Industrial Control Relays Type X Class 8501, pages 1 to 6

Pages 1 to 6 of 12

The original document is the PDF (355 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D 8501-XO30, Square D 8501-XO40, Schneider 8501-XO30 and Schneider 8501-XO40

Page 1

Industrial Control Relays Type X

Class 8501

CATALOG CONTENTS Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7 Product Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Page 2

Industrial Control Relays Type X - NEMA Type Relays General Information Class 8501 Type X relays combine a rugged, heavy-duty design with modular construction for greater flexibility. They are ideal for those applications where long life, high reliability and ease of maintenance are important. The Type X family offers a complete line of relays and accessories for all control applications.

Plug-In Contact Cartridges

2.

Remove contact cartridge and rotate 180˚.

• •

3.

Plug contact cartridge back in.

4.

Replace T-bar actuator and cover.

• • • • • • • • •

Specified In Major Automotive Plants Modular Design Provides Greater Versatility and Reduction In Stock XUDO Version Ideal for Power Plant Applications Replaceable, Convertible Contacts Extremely Reliable Contacts 600 Volt 10 Ampere Rating (NEMA Type A600) Plug-In Color-Coded Contact Cartridges Mechanical Tie Between Contact Cartridges 1 and 3 Minute Timing Relays 8 Pole Latching Relays DC Operated Relays

Contact Conversion Without Removing Terminal Screws or Wires 1. Remove relay cover and captive T-bar actuator.

Note: For additional information regarding contact cartridges see Page 9.

Normally Closed (Yellow)

Normally Open (Green)

Modular Construction A basic relay has room for up to 4 convertible contact cartridges. It can be expanded to 6 or 8 poles by installing an adder deck. A 10 or 12 pole relay can be built by adding a second deck. The same adder deck is used for both the middle and upper decks. Latching and timing relays are made by adding a latch or timer attachment to a basic relay. This reduces the number of components required in inventory.

Ring Or Spade Lugs – Form Y414 For relays with terminals that will accept ring or spade lugs, add Form Y414 to the Class and Type number of the device being ordered. Form Y414 is available on all AC relays, DC relays and attachments at no additional charge. Ring or spade lugs must have an outside diameter of .31 inch or less and an inside diameter large enough to accommodate a #6 screw. Lugs should accept #12 – #14 gauge (AWG) stranded copper wire. UL Listing is maintained only when AMP Plasti-Grip® #32958 insulated-barrel ring-tongue lugs are used.

Normally Closed Contacts

Common Mechanical Tie Non-Overlapping Contacts The Type X relay is designed to provide a significant degree of non-overlap between N.O. and N.C. contacts during normal operation. In addition, a common mechanical tie between all contact cartridges is provided. Therefore, the Type X relay is suitable for use in self-checking circuits for press control and automatic transfer line applications. Since the T-bar actuator is held captive in the cover plate, there is no chance of losing or forgetting to replace the mechanical tie when converting a contact or adding another deck.

2

Contact conversion is so simple that it is generally more economical to purchase relays with all contacts N.O. and convert contacts to N.C. as required. If it is preferred that relays be factory assembled with a combination of N.O. and N.C. contacts, change the type number so that following the “XO”, the first number indicates the number of normally open contacts (N.O.) and the second number indicates the number of normally closed contacts (N.C.). As indicated on contact arrangement tables found on Page 6. There is a price adder for the factory installation of normally closed (N.C.) contacts. How to Order: To Order Specify: • Class Number • Type Number • Voltage Code • Form(s)

Catalog Number Class

Type

Voltage Code

Form(s)

8501

XO40

V02

Y414

Page 3

Industrial Control Relays Type X - NEMA Type Relays/AC General Information, Order Information

AC Control Relays

AC Timing Relays

In addition to all of the features listed on the previous page, the Type XO relay also provides:

