Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor): 3: LAN Configuration and Connections

Pages 13 to 17 of 50, from Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor)

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-CRM-565 and Schneider 8030-CRM-565

Page 13 read from a scan by OCR; it may hold reading errors

30598-756-01 Page 3-1

3.0 LOCAL AREA NETWORK CONFIGURATION AND CONNECTIONS

3.1 Introduction

This section presents general information about the SY/NET Local Area Network. Sections later in thia manual! will then describe how PowerLogic Circuit Monitor networks operate.

3.2 Local Network Configuration

The SY/NET Local Area Network (LAN) is a high speed industrial communication system which allows up to 200 SY/MAX deviceg to intercommuni-cate. The network has a bus configuration with a single twinaxial_cable serving as the network communication bus]See Figure 3.1

SY/MAX Processors and other devices such as computers with SY/MAX protocol, printers, D-LOG modules, and other compatible devices are connected to the network through Clasa 8030 Type CRM5XX SY/NET Network Interface Modules (NIMs) or through SY/LINK Type SFI5XX personal computer network interface boards.

N 1 Computer M il Oe SYMAX SY/LINK \ symax P-L) P; P N I M (Or san itor OLOG Ont (18) = _ (1} ome

Figure 3.1 - Typical SY/NET Local Network Configuration

A maximum of 100 network interfaces (NIMs, PNIMs, or SY/LINK boards) can be connected to a single network. Each interface can connect two SY/MAX devices to the network. Therefore, a network can have a maximum of 200 SY/MAX devices.

However, even more devices can communicate by connecting multiple networks together.

A SY/NET Network Interface Module mounts in a register slot of a SY/MAX programmable controller I/O rack assembly. A NIM has a two digit thumbwheel for setting its Network Interface Number (address) between 00 and 99.

Click here to view graphic.

Figure 3.2 - Network Interface Module

A NIM has two RS-422 compatible COMM ports to which the programmable controllers or other devices are connected. The two ports are numbered 0 and 1. These port device numbers are combined with the NIM Network Interface Number to identify the devices for network communications. For example, the device connected to port 1 of NIM 5&5 would be identified by the number 155 in the route portion of network communication commands. The device connected to port 0 of the same module would have the number 055. (See[Section 5.3]for a discussion of network route instructions.)

On the bottom of a NIM module is a high speed, network port to which the network cable is connected. This port is connected dj Tee con- nector on the network cable (see Figure 3.2} or to an extension cable which leads to a Tee connector.

Like a NIM, the SY/LINK board also allowa two devices to be connected to the network. One device is the computer in which the board is mounted, a second device can be e RS-422 port on the SY/LINK board] See Figure 3.1}

Page 14 read from a scan by OCR; it may hold reading errors

Page 3-2 30598-756-01

For network-to-network communication, a COMM port on one network is connected to a COMM port on another network using a CC100 series differential communication cable. The two COMM porta involved in the net-to-net connection must have the same address number and must both be set to the NET-TO-NET mode via the DIP switches. For example, port 007 on network_1 must be connected to port 007 on network 2. Sed Figure 3.3 |he two ports must also be set for the same baud rate. See Section for a discussion of the routing necessary for net-to-net communication commands.

Q 7 oo-- ol + SYMAX 19] 10) Network A [} | | aon:

r - Net-to-Net Link

Cheuit GH Mentor O+

| if

| SY¥MAX Processor, o ol ]

Neb «SB (} aaw

* Must be a PNIM

Figure 3.3 - Network-to-Network Configuration

3.3 NIM COMM Port Connections

The COMM porta on a NIM utilize RS-422 com- patible signal levels.

The] following] signals are available at the NIM co ports.

