Square D catalog for the Class 8501 Type X family of NEMA industrial control relays. It covers AC control relays such as the XO30 and XO40, AC timing, latching and master relays, DC control, latching, timing and utility relays, accessories (latch and timer attachments, adder decks, contact cartridges, mounting track, enclosure), voltage codes and how to order, application data with contact ratings, contact arrangements and replacement coils, life-load guidance, product data on isolation and construction, and dimensions.
Its parts
- General
- Accessories
- Application Data
- Product Data
- Dimensions
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Square D catalog 8501CT9601 (December 1996) for the Class 8501 Type X NEMA industrial control relays, covering the AC control relays such as the XO30 and XO40 along with timing, latching, master, DC and utility versions. It explains ordering, accessories, contact ratings and pole arrangements, replacement coils, contact life and dimensions. It also shows how to convert a contact between normally open and normally closed.
- Device
- Class 8501 Type X NEMA industrial control relay, AC operated, with plug-in convertible contact cartridges p. 2, 3
- Contacts
- 8501-XO30: 3 normally open; 8501-XO40: 4 normally open (first number after XO is N.O., second is N.C.) p. 2, 3
- Contact rating
- NEMA A600: 600 VAC spacings, 10 A continuous, 60 A make and 6 A break at 120 VAC inductive p. 8
- Coil voltage range
- AC operation +10/-15%; DC operation +10/-20% p. 6
- Operating times
- AC relay: 15 ms pick-up, 16 ms drop-out (average) p. 6
- Operating temperature
- -40°C to +71°C (-40°F to +160°F) p. 6
- Ordering
- Class, Type, voltage code and any forms, for example 8501 XO40 V02 Y414 p. 2
- Expansion
- Basic relay holds 4 cartridges; XB20 or XB40 adder deck makes 6 or 8 poles, a second deck 10 or 12 p. 2, 5
- Contact cartridges
- XC1 standard (black), XC2 overlapping (red), XC4 master 20 A (blue); logic reed (grey) only in XBR adder decks p. 5, 9
- Attachments
- XL AC latch, XDL DC latch; XTE On Delay and XTD Off Delay pneumatic timers, 0.2-60 or 5-180 seconds; XJ1 timer lockout cover p. 3, 5
- Wiring
- Self-lifting pressure connectors take up to two #12-18 AWG stranded copper wires; Form Y414 for ring or spade lugs p. 2, 3
- Replacement coil
- AC coils: prefix 9998-X followed by a suffix number for the voltage p. 7
- Contact construction
- Single-throw double-break silver-cadmium-oxide contacts, each isolated from the others; DC rating NEMA P600 p. 9
- Enclosure
- NEMA Type 1 enclosure Class 9991 Type UE7 for a single relay p. 5
What this manual walks you through
- Converting a contact between normally open and normally closed p. 2
- Ordering a relay by class, type, voltage code and form p. 2, 3
- Choosing AC control, timing, latching and master relays p. 3
- Choosing DC control, timing, latching and utility relays p. 4
- Ordering accessories: latches, timers, adder decks, cartridges, track and enclosure p. 5
- Contact ratings and factory pole arrangements p. 6
- Finding the replacement AC or DC magnet coil p. 7
- Understanding contact ratings and estimating contact life p. 8
- Contact cartridge types, construction and uses p. 9, 10
- Dimensions and shipping weights p. 11
Good to know
- For automatic sequencing, NEMA ICS 5-1993 recommends loads under 25% of the 60 A make and 6 A break ratings. p. 8
- At most 8 N.C. contacts are allowed on 9-12 pole relays. p. 3
- Up to 6 master cartridges fit a 7 or 8 pole AC relay; none may be used on 9-12 pole AC or DC-operated relays. p. 5
- With ring lugs, UL Listing holds only with AMP Plasti-Grip #32958 insulated-barrel ring-tongue lugs. p. 2
- Logic reed cartridges are for resistive loads only. p. 10
Questions this manual answers
How many contacts does a Square D 8501 XO40 relay have?
Four normally open contacts, each convertible to normally closed; adder decks can take it to 8 or 12 poles. p. 2, 3
How do I change a Type X contact from normally open to normally closed?
Remove the cover and T-bar actuator, pull the contact cartridge, turn it 180 degrees, plug it back in and refit the actuator and cover. p. 2
What is the contact rating of a Class 8501 Type X relay?
NEMA A600: 600 VAC spacings, 10 A continuous, and 60 A make with 6 A break at 120 VAC for an inductive load. p. 8
What temperature range can a Type X relay work in?
-40°C to +71°C (-40°F to +160°F). p. 6
What replacement coil fits an 8501 Type X AC relay?
An AC magnet coil numbered 9998-X followed by the suffix number for the coil voltage and frequency. p. 7