•

• •

• •

•

• •

Straight–through wiring Plug-in contact cartridges for easy contact conversion and replacement Contact conversion without removing terminal screws or wires Self-lifting pressure wire connectors that will accept up to two #12-18 (AWG) gauge stranded copper wires Replaceable coil Normally Open Convertible Instantaneous Contacts

Control Relay ∆

0 2 3 4 6 8 10 12

XO00 ✻ XO20 ✻ XO30 ✻ XO40 ✻ XO60 ✻ XO80 ✻ XO1000 ✻ XO1200 ✻

• • • Type XO40

Easily convertible On Delay or Off Delay Two adjustable timing ranges Repeat accuracy well above ± 10% Convertible 1 N.O. and 1 N.C. timed contacts Large knob for easy adjustment of time delay Off Delay mode times out even after loss of power File CCN

Type

File CCN

E78403 NKCR

File Class

LR60905 60905 321103 03

Type XO40XTE1

E78403 NKCR

File Class

LR 60905 3211 03

Timing Mode

Normally Open Convertible Instantaneous Contacts

N.O.

N.C.

Type

Type

On Delay

0 2 4

1 1 1

1 1 1

XO00XTE1 ✻ XO20XTE1 ✻ XO40XTE1 ✻

XO00XTE2 ✻ XO20XTE2 ✻ XO40XTE2 ✻

Off Delay

0 2 4

1 1 1

1 1 1

XO00XTD1 ✻ XO20XTD1 ✻ XO40XTD1 ✻

XO00XTD2 ✻ XO20XTD2 ✻ XO40XTD2 ✻

Timed Convertible Contacts

Timing Relay 0.2-60 sec.

5-180 sec.

∆ A maximum of 8 N.C. contacts is allowed on 9-12 pole relays.

AC Latching Relays

AC Master Relays • •

• •

• • •

20 Ampere Contact Rating due to use of Master Contact Cartridges Provisions for Standard Cartridges to be used in contact cavities not occupied by Master Cartridges in 2-8 pole AC relay Straight–through wiring Plug-in contact cartridges for easy contact conversion and replacement Type XMO40 Contact conversion without removing terminal screws or wires Self-lifting pressure wire connectors that will accept up to two #12-18 (AWG) gauge stranded copper wires Replaceable coil Number of N.O. 20 Ampere Convertible Contacts

Open Type †

2 4 6

XMO20 ✻ XMO40 ✻ XMO60 ✻

File CCN

E78403 NKCR

File Class

LR 60905 3211 03

Type

•

•

•

•

Mechanical Latch holds all contacts switched even after removal of power from replaceable Latching Coil. Provides sequence memory in the event of power loss. Ideal for press control, process control and punch presses. Replaceable Unlatch Coil to switch contacts back to original state. Continuously rated Unlatch Coil (no coil clearing contacts required). Normally Open Convertible Instantaneous Contacts

Latching Relay

2 3 4 6 8

XO20XL ✻ XO30XL ✻ XO40XL ✻ XO60XL ✻ XO80XL ✻

Type XO40XL

File CCN

E78403 NKCR

File Class

LR 60905 3211 03

Type

✻ Voltage Code must be specified to order this product. Refer to standard voltage codes listed below and insert as shown in How To Order.

† Attachments not permitted on this relay.

Voltage Codes:

How to Order: To Order Specify: • Class Number • Type Number • Voltage Code

Catalog Number Class

Type

Voltage Code

8501

XO40

V02

AC Voltages, Hz.

Code

12 – 60 24 – 60 24 – 50 48 – 60 48 – 50 120 – 60/110 – 50 208 – 60 240 – 60/220 – 50 277 – 60 480 – 60/440 – 50 600 – 60/550 – 50

V11 V01 V12 V18 V16 V02 V08 V03 V04 V06 V07

3

Page 4

Industrial Control Relays Type X - NEMA Type Relays/DC General Information, Order Information DC Control Relays

