unique Network Device Number (NDN) to each device connected to the
PNIM.
On the right side of the module are two accesa holes which allow the thumbwheels to be set using a small screwdriver.
Page 11
Page 2-2 30598-756-01
Click here to view graphic.
Figure 2.2 - Thumbwheel Switches
2.4 Circult Board DiP Switches
On the rear of the PNIM are three ups of DIP switches labeled $3, $4, and s6| See Figure 2.3
Click here to view graphic.
Figure 2.3 - DIP Switches
DIP switch group S3 contains four individual switches (numbered 1 to 4) and is used to set the baud rate at which the high-speed network port is to operate. DIP switch groups $4 and S5 each contain seven individual switches (numbered 1 to 7) and are used to select the mode of operation, comm port baud rate and other apecial functions for communication ports 1 and 0, respectively.
See] Section 4.2.2]/for more information on DIP switch settings.
2.5 Network Port
On the bottom ofthe is a network port. This female connectoy (Figure 2.4) is used to connect the PNIM to the Local (SY/NET) Network cable.
Click here to view graphic.
Figure 2.4 - Network Port
2.6 COMM Ports On the front of the PNIM are two COMM ports (Fig-
These porta are used to interface with the
SY/MAX Family devices, modems, PowerLogic circuit monitors and other devices. These ports operate as RS-422 ports and will not support RS-232C devices directly. Each port operates independently and supports handshaking (Request te Send - RTS, and Clear to Send - CTS) signals. Adaptors for the conversion of RS-422 to RS-232 are available (Class 8010 Type CRM600 Single Channel Standalone and Class 8030 CRM601 Dual Channel Rack Mount).
Only COMM Port 0 can be selected for PowerLogic Mode, and hence only this port can be used to estab-lish communication link with circuit monitors. When in this mode, communication is half-duplex and CRC error checking is used. (Optionally, COMM Port 0 can be set for SY/MAX mode, but this setting prevents the PNIM from being used for circuit monitor network communication.)
COMM Port 1 can only be used in the SY/MAX Mode. This allows a SY/MAX Master (i.e. processor) or compatible device to communicate with 16 (max) PowerLogic Circuit Monitors connected to COMM Port 0.
Page 12
Click here to view graphic.
Figure 2.5 - COMM Ports
30598-756-01 Page 2-3
The COMM ports can operate at baud rates of 1200, 2400, 4800 and 9600 when in the SY/MAX or Power- Logic Mode.
Maximum distance between either of the PNIM COMM ports and a connected device ia 10,000 feet (8,048 M). In a typical application, COMM Port 1 is connected to a SY/MAX device while COMM Port 0 is connected to 1-16 Square D PowerLogic Circuit Monitor(s).