Pin Number Function Direction 1 Transmit Data - Out 2 Transmit Data + Out 3 Recaive Data - In 4 Receive Data + In 5 Clear to Send + In 6 Request to Send + Out 7 Clear to Send - In 8 Request to Send - Out 9 Shiek 3.3.1 NIM to SY/MAX Device

To connect a NIM COMM port to a SY/MAX family device, a Clasa 8010 Type CC100 series cable is required. Thies cable can be purchased in several lengths:

Clase Type Length

8010 CC100 10 feet (3 meters) 8010 CC101 30 feet (9.1 meters} 8010 CC102 2 feet (0.6 meter 8010 CC104 3 foot (06 meter 8010 C105 10 feet (3 maters)

Series CC100, 101, and 102 cables DO NOT support handshaking (RTS and CTS signals). Series CC104 and CC105 DO support handshaking.

When an application requires a cable length longer than 30 feet (9.1 meters), the user can purchase a connector kit and assemble a custom length cable of up to 10,000 feet (3,048 meters).

The cable connector kit (Class 8010 Type CCK102) consiata of:

Oty Description

2 DOBSP, 9-Pin Connectors 2 OB9P Connector Covers 18 Connector / Pins

Recommended cable type is Belden 8723 or equivalent or Belden 9502 (UL/CSA Approved) (2 pairs shielded, with ground). Pin connection for

Series CC1 102 cables (no handshaking) is shown in] Figure 3.4] Connection of Seri 4. and 105 (with handshaking) ie shown in Figure 3.5

1 1 2 2 3 3 4 4 = Cl: ;2 C: 9 9 PNIM SYMAX device (3pin male} (9-pin male)

Figure 3.4 - Type CC 100, 101 and 102 Series Cable Wiring Diagram (no handshaking)

Type CC series cables can be used for connecting a variety of SY/MAX devices. Consult the device Instruction Bulletins for the devices being used.

Page 15 read from a scan by OCR; it may hold reading errors

1 1 2 2 3 3 4 4 5 5 6 an é 7 7 ; a ne 5] 9 PNM SYMAX device (8-pin male} (9-pin mate}

Figure 3.5 - Type CC 104 and 105 Series Cable Wiring Diagram (with handshaking)

WARNING

Never connect the communication cables with handshaking to any SY/MAX processor port. The 5VDC power available on these ports (pins 5, 6, 7 & 8) may damage the other device the cable Is connected to.

3.3.2 RS-232 Device to NIM

When it is necessary to connect an RS-232 device to a NIM, and RS-232 to RS-422 adaptor can be used. Square D offers two such adaptors: the Class 8010 Type CRM600 and Class 8030 Type CRM601. The CRM601 is a dual channel device that mounts in a SY/MAX register slot, while the CRM600 is a single-channel freestanding unit. Consult the CRM601 Instruction Bulletin 30598-152-XX and the Printer Instruction Bulletin 30598-176-XX for more information.

NIM

H

Lr U

Figure 3.6 - Connecting an RS-232 Device

To RS232

‘ Device

CRM60O

3.4 Network Port Connections

The network port on the NIM connects to_a Tee connector in the network cable] See Figure 3.7]

30598-756-01 Page 3-3

Figure 3.7 - Network Cable Connections

The NIM network port can also connect to a Type CC202 or similar cable which in turn connects to the pe_connector for an extended drop length (see Fig-

3.4.1 Network Cable and Connectors

The main network cable consists of Belden 9272 twinaxial cable or equivalent. Factory asaembled cables (complete with cable ends) are available in two lengths:

Class Type Length 8030 cC201 2 feet (0.6 meter) 8030 CC202 10 feet (3 meters)

These cables are useful for connections between closely located network components. Most users, however, will find it necessary to assemble longer cables to meet specific application requirements.

Page 16 read from a scan by OCR; it may hold reading errors

Page 3-4 30598-756-01

NIM or PNIM

Type CC-202 Cable Drop Length 16 Foot > (3 Meters) FH) Extension XY Network Cable "Teo"

Connector

Figure 3.8 - Extended Network Cable Connection

When building a network cable, the following types of connectors are used:

Clasa Type Connector

8030 CCK211 Cable End

8030 CCK212 Tee Connector 8030 CCK213 Terminator (set of 2) 8030 CCK214 Cable Extension

Cable End - The cable end consists of a female socket. Two cable ends are required for each length of network cable.

D

Figure 3.9 - Cable End

Ny

See Appendix Alfor cable assembly inetructions.