DC Latching Relays

•

•

•

• • •

•

Replaceable, highly reliable pure DC Power Plant: no economizing resistors, overlapping contacts or dual-wound coil Utilizes the same Type XB Adder Decks and attachments as the AC Version Offers all the features of the AC Relay Available in up to 8 Poles Type XDO40 All contact poles are usable since no overlapping contacts are needed Self-lifting pressure wire connectors that will accept up to two #12-18 (AWG) gauge stranded copper wires Normally Open Convertible Instantaneous Contacts

Control Relay Type

File CCN

E78403 NKCR

0 2 4 6 8

XDO00 ✻ XDO20 ✻ XDO40 ✻ XDO60 ✻ XDO80 ✻

File Class

LR 60905 3211 03

• • • • •

Easily convertible On Delay or Off Delay Two adjustable timing ranges Repeat accuracy well above ± 10% Convertible 1 N.O. and 1 N.C. timed contacts Large knob for easy adjustment of time delay Off Delay mode times out even after loss of power File CCN

•

Normally Open Convertible Instantaneous Contacts

Latching Relay ∆

2 4 6 8

XDO20XDL ✻ XDO40XDL ✻ XDO60XDL ✻ XDO80XDL ✻

Type XDO40XDL

Type

File CCN

E78403 NKCR

File Class

LR 60905 3211 03

∆ Caution: Unlatch coil is rated for intermittent duty and should be connected through a N.O. contact of the relay if the input signal is maintained. Order one more N.O. contact than the application requires to use as a coil clearing contact. If a coil clearing contct is required in series with the latch coil, consult your local Square D field sales office.

Ideal for utility plant applications where reliable performance and a pure DC power plant are required. In addition to the Type XDO relay features, the Type XUDO provides: • •

Type XDO40XTE2

E78403 NKCR

Normally Open Convertible Instantaneous Contacts

N.O.

N.C.

On Delay

0 2 4

1 1 1

Off Delay

0 2 4

1 1 1

Timing Mode

•

DC Utility Relays

DC Timing Relays •

•

Mechanical Latch holds all contacts switched even after removal of power from replaceable Latching Coil Provides sequence memory in the event of power loss Ideal for sequencing applications such as press control, process control and punch presses Replaceable Unlatch coil to switch contacts back to original state

Timed Convertible Contacts

File Class

LR 60905 3211 03

•

Up to 12 poles N.O. or N.C. Nominal 125VDC coil, capable of handling 140VDC continuously and picking up at 105VDC after having been operated at 140VDC Type XDO40 continuously. Other voltages with comparable operating characteristics are available Enclosed device capable of operating in 145°F ambient Number of Convertible Contacts

Timing Relay

Open Type

5-180 sec.

N.O.

N.C.

Type

Type

Type

4 0

0 4

XUDO40 ✻ XUDO04 ✻

1 1 1

XDO00XTE1 ✻ XDO20XTE1 ✻ XDO40XTE1 ✻

XDO00XTE2 ✻ XDO20XTE2 ✻ XDO40XTE2 ✻

8 0

0 8

XUDO80 ✻ XUDO08 ✻

1 1 1

XDO00XTD1 ✻ XDO20XTD1 ✻ XDO40XTD1 ✻

XDO00XTD2 ✻ XDO20XTD2 ✻ XDO40XTD2 ✻

12 0

0 12

XUDO1200 ✻ XUDO0012 ✻

0.2-60 sec.

File CCN

E78403 NKCR

File Class

LR 60905 3211 03

✻ Voltage code must be specified to order this product. Refer to standard voltage code listed below and insert as shown in How To Order. Voltage Codes for 8501 XUDO Relays ONLY:

4

Voltage Codes for 8501 XDO Relays:

DC Voltages

Code

DC Voltages

Code

6 12 24 48 125 250

V50 V51 V53 V56 V63 V67

6 12 24 32 48 72 90 115/125 230/250

V50 V51 V53 V54 V56 V58 V59 V62 V66

For Replacement Coils . . . . . . . . . . . . . . . . . . . . . . . . . Page 6 How to Order: To Order Specify: • Class Number • Type Number • Voltage Code

