Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor): 4: Network Configuration and Connections
Pages 18 to 25 of 50, from Class 8030 Type CRM565 Network Interface Module (For Square D PowerLogic Circuit Monitor)
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D 8030-CRM-565 and Schneider 8030-CRM-565
Page 18
30598-756-01 Page 4-1
4.0 POWERLOGIC CIRCUIT MONITOR NETWORK CON- FIGURATION AND CONNECTIONS
4.1 Circuit Monitor Network
Configuration
The PNIM allows a SY/MAX device to be connected to COMM Port 1 while COMM Port 0 is used for PowerLogic circuit monitor network communication. See Figure 4.1]The PNIM can also be connected to a
SY/NET network through its network po his loca] network connection is optional](See Section 3)
ok BL.
PowerLogic Circuit Monitor Communication Link
Local Network {Optional}
Figure 4.1 - PNIM Connections
Each network has up to 99 NIMs or PNIMs. In general, the PNIM initiates communication with circuit monitors. Typically, the PNIM is located on a power distribution lineup or in a control room, while the circuit monitors are placed at various circuit locations.
Each PNIM can be connected to its own local network, showe a typical circuit monitor net- work with a PNIM communicating to circuit monitors.
4.1.1 Circuit Monitor Mode (Port 0 Only)
The PowerLogic Mode enables a SY/MAX device connected either directly to the PNIM or connected to a SY/NET Local Area Network containing a PNIM to initiate communication commands over the network to circuit monitor(s). Communication commands include READ, and WRITE rungs (ALARM rungs cannot be used to communicate with a CM) for SY/MAX Programmable Controllers. When using a D-LOG Data Controller, communication commands include GETN and PUTN.
Powe j j lected via DIP switch set- tings] See Section 4.2.2
SYMMAX Processor
2) ee - - Circuit Monitor Network, = 8 9 é 1 =e C ] C ] a2 O41 x 4 /
Figure 4.2 - Circuit Monitors on a Network
4.1.2 SY/MAX Mode (Port 1 or 0)
SY/MAX mode is selected for a PNIM COMM port to allow a SY/MAX device to connect to that port. Port 1 can only be set for SY/MAX mode. Port 0 can optionally be set for SY/MAX mode, but this prevents Port 0 from being used for a circuit monitor network link (in this case, the PNIM would function as a standard NIM, providing local network communication for two SY/MAX devices).
ig selected via DIP switch settings. See Section 4.2.2
Page 19
Page 4-2 30598-756-01
4.2 PNIM Configuration
To configure the Class 8030 Type CRM565 PNIM for operation with the PowerLogic Circuit Monitor, it is necessary to properly set the module address thumbwheels and the module DIP switches.
4.2.1 Network Address Thumbwheel Setting
Each PNIM (or NIM, or SY/LINK board) is assigned a two digit Network Interface Number (address) between 00 and 99.
This number is set using the thumbwheels visible on the front of the module. Access holes on the right side of the PNIM allow a screwdriver to be used for thumbwheel switch changes.
The number selected refers to:
« Network Interface Number (used with each of the COMM ports)
« Network time slot
* Network module communication priority
The Network Interface Number (thumbwheel ad- dress), when used with the COMM port number will define a Network Device Number or ROUTE ad- dress. For example, the PNIM with thumbwheel number 15 has Network Device Numbers
015 (COMM Port 0} 115 (COMM Port 1)
CAUTION:
Within one network, a Network Interface Number can be used ONLY ONCE. If more than one NIM has the same Interface number, the network will not operate properly.
The device number is used to route messages from one device to another. Any device that is plugged into a COMM port on the PowerLogic Network Interface Module (or NIM) will assume that COMM port’s device number.
Since the thumbwheel number can be set from 00 to 99 and each PNIM or NIM provides two COMM ports, the total number of devices that may be connected over a single SY/NET Local Area Network (LAN) is 100 x 2 = 200. Exception: When the PNIM is in the PowerLogic Mode, a maximum of 16 circuit monitors can interface to Port 0.
Note: If you need to connect more than 200 devices, the 8030 CRM510 or CRM540 Net- work Interface Module can be used to inter- connect networks via a NET-TO-NET approach, See Instruction Bulletin 30598- 257-XX or 30598-523-XX for more informa- tion.
