30598-208 Page 5-1

5.0 APPLICATION CONSIDERATIONS

5.1. Insertion and Removal Considerations

/\ CAUTION

EQUIPMENT DAMAGE

Do not insert or remove the RIM126 whife the rack is powered up, or while wires carrying input signals are connected to the module. See Section 3.5 for general start-up procedures.

Failure to observe this precaution can result in equipment damage.

* NEVER INSERT OR REMOVE THE RIM126

MODULE WHILE IT IS POWERED UP. Doing so can generate bus errors in the system, causing the processor that is connected to the RIM126 to go to HALT (due to an I/O ERROR condition).

If this type of error is generated in the processor, and the processor keyswitch is in the RUN position, clear the error by toggling the processor keyswitch to HALT and then back to RUN.

Prior to installing the RIM126, do not remove the factory installed keying pins from the slots in the rack assembly. These keying pins act as guides to ensure that the card edge connector on the module mates properly with the rack’s slot connector.

followed carefully. Polarity and wiring may differ from manufacturer to manufacturer.

The RIM126 should be treated as any load which is part of a signal loop. Note that 2-wire and 4-wire transmitterwirin arities will typically differ. Refer to Figured 3.7jan 3.8

The shield portion of the input cable must be connected only to the RIM126 module’s “C” terminal. At the transmitting device’s end (near the thermocouple, for example), the shield should be peeled back and insulated to prevent contact with other signal carrying wires. Do not attach the shield to the transmitting device.

This practice of singly grounding the shield is especially applicable when a cable has been spliced or nicked. The shield must be insulated along its entire length, and never be allowed to come in contact with any other surface.

The unshielded portions of the wire run (such as at the transmitting device and at the RIM126) should be kept as short as possible.

Wires carrying analog signals must be routed as far as possible from potential sources of noise such as motors, transformers, contactors, etc. Be especially suspicious of any AC devices. As a rule of thumb, allow six inches (15.2 cm) minimum separation for every 120 volts. Analog signal wires must never share the same conduit with AC wiring. On occasions where analog signal cabling must pass close to AC wiring, make sure it does so at right angles.

5.2 Wiring Considerations we . . ¢ Transmitting devices must never share the same signal

¢ Confirm that the RIM{126 and all signal-generating return Wire.

devices are powered down before connecting any signal carrying wiring to the input channels. Differences in ground potentials between the analog and digital portions of the RIM126 may cause problems if this is not done.

The cabling between high-level input devices and the RIM126 should consist only of shielded twisted-pair wire such as Belden 8760. The shield in this wire

The 0-20 and 4-20mA current range settings will have better noise immunity than the voltage range settings.

When operating on a high level voltage range, the allowable length of wire between the transmitting device and the RIM126 is limited by capacitance build-up to approximately 50 feet.

When operating on a current range, cable length is limited by the drive capability of the transmitter (typically 600-1000 ohms) and the total loop resistance.

protects the center conductors from noise, while the twisting of the conductors helps to ensure that any noise that does penetrate the shield will influence both conductors equally. In this way, the differential signal level between the two conductors is maintained, and the signal is preserved due to the common-mode rejection that is designed into the RIM126. The cabling between thermocouples and the RIM126 must consist of shielded thermocouple extension wire.

Consult the bibliography at the end of this instruction bulletin for additional] sources of information regarding wiring of analog signals.

5.3 Miscellaneous Considerations

* REGISTER ASSIGNMENT. When using the RIM126, eight to twelve registers can be assigned to the slot in which it is installed.

« Make sure that the conventions and_ instructions supplied by the manufacturer of the input devices are

Page 18 read from a scan by OCR; it may hold reading errors

Page 5-2 30598-208

NOTE: The RIM126 actually has 16 onboard registers. Registers 13 to 16 are used for manufacturer’ s testing and are NOT available to the user. If it is necessary to assign more than 12 registers to the RIM126’s slot (to allow for future expansion, etc.) keep in mind that registers 13 through 16 CANNOT be used for data storage or other functions.

