The text of a manual · part 1 of 3

SY/MAX Class 8030 Type RIM126 Eight Channel Isolated Analog-Thermocouple Input Module, pages 1 to 8

Pages 1 to 8 of 22

The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8030-RIM-126 and Schneider 8030-RIM-126

Page 1 read from a scan by OCR; it may hold reading errors

SQUARE D

Instruction Bulletin

SY MAH’

Class 8030 Type RIM126 Eight Channel Isolated Analog- Thermocouple Input Module

Bulletin #30598-208-01D2 May, 1995

DI

Replaces 30598-208-01D1 Dated February, 1995

Page 2 read from a scan by OCR; it may hold reading errors

/\, CAUTION

EQUIPMENT DAMAGE HAZARD To avoid improper handling of equipment:

1. Never remove this device while power is ON. Turn power supply switch to OFF and wait until all indicating lights are off before removing.

2. Do not subject to static discharge. This module contains electronic components that are very susceptible to damage from electrostatic discharge.

Failure to observe this precaution can result in equipment damage.

/\, WARNING

HAZARDOUS VOLTAGE

Do not touch the terminal block or the circuit board while power input wiring is connected.

Failure to observe this precaution can result in severe personal injury or death.

PLEASE NOTE

Electrical equipment should be serviced only by qualified electrical maintenance personnel, and this document should not be viewed as sufficient instruction for those who are not otherwise qualified to operate, service or maintain the equipment discussed. Although reasonable care has been taken to provide accurate and authoritative information in this document, no responsibility is assumed by Square D for any consequences arising out of the use of this material.

TRADEMARK NOTICE SY/MAX, SY/NET, SY/LINK, SY/MATE, and TOPAZ are registered trademarks of Square D Company.

Page 3 read from a scan by OCR; it may hold reading errors

Table of Contents

Section Title Page [1 Description of the Type RIM126 MOdUIe...........-sssssesccsssssessescessssesseeesssessseesconseeescessseseseeets 1-1 1.1 UMtPODUCTION oo. eee ete ceeeeee cee seesseeecaeeseecaeeseeessesaeenecsaecaesseessecacesaesaessaeeascusssesaesaesieeusacateseestens 1-1 1.1.1. Gemeral PUrPOSC. oo... ecceeeecee cece ceesaesaeeenecseececesaeeesaessaecaeesaussecsecscenstesteseeeaeeneeaaens 1-1

1.1.2 Gereral Operation ooo... eee eee ccceceeeeeeeeeeereeseeseeceeseeseeeseaeescescaeeseeessaecsssecaeseeeecateneneestenssens 1-1

1.2 Front Panel Features... ccccccceseseceeeecscneeeeesseceeeseescneeesssaecesesuascasesseeesseeecessecseseecsseescssseeseseneaas 1-2

1.3 Side Panel Features oo... ee cece ce eeeceecceeceecessseseeseesecacesaecaesseeaesaesaessaeeaessaessecaeesseeseeatesseeaecaeeneees 1-2

2 Specificationsh......s.scccccosssecssssssssececssssesessesssseeesecesssssesesssssseesessssssssesessonseceesessnnsseeessessseeeeees 2-1 Ps i101 | 6 (0 | ce ee cee 2-1

2.2 PHYSICAL... eee cececccececeeeceseeeeeeseaeeecaeesaeceaeessaeensuecseesaecessecsaeecsecusesaeesseecsueseasessecsaeecseescauseenesseseates 2-2

2.3 Environmental .......... ccc ceeecesceeseeceeeeeeeeceecseeeceaeeeseeccesseecsseseeseesevessesseseeeceeecssaecesesessesesasenesensentess 2-2

2.4 Compatibility With RACKS oo... eee cececseeseeeeeeseeecsecseeecseecsenessaesasseeasseeseseesseesaesessesessecsetsesaesstenssaeaee 2-2

2.5 Compatibility with ProceSSOrs ............ccccccececsscsseesecescesecseeeessseeseecanesesessaceaeecsesassascasceaeeatecaesaneeateneaues 2-2