4.2.2 DIP Switch Settings
On the rear of the CRM565 PowerLogic Network
Interface Module are DIP switches labeled $3, $4, and S5] See Figure 4.3
/ See
PNIM (Back) Figure 4.3 - DIP Switch Location
|
DIP switch group S83 contains four individual awitches (numbered 1 to 4) and is used to set the baud rate at which the SY/NET high speed network port is to operate. DIP switch groups S4 and S5 each contain seven individual switches (numbered 1 to 7) and are used to select the mode of operation, comm port baud rate and other special functions for communication ports 1 and 0 respectively.
Switch Group 3 - Network Baud Rate
Switch group S3 selects the communication baud rate of the SY/NET network port and musé be set the same for all NIMs (or PNIMs) connected on the same network cable.
As the network baud rate ia increased, it becomes necessary to limit the maximum overall length of the network cable in order to reduce noise suscep-tibility caused by signal reflections in the cable. For this reason, the network baud rate be set for values from 62.5K to 500K baud
CAUTION:
Remove power to the rack before removing or installing the CRM565 to change the DIP switches.
Page 20
Switch Groups S4 and S5 - COMM Port Parameters
Each of the two PNIM COMM ports has a DIP switch group for setting communication parameters. Switch group S4 is for COMM port 1 and switch group S5 is for COMM port 0. These switches are used to select the following values:
* Broadcast Enable/Disable
¢ Mode of operation.
* Baud Rate Self test
= 100/31 network size
DIP Switch 3 Baud Rate Max. Cable Length (Feet/Meters} 1234 , ue 500,000 2,400/732 oun 250,000 4,256/1 295 nt 125,000 9,250/2,812 UL 62,500 15,000/4,572 a» Switch Handle Up = Switch Handle Down «= Open
Figure 4.4 - DIP Switch 3 Baud Rate Settings
Switch groups S4 and S5 each contain 7 switches. (Each of these individual switches will be referred to by a group number followed by a switch number. For example, 4-1 switch is switch 1 of switch group 4.)
Switch 1 (Group 4 and 5) - Broadcast Enable (Not Applicable to PowerLogic Mode)
Switch 1 of switch group 4 and 5& select whether broadcast messages on the ne received by a COMM port] See Figure 4.5] Broadcast messages will only be accepted 1 setup for SY/MAX mode.
CAUTION:
Broadcast messages are NOT acknowledged by any Square D CRM-type module. The device sending the broadcast does not receive a reply, and therefore there Is no guarantee the CRM-type module ever recelved it.
30598-756-01 Page 4-3
Switch 4-1 controls broadcast enable for port 1 while awitch 5-1 serves the same function for port 0 (S65 is applicable only in SY/MAX mode).
Switch 4 - - Port 1 Switch 5 - Pon 0 1234567 1234567 Broadcaat Broadcast Enable Recaive Enable Receive Broadcast Broadcast
Fi « Switch Handle Up U = Switch Hande = Open Down
Figure 4.5 - Broadcast Enable Switch Setting
Switches 2 and 3 (Groups 4 and 5} - Operating Mode
The operating mode of the COMM ports is selected with switches 2 and 3 of switch groups 4 and 5. See [Figure 4.6.] Port 1 must be set for SY/MAX mode. Port 0 can be set for SY/MAX or PowerLogic mode.
OP Switch 4 - Port 1 DIP Switch S - Pori 0 1234567 1234567 SY MAX* SYMMAX
“NOTE: Settings other than these will cause communication {COMM} errors. PowerLogic = Handle Up (Open} = Handle Down (Closed)
Figure 4.6 - Operating Mode Settings
Switches 4, 5 and 6 (Groups 4 and 5) - COMM Port Baud Rate
The baud rate of the COMM porta is selected with switches 4, 5 and 6 of switch groups 4 and 5. See The switch settings for Port 0 will vary depending on whether SY/MAX mode or PowerLogic mode has been selected. (Port 1 must be set for SY/MAX mode.)
