Manual · Square D
SY/MAX Class 8030 Type RIM126 Eight Channel Isolated Analog-Thermocouple Input Module
Manual22 pagesPDF 1.2 MB
Instruction bulletin for the Square D SY/MAX Class 8030 Type RIM126 eight channel isolated analog and thermocouple input module.
Covers · 2 models
The models it covers
Summary
What is in it
Square D instruction bulletin for the SY/MAX Class 8030 Type RIM126, an isolated input module that brings up to eight channels of analog or thermocouple signals into SY/MAX processors with register I/O addressing. It covers the module description, electrical, physical and environmental specifications, compatible racks and processors, installation with keying, DIP switch settings for ranges, function groups and update rate, field wiring, start-up, register programming, application considerations, troubleshooting and theory of operation.
Its parts
- Module Description
- Specifications
- Installation
- Programming
- Application Considerations
- Troubleshooting
- Theory of Operation
From the manual
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Square D's May 1995 instruction bulletin (30598-208-01D2) for the SY/MAX Class 8030 Type RIM126, an eight-channel isolated analog and thermocouple input module. It covers specifications, DIP switch setup, field wiring, start-up, register use, application considerations and troubleshooting. The text comes from a scan, so some tables and figures are garbled.
- Device
- SY/MAX module inputting up to eight isolated analog or thermocouple channels to any SY/MAX processor with register I/O addressing p. 4
- Input types
- High level current and voltage ranges, including 0-20mA, 4-20mA and 0-10VDC; low level millivolt and thermocouple types J, K, T, E, B, N, R, S and C p. 4
- Isolation
- Channel-to-channel and channel-to-ground p. 4
- Readings
- High level inputs as a value up to 9995 in steps of 5 (percent of full scale); thermocouples directly in degrees C or F p. 4
- Update time
- FAST: 12 ms for eight high level inputs, 260 ms for eight thermocouples; HIGH ACCURACY: 24 ms and 285 ms (Series B1 Revision 2.0 or later) p. 11
- Resolution
- Five parts in 10,000 of full scale for VDC, mA and mV; 0.5° for thermocouple types J, K, E, T p. 6
- Thermocouple ranges
- Type J: -40 to +760 °C; Type K: -80 to +1240 °C; Type C: -20 to +2320 °C p. 6
- Registers
- 12 registers: 1-8 channel values, 9 open input bits, 10 under- and over-range bits, 11-12 DIP switch status p. 4, 14
- Power and calibration
- Powered from the SY/MAX rack, no external supply or current loop resistors; automatic calibration, no span or zero adjustment p. 4
- Racks
- RRK100, RRK200, RRK300 (not slot 1, not slots 17 & 18 of RRK300); HRK100, HRK150, HRK200, CRK210, CRK300, DRK210, DRK300, GRK110, GRK210 register slots p. 7
- Processors
- SCP311 and 332 (Series E and later), SCP323 and 344 (Series C and later), SCP313, 321, 322, 323, 333 (Series D and later); Model 400, 450, 500, 600, 650 and 700 p. 7
- Programming equipment
- SY/MAX CRT programmers SPR250, SPR260, SPR300, SPR310; SY/MATE software SYM322/422, SYM323/423/533, SYM324/424/534 p. 14
- Size and environment
- 1.5 x 12.8 x 6.6 inches, 1.6 kg approx.; 0 to 60°C operating, -40 to +85°C storage; 5-95% RH non-condensing p. 7
- Terminal strip
- Removable; Square D replacement part number D30617-083-50 p. 4
What this manual walks you through
- Setting the channel range switches SW1 to SW8 p. 9
- Defining the two function groups and their border p. 10
- Choosing degrees C or F and input averaging p. 10, 11
- Channel 1 priority scan and update rate selection p. 11
- Wiring high level transmitters and thermocouples p. 11, 12
- Checking the module at start-up from its status bits p. 12
- Register allocation and status codes p. 14
- Wiring practice and noise avoidance p. 17
- Troubleshooting with the RUN LED and status codes p. 19, 20
Good to know
- Never insert or remove the module with the rack powered or input wires connected; it can halt the processor with an I/O error. p. 17
- Do not change DIP switch settings while power is applied. p. 9
- On high level voltage ranges, wire length is limited to about 50 feet; ground the shield only at the RIM126 C terminal. p. 17
- A lit RUN LED does not prove correct operation; the multiplexer or converter can fail while it shows normal. p. 19
- Unused channels on voltage ranges may show non-zero values; switching in their current loop resistors (position 4 of SW1-SW8) prevents this. p. 12
Questions this manual answers
What thermocouple types does the Square D RIM126 accept?
Types J, K, T, E, B, N, R, S and C, plus a low level millivolt range. p. 4
What does status code C7 mean on the RIM126?
Bits 25 to 32 reading 11000111 (C7 hex) mean normal operation for registers 1-10; other patterns flag EPROM or RAM, DC-DC or watchdog failure. p. 12, 14
Why is the RIM126 RUN LED off?
If it never lights, the module gets no DC power; if it flashes and goes off, power-up failed, possibly from weak rack power or no processor or remote interface in the rack. p. 19
Does the 8030-RIM-126 need an external power supply?
No. It draws power from the SY/MAX rack and needs no external current loop resistors. p. 4