Tee Connector - The Tee connector allows a NIM or SY/LINK board to tie into the network cable. The Tee connector has two male plugs which connect to the network cable and a female connecter which con-necta to the NIM or SY/LINK board.

Figure 3.10 - Tee Connector

Terminator - A terminator is required at each end of the main network cable (two terminators required per network). The terminator consists of a female socket and an internal 78 ohm resister. It matea to a male plug on the Tee connector, or to a cable extension.

W yy

Figure 3.11 - Terminator

‘hes

Cable Extension - The cable extension conaista of two male plugs. This extension can be used to (1) connect two network cables together, (2) replace a Tee connector when a NIM or SY/LINK board is removed from the network, (3) provide the splice for the future installation of a NIM or SY/LINK board by replacing the cable extension with a Tee connector, and (4) extend the distance between a NIM and the Tee connector.

Figure 3.12 - Cable Extension

Page 17 read from a scan by OCR; it may hold reading errors

3.4.2 Network Cable Length

The maximum network cable length is dependent on the selected speed of network communication and on the drop lengths used on the network. The drop length is the cable distance between the NIM and the Tee connector.

The following] table]lists the maximum network cable Jength based on network baud rate. Network Maximum Network Length Baud Rate (Foet/Meters) 62.5 K Baud 15,000 / 4,572 125 K Baud 9,250 / 2,819 250 K Baud 4,250 / 1,295 500 K Baud 2,400 / 732

The above network cable lengths are based on connecting the network Tee connector directly to the NIM (drop length of 0 feet). ,

When it is necessary to extend the length of the network drop, the following [ehart}can be used as a guide in determining the maximum possible network length.

Network Number jDrop Maximum Netl- Baud Rate of Drops jLength |work Length (fm) 500 K Baud 100 0 2,400 / 732 250 K Baud 100 i] 4,250 / 1,295 125 K Baud 100 ie) 9,250 / 2,819 62.5 K Baud 25 100 15,000 / 4,572 62.5 K Baud 100 too 950 / 290 3.4.3 Network Cable Installation

Considerations

When installing the network cable, the following rules should be applied:

1. Provide a minimum six inch (15 cm) distance between the network cable and 120 VAC. Provide 12 inches (30 cm) distance from 240 volts AC and 24 inches (61 cm) from 480 volts AC.

2. When the network cable ia routed through conduit, the conduit must be grounded to building steel.

The signal level on the network cable is ap- proximately five volta DC (RS-422 voltage levels, Manchester encoded). Routing of the network cable should be done in accordance with standard wiring practices for low level switching signals. See Instruction Bulletin 30598-174-XX (Planning and Installation Guide).

30598-756-01 Page 3-5

3.5 Network Performance Considerations

A number of factors effect the efficiency with which messages are transmitted on the network. Network throughput can be negatively affected if many devices wish to speak on the network at the same time. Thia problem can be avoided by programming that ensures that devices communicate no more often than is truly necessary.

The hardware factors that effect network performance include network cable length, network baud rate, and network size setting.

Network cable length was discussed inj Section 3.4.2

3.5.1 Network Baud Rate

A network baud rate of 62.5K provides the highest noise-tolerance and the maximum network cable length. By increasing the network baud rate to 125K baud, network speed (throughput) is increased by seven percent. Each doubling of the network baud rate will improve throughput by seye : D to a maximum baud rate of 500K. See maximum network cable length based on baud Trate.

Note: Each SY/LINK Board, NIM, and PNIM on the network must be set for the same net- work baud rate.

3.5.2 Network Size Setting

The SY/NET network can have a maximum of 100 network interfaces (SY/LINK board or NIMs) on a single network. However, to improve information throughput/performance, the network size can be set for a maximum size of 31 (interface numbers 00 through 80).

This setting is only possible for networks having 31 interfaces or less. Any interfaces numbered 31 to 99 will not gain access to the network.

Note: All interfaces on the network must have the same network size setting.

Network performance and application programming are discussed more specifically in the SY/NET Network Interface Module Instruction Bulletin.