Page 21
Page 4-4 30598-756-01
DIP Switch 4 - Port 1 DP Switch 5 - Port 0 (SYMAX) (SYMAX or PowerLogic) 1234567 1234567
AQ] = AA} ~ ULAR) = ml (lM) ~ nie =
A = Switch Handle Up (Open}
A)
= Switch Hande Down (Closed)
Figure 4.7 - COMM Port Baud Rate Settings
Switch 7 (Group 4) - Self-Test Enable
Switch 7 of switch group 4 ia set UP for normal P operation, or DOWN to enable the self-test mode See Figure 4.8
DIP Switch 4
12434567
= Saitch Handle
Down = Open
Figure 4.8 - Self-Test/Normal Settings
A = Switch Hande Up
Switch 7 (Group 5) - Network Size
Switch 7 of switch group 6 is set UP for a local network size of 100 network interfaces (00 through 99), or DOWN to limit local network size to 31 interfaces (00 through 31), Limiting local network size improves throughput (see Section All NIMs and PNIMs on the same local net- work must be set for the same network size.
DP Gwttch 5
1234567
A 100 intertaces (0-99)
W 31 Interfaces (0-90)
I = Switch Handle Up ft «= Switch Handle «= Open
Figure 4.9 - Local Network Size Settings
Switch Setting Summary
Figure 4.10]provides a summary of PNIM DIP switch settings.
Page 22
30598-756-01 Page 4-5 Baud Baud SYV/MAX Mode {SY/MAX Mode) PowerLogic Mode 456 456 23 SYMAX Mode SYMAX Mode i fi Disabie Receive Broadcast fT 2400 PAY = PowerLogic Mode Enable Rocewe Broadcast 4200 7 1200 500K 1 Norma 7 Loca! ek Net Size Network 625K tl Solt-Test See S4 100 Baud Rate , v¥ 7 Hees 1234 1234667 12394587 . s3 $4 $5 Network Port COMM Port 1 COMM Port 0
= Switch Handie Up = Open
= Switch Handle Down
Figure 4.10 - DIP Switch Setting Summary
NIM Self-Test
To aid in toubleshooting, the CRM565 can run a self-test routine which checks internal ROM and RAM along with the two COMM ports and network port. To use this self-test, two teat plugs (Class 8010 Type CTP-11) are required for the COMM porta.
Switch 7 on switchbagk $4 activates the self-test sequences as shown on Figure 4.11
OPEN
Self-Test On
Self-Test Off (Normal Operaiion) Switchbank $4
Figure 4.11 - Self-Test Activation
Note: The COMM porta MUST have the teat plugs installed in them before the test sequence can be run.
Network Size
A SY/NET network can be configured for a maximum of either 31 NIMae or 100 NIMs (62 or 200 devices). When set for a maximum of 31 NIMs (network device numbers “00" to *30") network performance is improved 300% over the 100-NIM (00 to 99) setting. This is because internal timers within the NIMs no longer time to 100, but instead reset upon reaching network device number 30.
set to the “30” position.
OPEN s 8: * af ¢@ } a an . a 2 iH Li i i i dt 3 _ iJ
123 45 6 7 T 31 Nis Maximum ry 3 ri io 6 7 100 NiMs Maximum Switchbank S5 Figure 4.12 - Network Size Selection
Page 23
Page 4-6 30598-756-01
Note: The side-panel label on the CRM565 shows network size selection as “30/100". The 730" here is the largest thumbwheel setting that can be used. When dealing with actual module count, interpret thia as “31/100" since *00" is a valid network number.
CAUTION:
For proper operation, all modules on the SY/NET network MUST have the same network size num- ber. If “SIZE 100” operation ts desired and even one module on the network is set to "SIZE 30", the entire network operates as SIZE 30. All messages sent to modules with network device numbers of over “30” will not be acknowledged.