3 INStAaN ALION |... -ececcecsercccecenrccecccssececceceneccnccccaccceacdecasanacaanasansasasansasanansuscsansasanecanssentavansenssanes 3-1 3.1 Physical INSPeCtiON........... ccc ccs eeeeesceeesaeceseesessaeeaecaecececseesceceacsseceseseseeeeaessateaeesseaeecaecatensecseeasaneaaes 3-1 3.1.1 Ne@w MOdulle oo... ee eececcceescnccsseceeeeseceeeeeeeneeeesseeseecaesuaecaecaesssecseessecesssasssseseesasenusssesesaneas 3-1

3.1.2, Replacing Module 0.0... ee eeeccesesseceseeeeeteeseecaecsaeeaeseucsecseessecseeseesaessssseseassatessecsesessinesseas 3-1

B.2 KOYING oe. ees eeecneesseetecseesecsecneesnesecscuessaeesseesassasaecaeseeseesaessesacsseassasaesessdsareeecaceeeeesstesesanesasisenease 3-1

3.3 DIP Switch Settings...........ccccccccssesescscessccseeeseesseesscseesesesseseecseesseseceesessecsssseessessacauceseseutenessevaseaseass 3-2 3.3.1 Channel Range Selection ........0....ccccccccsccesscssecesseceseecsesecseceseseseeceeeecsuucsaseerecsesessacennesneentas 3-2

3.3.2 Function Group Range Selection ............ccccesccssesssesceseecsseseceeeeceeeecseeeseceseeceeseasueenessarentes 3-3

3.3.3 Border Selection oo... eee cecceseceeseeseeceesesseeecsecsesaeeseesessecacsavsesseesecaeceseaceesaueeersssaceuseusasesenaeaas 3-3

3.3.4 Temperature Readings Selection oo... ee cceseceseeeeceeenseseeseeeseceeecsessesseesaecaeessesseseeessesaees 3-3

3.3.5 Sample Selection... ccc cee ceceeecseeeseccecseceaesneeeaeceeeceessesseecseesaeeaeseesseseeesaeeesueseeessessaees 3-3

3.3.6 Alternate Scan Selection... cceccceceesesesseeseseeseeaeeseesesecseesesaecaecacsesseacsseetesuceessassenenes 3-4

3.3.7. Update Rate Selection (Series B or Later)...........cccccescccsecssessecsecesseseesecesseseesecsensaneveees 3-4

3.4 Field Wiring Terminations ............cceeeeecsccssceseceseessessecseeseeseeseeseesuescecsaceseesscasessesasesaseesesteseecsesareessess 3-4

3.5 Type RIM126 Start-up oo... ec cece ceececseeeeeeseeseseecaececsecsessesaecasgessesecnecsecsecsecsacassacsessesasegseassasensatens 3-5 3.5.1 Processor REQUIFEMENTS 0.0.00... cccececseecescesseceeeseseeeseecsuecaeeeaeesseecsueesssecseseatecstuseseeenentene 3-5

3.5.2 Indicator Light 0.0... ee cece cscceeeeeceeseeeseeeeaesaessessesaessesacsecaessessesa¢csesessesaesaeeeseuceessasseneeaes 3-6

4 = PFOQFAMMING]}.........ccsseesesseseseenensnessceesenssenseresensucenensaranenseneenasesuersuenesustasaesneseoeeesesenssensesaees 4-1 4.1 Register Usage and Rack Addressing .............:::csccessesseeceeeenseeesseeaecaeesaeesseetsseceaeceaeseasecsaeeseaeeseentess 4-1 4.1.1. Status and Error Register Table ............ cece eeeeesecneeceseseeseeesecseeenecaeesauseeseesseeeusaeesseeesenees 4-1