* PROCESSOR/REGISTER COMPATIBILITY. When the RIM126 resides in the same rack assembly as a SY/MAX Model 500 or 700 processor, either 8 or 12 registers must be assigned to the module. Refer to the instruction bulletin for the Model 500 (30598-105) or Model 700 (30598-107) for details.

* UNUSED INPUTS. Due to the nature of CMOS multiplexing circuitry, non-zero values may appear across the positive and “C” terminals of the RIM126 when using its voltage, even with no wires connected to the terminals. This is caused by the RIM126’s high input impedance, and is normal. This condition can be eliminated by selecting the current loop resistors for unused channels (position 4 of SW1 through SW8 = ON for | through 8, respectively).

« DIP SWITCHES. NEVER ALTER THE DIP SWITCH SETTINGS FOR “RANGE” WHILE THE RIM126 IS POWERED UP. These switches control the gain of various front-end stages, and improper settings made with power applied will cause permanent damage to the RIM 126.

« ISOLATION. Since the RIM126 “C” (common) inputs are individually isolated, analog input signals with different ground references and grounded or ungrounded thermocouples can be attached to the same module without producing erroneous readings.

¢ RESOLUTION. Analog accuracy is_ inherently temperature sensitive; the specified overall accuracy of +0.15% of full-scale will improve to +0.1% at room temperature.

5.4 Update Times

« The UPDATE TIME is the time required for a change in the analog input signal to be made available to the SY/MAX bus master.

* If the RIM126 is used in the same rack assembly as the SY/MAX processor, the processor is the bus master. If the RIM126 is configured in the remote rack of a remote interface (RI) or remote transfer interface (RTD system, then the RI module or RTI module is the master. Refer to instruction bulletin 30598-247 (remote interface system) or 30598-251 (remote transfer interface system) for more details on how these modules effect system response time.

¢ In Series B1 (or later) modules, the setting of DIP switch 11, position 2 (FAST or HIGH ACCURACY mode), has an effect on the update time.

The following is a summary of update time for the Series B1, Revision 2.00 RIM126 module. Update times when using (1) All standard analog ranges, (2) All thermocouple ranges, and (3) A mixture of standard and thermocouple ranges are examined.

1. ALL STANDARD ANALOG RANGES: With the FAST update mode selected, and only standard analog ranges in use, the average update time of the RIM126 is 12 milliseconds. This figure applies no matter how many channels are activated. If the ALTERNATE SCAN mode is used, Channel | is updated every 7 milliseconds while Channels 2 through 8 are updated every 16 milliseconds. If the HIGH ACCURACY (slower scan) mode is used, all the above times will aproximately double.

2. ALL THERMOCOUPLE RANGES: With the FAST update mode selected and a single thermocouple channel active (other channels set to “not used”), the average update time for that channel is 130 milliseconds. Each additional thermocouple channel that is activated will add five milliseconds to the update time. With all eight channels reading thermocouple signals, each channel is updated approximately every 165 milliseconds. If the HIGH ACCURACY mode is selected, the update time will increase by less than 10%.

If a single +50 millivolt channel is selected with other channels unused, the update time for that single channel will be about 45 milliseconds. Add three milliseconds for each additional +50 millivolt channel activated.

3. A MIXTURE OF STANDARD ANALOG AND THERMOCOUPLE RANGES: If two “function groups,” one standard analog and one thermoc are defined, update times are as shown in the chart] below. The times shown are with the FAST update mode selected.

Number of Channels Update Time Set to: for:

8 0 12ms

7 1 24 ms 155 ms 6 2 26 ms 170 ms 5 3 28 ms 185 ms 4 4 30 ms 200 ms 3 5 32 ms 215 ms 2 6 34 ms 230 ms 1 7 36 ms 245 ms 0 8 --- 260 ms

Page 19 read from a scan by OCR; it may hold reading errors

30598-208 Page 6-1

6.0 TROUBLESHOOTING

6.1 Diagnostic Light

Although the green RUN LED indicates that the RIM126 microprocessor is functioning properly, other problems not directly related to the microprocessor may be occurring,[Section 35] lists some of the situations in which the RUN LED may be ON, but the analog signais are not being properly converted. In other words, an illuminated RUN light does not always indicate proper RIM126 operation; a RUN LED that is OFF, however

(with power applied to the rack), indicates a definite problem.