4.3 Factory DIP Switch Settings The CRM565 is shipped from Square D Company ith the DIP awitch configuration shown below in Figure 4.13
M cmncmy (cmon Gita) | Awan) Bahu
Figure 4.13 - Factory DIP Switch Settings
The settings in Figure 4.13 configure the CRM565 to the following parameters:
Network Baud
Rate .......00e-e eae 62.5K baud COMM Port “1”
Operating Mode ...... SY/MAX COMM Port “0”
Operating Mode..... SY/MAX COMM Port “1”
Baud Rate ........... 9,600 baud COMM Port “0”
Baud Rate .........-- 9,600 baud Self-Test .......--..- Disabled Network Size ........ 100
Receive Broadcast ... Disabled
Page 24
30598-756-01 Page 4-7
SY/NET® NETWORK INTERFACE CLASS 8030 TYPE CRM565 | COMM. PORT SWITCH-SETTINGS S4 AND SS NETWORK - SWITCH 83 taser? | onorF | CONSULT BAUD RATE SWITCH | AUD RATE SEL TEBT INSTRUCTION 1f2]3]4 1«TEST | BULLETIN $600 oltyiii 00K mewn? 30598-756-XX 4800 1 1I1 250K 0100 | FOR ADDITIONAL 200 fet Bs [NETWORK RIZE Ton] INFORMATION Lc t NET Wael TorEOrrOF A eS | ee clear em ee ee | ig
Figure 4.14 - Network Interface Label
4.4 4.4.1
Module installation and Keying Installation
The PowerLogic Network Interface Module consists of a single module which can be plugged into the register slot of an I/O rack or any slot in a register rack. A PowerLogic Network Interface Module can be inserted in the following SY/MAX racks:
Class 8030 Type:
CRK100* GRK210 CRK200* HRK100 CRK210 HRK150 CRK300 HRK200 DRK210 RRK100 DRK300 RRK200 GRK110 RRK300
* These racke contain only one register slot.
The PowerLogic Network Interface Module operates on 5 VDC and obtaina this power from a SY/MAX power supply when inserted in a register alot. No other signals exist between the PowerLogic Network Interface Mcdule and the rack except for power con-nectione.
4.4.2 Module Keying
Each register slot, whether on a digital or register rack, has a keying pin which is installed at the factory. This pin ie located between slot location 4 and 6. Its function is to ensure that only register modules can be plugged into register slots.
Each SY/MAX register slot may be keyed to accept only one type of SY/MAX Register module. An op-| tional keying pin kit, Class 8030 Type CBP104, is available for this purpose. The correct position of the keying pin for the Network Interface Module is between pins 14 and 16 [See Figure 4.15] The keying pin is simply inserted manually into the slot of the rack connector.
CAUTION:
When inserting or removing the Keying pins, use care to avoid touching the contact fingers within the connector. Improper insertion/removal may damage the connector.
2 4 < Register Keying Pin . Botween Slots 4 and 6 16 Interface Module Keying Recs Pin Between Slots 14 and 16 Slot
Figure 4.15 - Keying Pin Location
Page 25
Page 4-8 30598-756-01
4.5 Circult Monitor Communication Link Connections
Comm Port 0 of the PNIM _is_used for the circuit monitor communication link|See Figure 4.1
Port 0, when set to the PowerLogic mode, provides half-duplex RS-422 communication. The term half-duplex means that communication can occur in only one direction at a time (as opposed to a full-duplex which allows simultaneous two-way communication. Full-duplex is what occurs in the SY/MAX mode).
The differential, RS-422 signals provided at Port 0 are shown in the pinout diagram inj Figure 4.16
705 \ Clear 10 Send +
Shield | 90
O4 | Datine Request to Send- | 8O O3 Data in - Clear Send- | 70 O2 Data Out + Request to Send+ | 6O aay, Data Out -
Figure 4.16 - PNIM COMM Port Signals
The Circuit Monitor requires a communication cable containing two shielded twisted pairs (Belden 8723 or equivalent). Communications wires are daisy-chained from one Cireuit Monitor to the next, IN+ being wired to IN+, OUT- to OUT-, and shield to shield. The connection to a processor PNIM, or remote worksts ade using a 9-pin male (DB- 9) connector. illustrates the required cable pinouta.
OB-0 Pin Connections at SY/MAX (SY/LINK) End
Cireutt Monkor Terminal Strip
20 (ine) 21 (kr)
22 (Outs) 23 (Out)
24 (Shield)
l[OO000 0]
Figure 4.17 - Communication Cable Pinouts