4.2 Programming Equipment ........... cece cccceeeeeeeseeeeeenectaesseseaeseeeueeesessesseessecesessesessesseesatsuarsaeecseneseas 4-1 4.3 Type RIM126 Register AlloCation ......... sc cccecceecceseesscssesseeseceseeeessscsecseesatensccucssesasesessenesuansanseateesees 4-4 4.3.1 Analog Input (Registers 1 - 8) oo. ceeseenecseceeeecsececeecaeseeeetensesenessetsesettaeascasensatens 4-1

4.3.2 | Thermocouple Status (Registers 9 & 10)... eeeecsseccesssesseecsaeecseesseeneessaeesaecseeeseeenees 4-2

4.3.3 DIP Switch Status (Registers 11 & 12) oo... ees cseeeecseeeeeeceecseseeeceeaeaeeaeeaeeeeseneeseeeesesaes 4-2

4.4 Sample Scaling Programs. ............ cc ccc sees ceseeseecseceesuesaessussaecaeseesecessessuesaessaseeeseesaeeenesseseeeeetenes 4-3

4.5 Program Editing 00... eee cecceeecsesesetseseeeeeeeeeessereeensceesaeseeeseeenaccaeeseceaesaessusseseeseseaesaeeyateaescaeanenes 4-3

5 Application Considerations] eseeseneusoueuensnsneeneessuerserssaesneeeanseeasaesoneseususnsenscessenanesseresensseeeeseees 5-1 5.1 Insertion and Removal Considerations .......... eee ceceeccesseceseeeseeecsesseeceanecaeesaeeseseeeecaeesesessaeessessnees 5-1

5.2 Wiring Considerations ............ccccececcesscesseceeecseeeeseecsaeseeeecseesnecseaecssscseseseeesaetesaececeeeessatessueensesseesates 5-1

5.3 Miscellaneous Considerations 22.0.0... cecececeeseceecssecseeseeeeeeseecsecseeseseeeeeeeseecetessecausessaeseeesessuesaeeesenss 5-1

5.4 Update Time ...... cece ccacecceseseessaeceeceseesseesesseccsecaeeesaeesenesaeeesastaeseneeseaestaeeneeseessaestsaeeneessaneatens 5-2

6 Troubleshooting | aeranensantansaresensensnssnssssaneosonnsansnnszasnnecnnonsrsedcorstususasarsuserassesessoserosensrarsacasaseecess 6-1 6.1 Diagnostic Light... eee cceceeseeesctsaeesseeesneceseesasseeecseeeesesesscesescsacsseeeesesessesnessaeeeaeecaesssseseressees 6-1

6.2 Using Programming Equipment .....................c2.ceccecceccecceecceseeeeeeseessensteseeneestessecateaceaecsecssseeesasnesease 6-1

6.3 Erratic Operation oo... eee cecececceeeeseeeseeeeeseesseescecseeseeeceaeessesaessassecsseseeseseseessaseasesseseseaesuarsarssseensene 6-2

| 7 Theory of Operation} sesaucusnsuceceecseuaesauausasensesensensenecsesenaeensesnsceseeseeceeeaaanaegerenseeeeensnaesessaasasenees 7-1 | Bibliography |..........ssesssesssesssnesssessneeseeessnesssesensesseesnsesssessseesnesssssssnsssuessneseneesssessuneeseceneesaneeed 7-2

Page 4 read from a scan by OCR; it may hold reading errors

30598-208 Page 1-1

1.0 DESCRIPTION OF THE TYPE RIM126 MODULE

1.1. Introduction

1.1.1. General Purpose

The Type RIM126 isolated analog/thermocouple input module can input up to eight channels of analog signals to any SY/MAX processor which possesses register I/O addressing capability.

Analog input signals are user-selectable for two types: high level analog and low level/thermocouple. High level analog signals include ranges of 0-20mA, 4-20mA, 0- 5VDC, 1-SVDC, 0-10VDC, +5VDC and +10VDC. Low level/thermocouple analog signals include +50mV, and thermocouple types J, K, T, E, B, N, R, S & C. See

All of the input signals are isolated channel-to-channel and channel-to-ground. The user can define two unique input function groups on the module, with each input function group monitoring different types and/or ranges of signals simultaneously. Sed Section 3.3

The RIM126 can be inserted into any slot of a register rack (except slot 1) or a register slot a digital rack.