Catalog Number Class

Type

Voltage Code

8501

XDO40

V53

Page 5

Industrial Control Relays Type X - NEMA Type Relays Accessories, Order Information

Class 8501 Type Mechanical Latch Attachment – Mounts on any 2 through 8 pole relay (except XMO master relay). The Type XL and XDL latch attachments are identical in size and mounting provisions. The Type XL AC latch attachment has a continuous-duty-rated coil which is replaceable. The Type XDL DC latch attachment has an intermittent–rated coil (replaceable) and should be connected through a N.O. contact of the basic relay if the input signal is maintained to the unlatch coil. AC Latch Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . DC Latch Attachment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

File E78403 CCN NKCR2

XL * XDL *

Pneumatic Timer Attachment – Mounts on any 0 through 4 pole AC or DC relay (except XMO master relay). It provides 1 N.O. and 1 N.C. convertible timed contacts, which are the same Type XC-1 cartridges used on the basic relay. Two timing ranges are available, and conversion from On Delay to Off Delay or vice versa is easy. Off Delay 0.2-60 seconds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-180 seconds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . On Delay 0.2-60 seconds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-180 seconds. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

XTD1 XTD2

Timer Lockout Cover – Fits over the time delay adjustment knob of any Type XT timing attachment. The Lockout Cover is designed to protect the time setting against accidental adjustment. It mounts directly to the timing attachment with two included screws. . . . . . .

XJ1

Adder Decks – Adder decks are used to expand the number of poles on a relay. The basic 4 pole relay can be easily converted to an 8 pole or 12 pole relay by installing one or two adder decks. The Class 8501 Type XB20 comes with 2 convertible contact cartridges and will accept 2 additional convertible contact cartridges. The Class 8501 Type XB40 comes with 4 convertible contact cartridges. The same Type XB adder deck is used for both the middle and upper decks of the AC or DC relay. With 2 N.O. contact cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . With 4 N.O. contact cartridges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Logic Reed Adder Deck – Used for switching low energy circuits. The Logic Reed Adder Deck is supplied with either one or two logic reed cartridges fixed into the center positions of an adder deck. Contact cartridges are neither convertible nor replaceable. Standard cartridges can be inserted in unused cavities of the Logic Reed Adder Deck. One or two Logic Reed Adder Decks may be added to the basic 4 pole relay. See Application Data on Page 5 for electrical ratings.

Number of N.O. Logic Reed Contact Cartridges 2 1 1 0 0

Number of N.C. Logic Reed Contact Cartridges 0 1 0 1 2

File LR 60905 Class 3211 02

File E78403 CCN NKCR2 File LR 60905 Class 3211 02

XTE1 XTE2

File E78403 CCN NKCR2

XB20 XB40

File LR 60905 Class 3211 02

File E78403 CCN NKCR2

XBR20 XBR11 XBR10 XBR01 XBR02

File LR 60905 Class 3211 02

Contact Cartridges – The Type X relay offers 4 Types of contact cartridges. All are color–coded for visual identification of each Type. Note: For additional information regarding contact cartridge see Pages 9-10 Standard Cartridge – The standard cartridge, used for most applications, has a black case. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

XC1

Overlapping Cartridge – Same NEMA Type A600 AC rating as standard cartridge and a NEMA Type P150 DC rating. When it is used in the N.O. mode it will close early and when used in the N.C. mode it will open late. If two or more are used together, the N.O. contacts will close before the N.C. contacts open as the relay picks up. Overlap also occurs during dropout. Overlapping cartridge has a red case.

