The text of a manual · part 2 of 2
Industrial Control Relays Type X Class 8501, pages 7 to 12
Pages 7 to 12 of 12
The original document is the PDF (355 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Square D 8501-XO30, Square D 8501-XO40, Schneider 8501-XO30 and Schneider 8501-XO40
Page 7
Industrial Control Relays Type X, NEMA Type Relays Application Data
Replacement AC Magnet Coils For Relays Equipment to be serviced Class
Type
Poles
Coil Prefix or Class and Type
8501
X
All
9998-X
Suffix Number (Complete Coil Number consists of Prefix or Class and Type followed by Suffix Number) Hz
60 50
Coil Volt-Amperes
24 Volts
110-115 Volts
120 Volts
208 Volts
220 Volts
240 Volts
277 Volts
380 Volts
440 Volts
480 Volts
550 Volts
600 Volts
Inrush
Sealed
23 24, 44
44, 51 52
52 53
53, 55, - - - 62
62, - 65
65, 148 143
23 25
Replacement DC Magnet Coils For Relays Equipment to be serviced
Coil Prefix or Class and Type
Suffix Number (Complete Coil Number consists of Prefix or Class and Type followed by Suffix Number) 6 Volts
12 Volts
18 Volts
24 Volts
32 Volts
48 Volts
64 Volts
72 Volts
90 Volts
110 Volts
115/125 Volts
220 Volts
230/250 Volts
Coil Burden Watts
Class
Type
Poles
XD
All
9998 XD
19
28
34
37
40
46
49
52
55, 58, 67
18
8501
XDL, 9998 XDL
19B
28B
34B
37B
40B
46B
49B
52B
55B, 58B, 67B
50
XUD
All
9998 XUD
19
28, 37, 46, - - - 58*, 67*
16
7
Page 8
Industrial Control Relays Type X, NEMA Type Relays Application Data Definition of Ratings
Contact Life
Control relays are designed for switching inductive and resistive loads in both AC and DC circuits. By far, the greatest number of applications involve the switching of inductive loads in AC circuits. Typical loads include solenoids and operating coils of such devices as other relays, timers, starters and contactors.
The life of control relay contacts depends upon the magnitude and characteristics of the electrical load, inductance, duty cycle, mechanical properties of the device in which they are used, voltage fluctuations, environment, etc. The Class 8501 Type X relay carries a NEMA A600 rating. NEMA A600 relays have 600 VAC spacings, a 10 ampere continuous rating, a 60 ampere make rating, and a 6 ampere break rating at 120 volt AC for an AC inductive load.
• Resistive Rating - Indicates the resistive load that the contacts can make, break or carry continuously. Resistive ratings are based on a 75% power factor. • Inductive Rating - Refers to loads such as coils of contactors, starters and relays and solenoids that contacts can make, break and carry continuously. Inductive rating tests are run with 35% power factor load. • Make Rating - Applies to the current that can be handled by the contact at the time of contact closure. In inductive AC circuits, the momentary inrush current is often 10 times the sealed current, and a relay must be able to handle this inrush current as well as be able to break it in an emergency. The endurance test listed in NEMA Standard ICS 5-1993 Paragraph 8 requires relay contacts to make the make rating for 6,000 operations. • Break Rating - Refers to the current that can be interrupted successfully by the contact. The inductive break rating is always less than the resistive or continuous ratings. When contacts break an inductive circuit, the inductance of the load tends to maintain the current. The result is an arc across the contacts which causes heating and erosion of the contacts. Because of the extra heat generated, the allowable inductive current must be less than the resistive current for equal contact life. The endurance test from NEMA Standard ICS 51993 Paragraph 8 requires relay contacts to interrupt the break rating for 6,000 operations. It also requires relay contacts to interrupt the make rating for 6 operations in an emergency. • Continuous Rating - Continuous rating indicates the load that the contacts can carry continuously without making or breaking the circuit and without exceeding a certain temperature rise.
8
Life-Load Guide The information shown is provided to estimate the service life of a Class 8501 Type X control relay. This information is not to be taken as a guarantee, but rather an approximate life expectancy. The information is based on the following: • • • • •
Operating 40 hours per week Operating 52 weeks per year Inrush and continuous current ratings not exceeded Application in usual service conditions (such as described in NEMA Standard ICS 1-1993 Paragraph 6) Operating at 120 Volts 60 Hertz 15
@
@
300 Operations Per Hour
60 Operations Per Hour
10
5
Endurance Tested For 6 Operations Per NEMA Std. ICS 5-1993 paragraph 8
Contact Ratings on page 5 shows current and VA (voltampere) values in sufficient detail for most applications. A short definition of some of the terms used in the table follow:
Endurance Tested For 6000 Operations Per NEMA Std. ICS 5-1993 paragraph 8
Contact Ratings
When control circuit relays are operated at maximum rated load, the life of the contact is usually less than that of the mechanical life of the device. If the application requires a large number of operations during the life of the contacts, the contacts must be applied at values less than their maximum make and break ratings. NEMA Standard ICS 5-1993 Paragraph 8 recommends that control relays for automaticallyoperated sequencing systems be utilized with loads of less than 25% of the 60 ampere make and 6 ampere break ratings. It does not recommend using a relay at its maximum ampere rating where the number of operations are expected to substantially exceed the 6000 operations required by the endurance test in NEMA Standard ICS 5-1993 Paragraph 8.