Each RIM126 module utilizes twelve registers in the programmable controller system:

¢ The first eight registers correspond to the analog input data for input channels one through eight, one register per input channel. Each of these eight registers converts the high level analog current or voltage being measured into a value ranging from 0 to 9995 in increments of 5. This conversion provides a register value based on a percent of full scale, with 2 decimal place resolution for high level analog signals. Simple programming techniques allow these input readings to be scaled to engineering values, provided the processor being used has math capability. The low level/thermocouple values are converted directly to readings in degrees C or F.

¢ The ninth and tenth registers provide thermocouple status information such as open input detection and under/over range indication.

¢ The eleventh and twelfth registers provide software control of the module and allow the user to read the analog signal type and range for each of the two input function groups, as well as the group border definitions and software averaging routines, if desired.

Input update rate is selectable. In the FAST mode, input updates are performed rapidly, although accuracy is somewhat reduced. In the HIGH ACCURACY mode, better accuracy is achieved for the volt and millivolt ranges. but updates are not performed as often. See | Section 3.3.7

The RIM126 module requires no external power supply to operate since it draws power from the SY/MAX rack. No additional components, such as current loop resistors, are needed. No user adjustment of span and zero is required, since automatic calibration is performed by the onboard microprocessor. A removable terminal strip facilitates quick module replacement, and eliminates the need for extensive rewiring.

1.1.2 General Operation

The RIM126 module performs its tasks utilizing several subsystems. Channel-to-channel isolation is accomplished through the use of isolation amplifiers. An analog-to-digital converter (ADC) performs the actual conversion of the selected input channel, while the multiplexer (MUX), under the control of an on-board microprocessor, performs the channel selection. The auto-calibration system (ACS) provides zero and reference voltage. The module also contains a DC-to-DC converter to provide the +15VDC required.

For complete operational details well as a block diagram of RIM126 operation, see]Section 7|

1.2 Front Panel Features

Refer wo[Figure 14 The front of the RIM126 contains a terminal strip and a green RUN LED. The terminal strip contains eight groups of two terminals; each group corresponds to one input channel. One terminal in the group is for the positive wire of the signal source, the other is for both the negative and shield wire. The

Square D replacement part number for the terminal strip is D30617-083-50. For field wiring considerations, see

The RUN LED indicates the RIM126 microprocessor is functioning properly, however_it does not guarantee proper RIM126 operation. Seq Section 6.1| for a complete description of this LED.

Page 5 read from a scan by OCR; it may hold reading errors

30598-208 Page 1-2

Figure 1.1 - RIM126 Front Panel

Willi NGA HUGGED RREGTUT BARE tilt ou titi s > 2 7 a) =) s @ » | e] B L ® > 2 9

CUE villi Mi

Figure 1.2 - DIP Switch Access

1.3 Side Panel Features

Removing the side cover plate provides access to eight sets of six-position DIP switches and three sets of eight-position DIP switches. These switches are used to set input ranges, and to define the two input function groups. See| Section 3.3] for instructions on how to set these switches.

Page 6 read from a scan by OCR; it may hold reading errors

30598-208 Page 2-1

2.0 SPECIFICATIONS

2.1 Electrical

Inputs per module ....... Eight (two user-defined groups)

Registers required for rack addressing....... 12

User-definable function groups....... Two independent input function groups, each with its own range and number of inputs, can be created per module.

