Page 1 of SY/MAX Class 8030 Type RIM126 Eight Channel Isolated Analog-Thermocouple Input Module

Manual · Square D

SY/MAX Class 8030 Type RIM126 Eight Channel Isolated Analog-Thermocouple Input Module

Manual22 pagesPDF 1.2 MB

Instruction bulletin for the Square D SY/MAX Class 8030 Type RIM126 eight channel isolated analog and thermocouple input module.

Download the PDF1.2 MB

Covers · 2 models

The models it covers

Summary

What is in it

Square D instruction bulletin for the SY/MAX Class 8030 Type RIM126, an isolated input module that brings up to eight channels of analog or thermocouple signals into SY/MAX processors with register I/O addressing. It covers the module description, electrical, physical and environmental specifications, compatible racks and processors, installation with keying, DIP switch settings for ranges, function groups and update rate, field wiring, start-up, register programming, application considerations, troubleshooting and theory of operation.

Its parts

  1. Module Description
  2. Specifications
  3. Installation
  4. Programming
  5. Application Considerations
  6. Troubleshooting
  7. Theory of Operation

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Square D's May 1995 instruction bulletin (30598-208-01D2) for the SY/MAX Class 8030 Type RIM126, an eight-channel isolated analog and thermocouple input module. It covers specifications, DIP switch setup, field wiring, start-up, register use, application considerations and troubleshooting. The text comes from a scan, so some tables and figures are garbled.

Read for this summary: pages 1 to 2, 4 to 7, 9 to 12, 14, 17 and 19 to 20 of 22.

Device
SY/MAX module inputting up to eight isolated analog or thermocouple channels to any SY/MAX processor with register I/O addressing p. 4
Input types
High level current and voltage ranges, including 0-20mA, 4-20mA and 0-10VDC; low level millivolt and thermocouple types J, K, T, E, B, N, R, S and C p. 4
Isolation
Channel-to-channel and channel-to-ground p. 4
Readings
High level inputs as a value up to 9995 in steps of 5 (percent of full scale); thermocouples directly in degrees C or F p. 4
Update time
FAST: 12 ms for eight high level inputs, 260 ms for eight thermocouples; HIGH ACCURACY: 24 ms and 285 ms (Series B1 Revision 2.0 or later) p. 11
Resolution
Five parts in 10,000 of full scale for VDC, mA and mV; 0.5° for thermocouple types J, K, E, T p. 6
Thermocouple ranges
Type J: -40 to +760 °C; Type K: -80 to +1240 °C; Type C: -20 to +2320 °C p. 6
Registers
12 registers: 1-8 channel values, 9 open input bits, 10 under- and over-range bits, 11-12 DIP switch status p. 4, 14
Power and calibration
Powered from the SY/MAX rack, no external supply or current loop resistors; automatic calibration, no span or zero adjustment p. 4
Racks
RRK100, RRK200, RRK300 (not slot 1, not slots 17 & 18 of RRK300); HRK100, HRK150, HRK200, CRK210, CRK300, DRK210, DRK300, GRK110, GRK210 register slots p. 7
Processors
SCP311 and 332 (Series E and later), SCP323 and 344 (Series C and later), SCP313, 321, 322, 323, 333 (Series D and later); Model 400, 450, 500, 600, 650 and 700 p. 7
Programming equipment
SY/MAX CRT programmers SPR250, SPR260, SPR300, SPR310; SY/MATE software SYM322/422, SYM323/423/533, SYM324/424/534 p. 14
Size and environment
1.5 x 12.8 x 6.6 inches, 1.6 kg approx.; 0 to 60°C operating, -40 to +85°C storage; 5-95% RH non-condensing p. 7
Terminal strip
Removable; Square D replacement part number D30617-083-50 p. 4

What this manual walks you through

  • Setting the channel range switches SW1 to SW8 p. 9
  • Defining the two function groups and their border p. 10
  • Choosing degrees C or F and input averaging p. 10, 11
  • Channel 1 priority scan and update rate selection p. 11
  • Wiring high level transmitters and thermocouples p. 11, 12
  • Checking the module at start-up from its status bits p. 12
  • Register allocation and status codes p. 14
  • Wiring practice and noise avoidance p. 17
  • Troubleshooting with the RUN LED and status codes p. 19, 20

Good to know

  • Never insert or remove the module with the rack powered or input wires connected; it can halt the processor with an I/O error. p. 17
  • Do not change DIP switch settings while power is applied. p. 9
  • On high level voltage ranges, wire length is limited to about 50 feet; ground the shield only at the RIM126 C terminal. p. 17
  • A lit RUN LED does not prove correct operation; the multiplexer or converter can fail while it shows normal. p. 19
  • Unused channels on voltage ranges may show non-zero values; switching in their current loop resistors (position 4 of SW1-SW8) prevents this. p. 12

Questions this manual answers

What thermocouple types does the Square D RIM126 accept?

Types J, K, T, E, B, N, R, S and C, plus a low level millivolt range. p. 4

What does status code C7 mean on the RIM126?

Bits 25 to 32 reading 11000111 (C7 hex) mean normal operation for registers 1-10; other patterns flag EPROM or RAM, DC-DC or watchdog failure. p. 12, 14

Why is the RIM126 RUN LED off?

If it never lights, the module gets no DC power; if it flashes and goes off, power-up failed, possibly from weak rack power or no processor or remote interface in the rack. p. 19

Does the 8030-RIM-126 need an external power supply?

No. It draws power from the SY/MAX rack and needs no external current loop resistors. p. 4

What cable should be used with the RIM126?

Shielded twisted pair such as Belden 8760 for high level signals, and shielded thermocouple extension wire for thermocouples. p. 11, 17

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. SY/MAX Type RIM1261
  2. 8-Channel Isolated1
  3. Analog-Thermocouple1
  4. Input Module1
  5. Precautions2
  6. 1: Module Description4
    1. 1.1 Introduction4
    2. 1.2 Front Panel Features4
    3. 1.3 Side Panel Features5
  7. 2: Specifications6
    1. 2.1 Electrical6
    2. 2.2 Physical7
    3. 2.3 Environmental7
    4. 2.4 Compatibility with Racks7
    5. 2.5 Compatibility with Processors7
  8. 3: Installation8
    1. 3.1 Physical Inspection8
    2. 3.2 Keying8
    3. 3.3 DIP Switch Settings9
    4. 3.4 Field Wiring Terminations11
    5. 3.5 RIM126 Start-Up12
  9. 4: Programming14
    1. 4.1 Register Usage & Rack Addressing14
    2. 4.2 Programming Equipment14
    3. 4.3 Register Allocation14
    4. 4.4 Sample Scaling Program16
    5. 4.5 Program Editing16
  10. 5: Application Considerations17
    1. 5.1 Insertion & Removal17
    2. 5.2 Wiring17
    3. 5.3 Miscellaneous17
    4. 5.4 Update Times18
  11. 6: Troubleshooting19
    1. 6.1 Diagnostic Light19
    2. 6.2 Using Programming Equipment19
    3. 6.3 Erratic Operation20
  12. 7: Theory of Operation21
  13. Bibliography22

From the PDF’s own bookmarks.

The whole text · 3 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 81-8
  2. Pages 9 to 169-16
  3. Pages 17 to 2217-22

The file

Revision and size

RevisionBulletin #30598-208-01D2, May, 1995
PublisherSquare D
Pages22
PDF1.2 MB
TextThe pages are scans; their text was read by OCR, which may hold reading errors.