Service Life - Years
The magnets on AC devices exhibit an inrush current when first switched on, with the current subsiding to some lesser value, known as the sealed current, after the magnet has moved to its sealed position. DC devices do not have an inrush current when first energized. Relay contacts may also be called upon to carry current continuously for long periods of time. This has resulted in recognizing three important ratings for relay contacts: the make rating, break rating and the continuous current rating. In addition, ratings are further divided into categories which depend upon whether the load is resistive or inductive in nature.
6
60
0 1.5
3
Break Current - Amperes
Figure 1: Service Live vs. Break Current
Page 9
Industrial Control Relays Type X, NEMA Type Relays Product Data
Isolation The class 8501 Type X relay has electrical clearances for up to 600 volts. All contacts are single-throw double-break contacts and are completely isolated from one another. This means that different contacts on the same relay may be connected to control circuits having different voltage values. It also means that if different contacts are connected to different sources, polarity on adjacent connections need not be the same. Electrical spacings per UL 508: •
•
Of not less than 3/8” (9.5mm) through air and 1/2” (12.7mm) over the surface of insulating material are maintained between uninsulated live parts and an uninsulated ground part other than the enclosure, or exposed metal part. Of not less than 1/2” (12.7mm) measured over the shortest distance are maintained between any uninsulated live part and the walls of a metal enclosure, including fittings for conduit or armored cable.
Contact Cartridge Construction Each contact on the Type X relay is a double-break contact. This places, for practical purposes, two single-break contacts in series so that two arcs occur when the contact interrupts the current flow. This division of energy in the arc materially extends the electrical life of the contact when compared to devices employing single-break contacts. The stationary and movable contacts are made of silver-cadmium-oxide. This choice of material is important because of its resistance to welding when closing on the inrush currents normally associated with inductive loads. It also helps to reduce contact erosion which occurs with repeated interruption of inductive loads. The movable contact is split down the center to provide two parallel paths per pole. The fact that both halves of the movable contact are rigidly connected assures that all four contact points will be held closed with nearly equal force. In addition, a conductive bridge straddles the two fingers to provide a cross-over path for even greater contact reliability.
The construction of the cartridges is such that, with the relay mounted in the normal manner, external dust is virtually prevented from entering in to the contact area. A glass-filled thermoplastic is used for the contact carrier in the cartridge. This material was selected because of its ability to withstand high operating temperatures and its low wear rate. The plug-in interface between the relay terminals and the cartridges consist of fine silver which, under pressure, assures a reliable connection. The force of the connection is in excess of one pound.
Contact Cartridge Types and Color Codes Four types of contact cartridges are available for use with the Type X relay: standard contact cartridge which is black, overlapping contact cartridge which is red, logic reed contact cartridge which is grey (only available when ordered as a Class 8501 Type XBR adder deck) and the master contact cartridge which is blue. All are the same size and color coded for visual identification. In addition, the normally open contact symbol ll appears on a green background and the normally closed symbol ll appears on a yellow background. This color coded scheme is consistent throughout the Type X product offering. A.
Standard Contact Cartridge Standard Type X relay contact cartridges are designed so that there is a mechanical differential between normally open and normally closed contacts mounted in the same relay. This means that the normally closed contacts open substantially before the normally open contacts close during the stroke of the relay. This nonoverlapping also takes place during the drop-out of the relay. The standard cartridge, used in most applications, has a black case. It is rated NEMA A600 for AC applications and NEMA P600 for DC applications.
B.
Overlapping Contact Cartridge There are certain cases where an intentional overlap is desired, and an optional contact has been designed for these purposes. The overlapping contact cartridge, which has a red case, has the same NEMA A600 AC contact rating as the standard cartridge and a NEMA P150 DC rating.
Double Break Contact
Contact Bridge
When an overlapping contact cartridge is inserted into the relay as a normally open contact, it will close sooner (early closing contact) in the stroke of the relay than a standard contact. If it is inserted as a normally closed contact, it will open later (late opening contact) in the stroke of the relay than a standard contact. When two such contacts are used in conjunction with one another, they will produce an output signal to the load which is originated through the normally closed contact and maintained through the normally open contact after the relay has picked up. The overlap feature prevents dropout of the load during the transfer from the pickup to the dropout circuit.