High-level ranges ....... Seven: 0-SVDC, 1-5VDC, 0- 10VDC, +1-5VDC, +10VDC,

0-20mA, 4-20mA

Thermocouple accuracy and repeatability:

Accuracy (% of full-scale) Repeat . bilit Type/ Fast Update High Accuracy ( % of Range Update* full- 0 ul 0 u seale) ° vera 5 vera @20°C 0-60°C @20°C 0-60°C J 0.3% 0.4% 0.3% 0.4% 0.1% K 0.25% 0.3% 0.25% 0.3% 0.1% T 0.5% 0.6% 0.5% 0.6% 0.2% E 0.5% 0.5% 0.5% 0.5% 0.15% R 0.5% 0.75% 0.5% 0.75% 0.15% S 0.4% 0.5% 0.4% 0.5% 0.15% N 0.5% 0.5% 0.5% 0.5% 0.15% B** 0.5% 0.5% 0.5% 0.5% 0.15% Cc 0.4% 0.5% 0.4% 0.5% 0.15% mV 0.2% 0.2% 0.1% 0.15% 0.05% v 0.4% 0.5% 0.1% 0.15% 0.05%

* The “HIGH ACCURACY” mode affects only the mV, current and V ranges (Series B1 or later)

** Type B thermocouple accuracy is +2.0% below 1500°F (815°C). Above this temperature the figures in the table above apply.

NOTE: The accuracies in the above table relate strictly to the RIM126. The accuracy of thermocouples varies greatly and should be taken into account when used with this module.

Calibration............

Under-range indication

Automatic

Low-level ranges........ Nine: +50mVDC, and thermocouple types J, K, T, E, B,N,R,S&C Thermocouple operation ranges (full-scale): Type Temp. Range, °F | Temp. Range, °C J -50 to +1400 -40 to +760 K -100 to +2250 -80 to +1240 T -200 to +660 -130 to +350 E -400 to +1250 -240 to +680 N -325 to +2010 -200 to +1100 R 0 to +3200 -20 to +1760 S 0 to +3200 -20 to +1760 B +500 to +3200 +260 to +1760 C 0 to +4200 -20 to +2320 Resolution: (VDC, mA, mV DC). . .Five parts in 10,000 (full scale range) Resolution: Thermocouple Types J,K,E,T ...... 0.5° (°C and °F) Thermocouple Types R,S,B,C...... 4°F, 2°C Thermocouple TypeN ............. 4°F, 2°C

(VDC, mA, mV DC). . Converted to -1 for the 1- SVDC and 4-20mA inputs at signals less than 0.9VDC and 3.6mA respectively. All other unipolar voltage ranges are converted to 0.

Under-range indication (Thermocouple)...... Provided in RIM126 register number 10; bits 1 through 8 turn ON for channels | through 8 respectively.

Page 7 read from a scan by OCR; it may hold reading errors

Page 2-2 30598-208

Over-range indication

(VDC, mA, mV DC). .

Over-range indication

(Thermocouple)... ..

Open input detection

(Thermocouple). ....

Update time: NOTE:

Converted to 9999, Use 2 in programming comparison rungs. (Converted to 9995 for Series B1, Rev. 2.01 only.)

Provided in RIM126 register number 10; bits 9 through 16 turn ON for channels 1 through 8 respectively

Provided in RIM126 register number 9; bits | through 8 turn ON for channels 1 through 8 respectively

“Update time” is defined as the time required for a change in input to be available to the SY/MAX processor/bus master. See Section 5.4 jon page 5-2.

FAST Mode........

HIGH ACCURACY

Maximum input overload...........

Overvoltage protection . .

Current loop resistors ...

Power requirements from SY/MAX supply. . .

Input impedances

Hi-level voltage. .... Hi-level current.....

LO level/ thermocouple. ......

12 milliseconds for all eight high-level input channels, 260 milliseconds for all eight thermocouple input channels

24 milliseconds for all eight high-level input channels, 285 milliseconds for all eight thermocouple input channels.

750V channel-to-channel and channel-to-ground (or analog circuit to digital logic circuit) continuously applied. 1500V transient isolation.