Failures experienced by the RIM126 module are classified as fatal or non-fatal.

Fatal errors are indicated by the RUN LED remaining OFF. Recovery (when possible) can only be accomplished by cycling power to the rack in which the module is inserted.

During a non-fatal error, the RIM126 RUN LED is illuminated but the processor (or drop) may refuse to go into RUN. Simple toggling of the processor keyswitch to HALT and back to RUN may be sufficient to clear the error.

Distinctions between fatal and non-fatal errors are handled in this fashion because under certain “cold start” conditions, the RIM126 circuitry may require a brief warm-up period. Such a condition is not a true module error, but rather a normal physical limitation which clears itself after a brief period of time. In these cases, toggling the processor keyswitch is sufficient to allow the system to recover.

If the RUN LED fails to come on at all, the module is not receiving DC power; check to see that the rack is connected to a properly sized SY/MAX power supply which itself is producing power.

If the RUN LED flashes briefly upon the application of power and then remains OFF, the RIM126 module has failed to complete its power-up sequence and is experiencing a fatal error. Once again, this does not necessarily indicate a defective RIM126 module. The DC power from the rack may be inadequate to sustain operation. This brief flash will also occur if there is no processor or remote interface module located in the same rack, since the RIM126’s microprocessor can sense that there is no device present with which to communicate.

If the RUN LED refuses to illuminate, try installing the module in a configuration in which these possibilities can be ruled out. See| Section 3.5.1]for three examples of simple system layouts.

If the module is proven to be defective, register status bits will identify the reason. Seq Section 6.2

/\, CAUTION

EQUIPMENT DAMAGE HAZARD

The RIM126 module must never be inserted or removed from the rack while under power. This principle must be observed when performing any troubleshooting.

Failure to observe this precaution can result in equipment damage.

6.2 Using Programming Equipment

If the RUN LED is ON, the next step is to check the controlling processor to verify that communication has been established. This is best done by using a programming device’s DATA mode to examine the registers that are assigned to the analog input channels.

Status bits 25 through 32 of the respective registers reveal a great deal of information} Section 4.1.1|contains a table that describes these status bits and their meaning.

If none of the bit patterns in Section 4.1.1 appear, suspect a rack addressing problem. See instruction bulletin 50598-165 or 30598-167.

The bit patterns in Section 4.1.1 may be interpreted as follows:

Normal Operation - All digital circuitry is functioning reliably. Applying an analog signal (within the intended operating range) should cause changes in the assigned storage register to reflect the changing input. If this does not occur, suspect either the signal generating device or the analog portion of the RIM126 module.

NOTE: If is possible for the multiplexer or the analog-to-digital converter chip to malfunction and still give the indication of normal operation via the RUN LED.

Page 20 read from a scan by OCR; it may hold reading errors

Page 6-2 30598-208

EPROM Failure - The RIM126 is defective and must be replaced.

DC-DC Failure - The DC power being supplied to the digital circuitry of the RIM126 is insufficient for reliable operation. If the SY/MAX power supply powering the rack is functioning properly, the fault lies with the DC-to- DC converter inside the RIM126 module. The module must be replaced if its DC-to-DC converter is defective.

Watchdog Failure - A failure of the RIM126’s microprocessor to prevent the watchdog circuit from timing out. If this condition occurs, power down the rack in which the module resides and the reapply power. If the module comes up in the Normal Operation mode, the condition which caused the fault has been eliminated. If, however, the same error code is produced, the RIM126 is defective and must be replaced.

No Card Acknowledged In Slot - The processor is not aware of the RIM126’s presence. Try reinserting the module to make sure that it is seated properly. If this doesn’t work, check the rack slot addressing for proper allocation of registers and slots.

Slot Not Addressed - The overall programmable controller system is not properly configured.

6.3 Erratic Operation

One cause of erratic operation is improper grounding and routing of signal wires.

Ensure that the programmable controller system is grounded per the instructions in the “Planning and Installation Guide” instruction bulletin (30598-175).