XC2

File E78403 CCN NKCR2

May be ordered factory installed: Substitute 1 N.O. and 1 N.C. overlapping cartridges for 2 standard cartridges.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Substitute 2 N.O. and 2 N.C. overlapping cartridges for 4 standard cartridges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Form Y1591 Y1592

File LR 60905 Class 3211 02

Master Cartridge – Features the same contact ratings as the Type XC1 standard cartridge except it has a 20 Ampere continuous current rating instead of 10 Amperes. It can be used in circuits where a master relay is required. Master cartridge has a blue case. Maximum of 6 master cartridges may be used on any 7 and 8 pole AC relays. Do not use any master cartridges on 9-12 pole AC or any DC-operated devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

XC4

Logic Reed Cartridge – See Logic Reed Adder Deck above . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

–

Mounting Track – The mounting track has pre-punched mounting holes to simplify mounting the track on the control panel. The relay mounting screws are factory installed on the track so that the relays can be hung prior to tightening the screws. 9'' long for 4 relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18'' long for 8 relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27'' long for 12 relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36'' long for 16 relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72'' long for 32 relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

XM4 XM8 XM12 XM16 XM32

Manual Test Tool – Provides a means of manually switching the contacts of a basic relay or timing relay and holding all contacts in their switched state until the tool is removed. This simplifies the checking of control circuits without power on the coil or contacts. . . . . . . . .

XA1

XS1

File LR60905 Class 321102

NEMA Type 1 Enclosure – Formed from sheet steel to provide strength and rigidity. Two conduit knockouts are located in both the top and bottom of the enclosure. The enclosure is furnished with self tapping screws for mounting the relay inside the enclosure. Accommodates a single 4 or 8 pole AC or DC relay, 12 pole AC relay, 4 pole AC latching relay, and 4 pole AC timing relay. NOTE: The 4 pole DC latching relay, 4 pole DC timing relay, 8 pole AC and DC latching relays and 12 pole Utility Auxiliary Relay will not fit.

Class 9991 Type UE7

File E78403 CCN NKCR

*Mechanical Latch Attachment Voltage Codes: AC Voltages

Code

24 – 60 24 – 50 120-60/110-50 208 – 60 240 – 60/220 – 50 277 – 60 480 – 60/440 – 50 600 – 60/550 – 50

V01 V12 V02 V08 V03 V04 V06 V07

♦ Specify voltage on order.

File E78403 CCN NKCR2

Transient Suppressor – Consists of an R-C circuit designed to suppress coil generated transients to approximately 200 percent of peak voltage. It is particularly useful when switching the Type X relay near solid state equipment. It is designed for use on coils up to 120VAC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DC Voltage 6 12 18 24 48 72 90 115/125 230/250

Code V50 V51 ♦ V99 V53 V56 V58 V59 V62 V66

For Replacement Coils . . . . . . . . . . . . . . . . . . . . . . . . Page 6 How to Order: To Order Specify: • Class Number • Type Number • Voltage Code for mechanical latch attachment • Form for factory installed overlapping contacts

Catalog Number Class

Type

8501

XTE1

5

Page 6

Industrial Control Relays Type X, NEMA Type Relays Application Data Voltage Range: AC operation, +10/-15% DC operation, +10/-20% In the case of dual rated DC coils, the range is +10% of the larger number and -20% of smaller number.

Average Operating Times In Milliseconds Device

Pick-Up

Drop-Out

AC Relay

15

16

AC Latching Relay

15

13

DC Relay

37

21

DC Latching Relay

37

45

Operating Temperature Range: -40°C to +71°C (-40°F to +160°F)

Contact Ratings AC Ratings Type of Cartridge

Standard Overlapping

DC Ratings Resistive 75% Power Factor

Inductive 35% Power Factor Volts

Make NEMA Rating

120 240 480 600

Break

Amperes

VA

Amperes

VA

60 30 15 12

7200 7200 7200 7200

6 3 1.5 1.2

720 720 720 720

A600

Make, Break Continuous and Continuous Amperes Amperes 10 10 10 10

Inductive Volts NEMA Rating

Max. Make and Break Amperes (138VA Max. for 300 V or Less)

Continuous Amperes

Make and Break Amperes

Continuous Amperes

P600

1.1 0.55 0.20

5 5 5

4 0.8 -

5 5 -

125 250 301 - 600

10 10 10 10

Resistive

125 P150 1.1 5 4 125 1.1 5 4 Master ✻ – A600 250 P600 0.55 5 0.8 301 - 600 0.20 5 Logic Reed – – 150VAC, 150MA, 8W Maximum – – 30VDC, 60MA ✻ Maximum of six 8501 Type XC – 4 Master Cartridges may be used on any 7 and 8 pole AC device. Do not use any Master Cartridges on 9-12 pole AC or any DC-operated relays.