CURRENT RANGE: 30mA (continuous)

VOLTAGE AND THERMOCOUPLE RANGE: SOVDC (continuous) Clamping diode

250 ohm +0.05%, 25 PPM/deg. C (resident in the module)

1250 mA

1 Megohm 250 ohms

100 Megohms

Common mode rejection ratio ....... 110 dB A/D conversion........ 14-bit high speed Multiplexer type ....... AD7508, 16-channel, single-ended CMOS Microprocessor type and clock speed ......... 70116C-8 (8086 equiv.), 8MHz clock Indicator light ......... Green RUN LED indicates that microprocessor is operating correctly

Product certification ....

UL, CSA, FM 2.2 Physical Weight ............... 3.5 Ibs (1.6 kg) approx.

Dimensions (WxHxD)... 1.5 x 12.8 x 6.6 inches 3.8 x 32.5 x 16.8 cm

2.3 Environmental

Ambient temperature ratings:

Operational ......... 0 to 60°C Storage ............ -40 to +85°C Humidity rating........ 5-95% RH, non-condensing

2.4 Compatibility with Racks

The following SY/MAX Class 8030 racks are compatible with the Type RIM126 module:

¢ RRK100, RRK200, RRK300 (except the first slot of all RRK racks and slots 17 & 18 of RRK300)

HRK100, HRK150, HRK200 (register slots only) CRK210, CRK300 (register slot only) DRK210, DRK300 (register slot only) GRK110, GRK210 (register slot only)

2.5 Compatibility with Processors

The following SY/MAX Class 8030 and 8055 Type SCP programmable controllers can be used with the Type RIM126 module:

¢ SCP311 and 332 (Series E and later) « SCP323 and 344 (Series C and later) ¢ SCP313, 321, 322, 323, 333 (Series D and later)

* All Model 400, 450, 500, 600, 650 and 700 programmable controllers

Page 8 read from a scan by OCR; it may hold reading errors

30598-208 Page 3-1

3.0

INSTALLATION

3.1 Physical Inspection 3.1.1 New Module

The Type RIM126 module requires no additonal components to function, and requires no manual adjustments for zero and span since these adjustments are performed by the Automatic Calibration System.

The following compatibility checks must be made before plugging the RIM126 into a rack assembly. Refer to the section shown in parentheses for more information on each check.

¢ The desired range for the application is available (2.1)

¢ The proper range is selected

¢ The system processor is compatible|(2.6)

* The rack and necessary slot is availablg (2.4)

¢ The SY/MAX power supply is adequately sized (Section 2.1] and Instruction Bulletins 30598-159 and 30598-802).

* The rack is not keyed to prevent module insertion (3.2) Field wiring terminations are understood and 5.2).

¢ The required programming, especially Rack Addressing, is understood (see appropriate programmer Instruction Bulletin).

Z\ CAUTION

EQUIPMENT DAMAGE

Do not insert or remove the RIM126 while the rack is powered up, or while wires carrying input signals are connected to the module. See|Section 3.5|for general start-up procedures and|Section 5.1 |for application considerations regarding module insertion.

Failure to observe this precaution can result in equipment damage.

3.1.2 Replacing A Module

The RIM126 is installed by aligning the module edge connector with the desired slot in the rack and inserting the module so that it snaps into place. Secure to the rack using the module’s captive screw.

The RIM126 can be quickly and easily replaced with another module. There is no need to rewire the analog input points since the terminal strip can be removed by simply pulling it straight off the face of the module (Figure 3.1). The DIP switches in the replacement module must be properly coded for the desired range. No software reprogramming is necessary. See for application considerations regarding module insertion and removal.

Figure 3.1 - Terminal Block Removal

3.2 Keying

It is possible to key a particular slot on the rack assembly so that only the Type RIM126 module can be inserted there. A keying pin kit, Class 8030 Type CBP104, may be used to insert a keying pin between pins 67-68 and 69-70 of the appropriate slot, as described in the register rack Instruction Bulletin, 30598-265. The same procedure also applies to the register slot(s) of any digital rack.

The factory installed keying pin should not be removed from the register slots, as it ensures proper alignment between the slot pins and edge connector pads when the module is inserted or removed.