Figure 2: Movable Contact
9
Page 10
Industrial Control Relays Type X, NEMA Type Relays Product Data Contact Cartridge Types and Color Codes con’t.
contact. In the case of a normally open logic reed contact, this occurs when the relay coil is energized and the magnet carrier moves down, bringing the magnet close enough to close the contacts. The contact ratings of the logic reed cartridge are specified as maximum wattage, maximum voltage, and maximum current. The maximum voltage times the maximum switched current cannot exceed the maximum wattage.
See below for illustration of a typical application with two limit switches, LS1 and LS2. The machine is such that LS2 is closed to pick up CR1 but, because of the cam limitations, LS2 opens before the dropout of the relay is desired. Assuming that the dropout of the relay can be performed by the opening of LS1, we have a natural application for overlapping contacts. L1 LS1
CR1
CR1
L2
✻
Figure 4: Logic Reed Construction
D. LS2
Master contact cartridges, which have a blue case, feature a 20 ampere AC continuous current rating instead of 10 amperes. Their AC make and break rating remain 7200VA and 720VA respectively. The master contact cartridge can be used in circuits where a master relay is required. Under normal operating conditions, the master contacts are rated to carry the total continuous current of all the loads in the circuit. They do not make or break this current except in an emergency. In an emergency situation, master contacts can interrupt their break rating 6,000 operations and interrupt their make rating for 6 operations. This is in accordance with NEMA Standard ICS 5-1993 Part 2.
✻ ✻ Denotes Overlap Figure 3: Overlapping Contact Application
C.
Logic Reed Contact Cartridge The logic reed contact cartridges are available only in the logic reed adder deck. The contact cartridges are permanently fixed within the center positions of the adder deck and can not be converted or changed in position. The adder decks are available in a combination of normally open or normally closed contacts. The outside positions of the adder deck can be filled with any other type of cartridge available in the Type X contact cartridge line. The adder deck can be added to any 0-8 pole AC or DC relay. A logic reed cartridge consists of a magnetic reed switch mounted in the plug in-cartridge housing in place of the standard silver-cadmium-oxide contacts. It is used for improved contact reliability when switching low-energy circuits. Logic reed cartridges are rated 150 VAC (8W maximum) or 60 milliamperes and 30 VDC and are for use on resistive loads only. These cartridges are identified by a gray housing. The reed switch mounted within the cartridge housing consists of four basic components: glass capsule, gas (atmosphere within the glass capsule), contacts (reeds) and leads. The reeds are hermetically sealed into the glass capsule in cantilever fashion so that the ends align and overlap – but with a small gap. When the reeds are brought into the influence of a magnetic field, they are attracted to one another and make
10
Master Contact Cartridge
CR1
Note: A maximum of 6 master cartridges may be used on a 7 or 8 pole AC device. Do not use any master cartridges on 9-12 pole AC or and DC-operated relays. L1
L2
CR M Master Relay CRM
CRM
CR CR CR
Figure 5: Master Relay Circuit
Note: For additional product data regarding the Class 8501 Type X Relay request Product Data Report M-623.
Page 11
Industrial Control Relays Type X, NEMA Type Relays Dimensions, Shipping Weights
AC Control Relay
DC Control Relay, Utility Auxiliary Relay “A” Dim.
No. of Poles
IN
0–4 6–8 10 – 12 mm
No. of Poles
IN mm
Shipping Weight Lbs.
3.95
100
2.0
0–4
5.17
131
3.1
5.16
131
2.3
6–8
6.37
162
3.4
6.36
162
2.7
10 – 12
7.57
193
3.8
No. of Poles
“A” Dim.
AC Latching Relay
DC Latching Relay “A” Dim.
No. of Poles
IN mm
Shipping Weight Lbs.
IN mm
Shipping Weight Lbs.
2–4
6.54
166
2.8
2–4
7.76
197
3.9
6–8
7.74
197
3.1
6–8
8.96
228
4.2
AC Timing Relay
DC Timing Relay
Type X Relay Mounting Track
NEMA 1 Enclosure Class 9991 Type UE-7
“A” Dim.
No. of Relays
IN mm
Shipping Weight Lbs.
4
9
229
0.75
8
18
457
1.5
12
27
686
2.25
16
36
914
3.0
32
72
1828
6.0
“A” Dim.
Shipping Weight Lbs.
Dimensions Inches MM
11
Page 12
Square D Company P.O. Box 27446 Raleigh, N.C. 27611, USA is a registered trademark of Underwriter’s Labratories. UL is a registered trademark of Underwriter’s Labratories. CSA is a registered trademark of Canadian Standard Association.
8501CT9601
December 1996
Printed in USA