5 5 5 -

Same as standard cartridge above except substitute 20 Ampere for the continuous Ampere rating

Contact Arrangement The following tables list all pole arrangements and the location of the N.O. and N.C. poles. Relays purchased from the factory will correspond to these tables. For example: an XO12 will have one N.O. pole in position 1; positions 2 and 3 will have N.C. poles; position 4 will be a space.

Note: Note: For additional information regarding contact cartridges see Pages 9 and 10. 2, 3, and 4 Pole Relay – All contacts convertible No. of Poles 2

3

4

Pole Number † Type XO20 XO11 XO02 XO30 XO21 XO12 XO03 XO40 XO31 XO22 XO13 XO04

1

2

3

4

S S S O O O 1 O O O O 1

O O 1 O 1 1 1 O 1 1 1 1

O S 1 S 1 S O S O S 1 S 1 S O O O O 1 O 1 1 1 1

10 and 12 Pole Relay – All contacts convertible

6 and 8 Pole Relay – All contacts convertible No. of Poles

Type XO60 XO51 XO42

6

XO33 XO24 XO15 XO06

Pole Number † 5 6 7 8 1 2 3 4 S O O S O O O O S O O S O 1 O O S O O S O 1 1 O S 1 1 S O 1 O O S 1 1 S O 1 1 O S 1 1 S O 1 1 1 S 1 1 S 1 1 1 1

No. of Poles

Type XO80 XO71 XO62 XO53

8

XO44 XO35 XO26 XO17 XO08

Pole Number † 5 6 7 8 1 2 3 4 O O O O O O O O O 1 O O O O O O O 1 1 O O O O O O 1 O O O 1 1 O O 1 1 O O 1 1 O O 1 1 1 O 1 1 O O 1 1 O 1 1 1 1 O 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

No. of Poles

10

Pole Number † No. 9 10 11 12 of 5 6 7 8 Poles 1 2 3 4 S O O S XO1000 O O O O O O O O S O O S XO0901 O 1 O O O O O O S O O S XO0802 O 1 1 O O O O O S O O S XO0703 O 1 1 O O 1 O O S O O S XO0604 O 1 1 O 12 O 1 1 O S O O S XO0505 O 1 1 1 O 1 1 O S 1 1 S XO0406 O 1 1 O O 1 1 O S 1 1 S XO0307 O 1 1 1 O 1 1 O S 1 1 S XO0208 O 1 1 O 1 1 1 1 8 N.C. Poles Maximum Type

Pole Number † 9 10 11 12 5 6 7 8 1 2 3 4 O O O O XO1200 O O O O O O O O O 1 O O XO1101 O O O O O O O O O 1 1 O XO1002 O O O O O O O O O 1 1 O XO0903 O 1 O O O O O O O 1 1 O XO0804 O 1 1 O O O O O O 1 1 O XO0705 O 1 1 O O 1 O O O 1 1 O XO0606 O 1 1 O O 1 1 O O 1 1 O XO0507 O 1 1 O O 1 1 1 O 1 1 O XO0408 O 1 1 O 1 1 1 1 8 N.C. Poles Maximum Type

XTD & XTE Timer Attachments –All Contacts Convertible

✻ For latch relay use same diagram as above except for the addition of an unlatch coil (8 pole maximum).

6

No. of Timed Contacts

Type

2

XTD XTE

† O – Normally Open Contact

Pole Number † 13

14

O

1

1 – Normally Closed Contact

S – Space for Future Contact