Also, confirm that the shield of each analog signal wire is connected to the “C” terminal of the RIM126 and that the other end (transmitting device’s end) is not grounded. See Section 5.2 ffor other wiring considerations.

If the defective element in the system can still not be tracked down, try one or_more of the sample hardware configurations shown in| Section 3.5.1] Because of their simplicity, these example layouts can help narrow down the source of the problem.

Page 21 read from a scan by OCR; it may hold reading errors

30598-208 Page 7-1

7.0 THEORY OF OPERATION

This section describes the various RIM126 subsystems. Refer to the block diagram on page 7-2| (Figure 7.1) while reading this section.

The operation of the module is governed by a Type uD70116C-8 (80C86) microprocessor running at 8MHz. It controls such tasks as power-up and diagnostic checks, monitoring of DIP switch selections, software signal averaging (when selected), and communications to the SY/MAX processor. Also controlled by _ the microprocessor are the multiplexer, gain/offset stage selections, the Automatic Calibration System (ACS) and the Analog-to-Digital Converter (ADC).

The RIM126 module has its own DC/DC power supply which converts the SVDC from the SY/MAX power supply to the +15 VDC required by some of the RIM126’s analog circuitry. A -5VDC output furnishes power required by the digital circuitry, and balance of the analog circuitry, of the RIM126.

The RIM126 employs a Type AD7506 sixteen channel, single-ended CMOS multiplexer (MUX) to switch, in turn, each of the eight input channels into the ADC. This MUX also switches the on-board precision voltage reference, ground, and two cold junction temperature sensors that provide reference signals to the ADC.

The analog MUX selects an input channel to feed to the ADC system. The ADC used in the RIM126 is a 14-bit high-speed A/D converter. The 14-bit resolution (1 part in 16,384) of this ADC is mathematically “compressed,” for reasons of accuracy, to 5 parts in 10,000 for use in the RIM126.

The analog circuitry of the module is designed to float at the potential of the analog input common. Isolation of power and signal is achieved through the use of isolation amplifiers.

The ACS, under the control of the isolated microprocessor, eliminates the need for externally calibrated input signals. Adjustments to eliminate initial errors in system offset and gain are performed internally. The ACS uses protected CMOS switches to apply both a precision voltage (5.000V) and analog ground (0.0000V) signal to the ADC. These signals are fed through each gain and offset stage currently in use by the RIM126 to provide a base line. When subsequent conversions are performed on field-produced analog input signals, the conversion circuitry errors are eliminated using a Y=mX-+b software algorithm, providing corrected digital information to the user. Accurate ACS operation is dependent on the following points:

1. The initial accuracy of the 5V reference must be high; the RIM126 accuracy is 5.0000V +0.0002V (less than 1/4 of 1 bit worst case).

2. The temperature drift of the reference must be low; the RIM126 drift is 0.3 to O.Sppm/deg. C typical.

l ) depicting all these subsystems appears in Figure 7.1.

Page 22 read from a scan by OCR; it may hold reading errors

LOGIC SUPPLY

DIGITAL SECTION r - SY/MAX |, BUS

Page 7-2 30598-208 ISOLATION SCALING AMPLIFIER INPUT 1, - 4 COMMON 1, dL g50 +/-15VDC AMP SUPPLY INPUT 2, - > COMMON 2, - > AMPLIFICATION SCALING MUX - - - OO, - > - | +~AD ISO = ro SCALING AMP INPUT 8 COMMON 8 ~ ISOLATION BARRIER.” VOLTAGE MICRO- REFERENCE PROCESSOR GROUND, REFERENCE © AMBIENT TEMP #1 AMBIENT TEMP #2

BIBLIOGRAPHY

Figure 7.1 - Block Diagram

IEEE Std 518-1977, Guide for the Installation of Electrical Equipment to Minimize Electrical Noise Inputs to Controllers from External Sources.

IEEE

Std 142-1982, Recommended Practice for

Grounding of Industrial and Commercial Power Systems.

Ott, Henry W. Noise Reduction Techniques in Electronic Systems. New York: Wiley - Interscience, 1976.

DIP

SWITCHES