The text of a manual · part 1 of 4

POWERLINK AS Control Module AS42C and AS42C-T, pages 1 to 8

Pages 1 to 8 of 28

The original document is the PDF (327 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D AS42C and Schneider AS42C

Page 1

Bulletin 1210IM9502R12/97 December 1997

SECTION 1, GENERAL

SECTION 1 - GENERAL This bulletin contains important information about the POWERLINK AS Control Module AS42C and AS42C-T. Please retain this bulletin for future reference.

BULLETIN FORMAT This bulletin is arranged in the following format: •

Section 1 - General - gives important information to be read before using the control module.

•

Section 2 - Installation - explains how to properly install and remove the control module.

•

Section 3 - Programming Basics, explains the POWERLINK AS system and gives stepby-step directions for setting up control module communication parameters.

•

Section 4 - Troubleshooting, explains what to do for common problems with control module operation.

•

Appendix A, System Components - describes the POWERLINK AS system components.

•

Appendix B, Configuration Sheets, provides system configuration worksheets to use when programming the control module.

•

Appendix C - Operation of Inputs in a POWERLINK AS System - provides a detailed description of input operation.

•

Appendix D - Priorities - explains how the POWERLINK system avoids conflicts by assigning priorities.

•

Appendix E - Sunrise/Sunset Data Tables - provides data for entering latitude information through POWERLINK software.

TECHNICAL SUPPORT For technical assistance, please contact your local Square D distributor or field office, or: •

•

Fax your request for support to (615) 2873404, 24 hours a day, seven days a week. Be sure to include your name and company, address, phone number, type(s) of POWERLINK product(s), and a detailed description of your problem. The support center will normally respond within two business hours. Business hours are 7:30 A .M. to 4:30 P.M., Central Time, Monday through Friday - except holidays. Phone (615) 287-3400, 7:30 AM. to 4:30 P .M., Central Time, Monday through Friday - except holidays - for assistance from a technical support specialist. If a support specialist is not available, leave a voice mail message, or, in an urgent situation, speak to an operator who will process your request. The support center will normally respond within two business hours.

Be sure to have the product serial number ready. The serial number is located on the back of the control module.

BEFORE BEGINNING This bulletin assumes that: •

User understands the system configuration. (See Appendix B for system configuration worksheets.)

If you have questions concerning system installation or configuration, contact Square D.

NOTE: For a complete description of the POWERLINK AS system, see Appendix A.

1997 Square D All Rights Reserved

1

Page 2

Bulletin 1210IM9502R12/97 December 1997

SECTION 2, P ROGRAMMING BASICS

SECTION 2, INSTALLATION INSTALLING CONTROL MODULE

A

B

D

1. Open panelboard cover. Note: The control module is installed with panelboard deadfront in place. Power to the panelboard does not need to be turned off to install or program the control module. DO NOT REMOVE PANELBOARD DEADFRONT.

–

+

–

+

STATUS

–

+

CPU

–

+

CLK

–

+

–

+

–

+

SETUP

–

+

RX

ADDRESS

–

+

TX

K BAUD

–

+

COMMUNICATIONS

MODIFY

SELECT

–

+

–

+

+ -

AS

2. Install control module onto power interface module (see figure 1). Position control module (A) with reset button (B) to the right. Align the two mounting holes on back of control module with power interface module mounting tabs (C). Push control module at points D until mounting holes snap onto power interface module mounting tabs. Do NOT apply force to display screen on module. Note: This also connects control module and power interface module connectors. 3. Set up control module’s communications parameters as instructed in the user’s guide.

C Figure 1

4. Close panelboard door. Note: While in SETUP mode, values may be changed as many times as needed; however, if no key is pressed for two and a half minutes, the module automatically exits SETUP mode.

A REMOVING CONTROL MODULE Grasp control module (figure 2) by edges (A). Lift up until module comes free. Note: If control module is removed, the POWERLINK AS circuit breakers will go to their default positions as specified by the “Default Controller Action” setting (either ALL ON, ALL OFF, NO CHANGES, or RUN INPUTS). This is set using POWERLINK software. Power does not need to be turned off to remove unit.

–

+

–

+

–

+

STATUS

SETUP

–

+

–

+

CPU

RX

ADDRESS

–

+

–

+

CLK

TX

K BAUD

–

+

–

+

–

+

COMMUNICATIONS

MODIFY

SELECT

AS

A Figure 2

2

1997 Square D All Rights Reserved

–

+

–

+

+ -

Page 3

Bulletin 1210IM9502R12/97 December 1997

SECTION 3 - PROGRAMMING BASICS

SECTION 3 - PROGRAMMING BASICS CONTROL MODULE DESCRIPTION The POWERLINK AS Control Module (figures 3 and 4) is used to control operation of a POWERLINK AS system. It uses remotely operated circuit breakers to control up to 42 independent branch circuits. Control signals can originate externally from dry contact closures via external control devices or from commands received from the communications network, or internally from data entered into the control module. The control module displays status and communication parameters using indicators (D, F, G) and an LED display (B). System configuration is done using selection keys (A) on both sides of the control module. In addition to the network connection, a temporary link is available using the RS-232 (serial) communications port (E). (If using the RS232 port, serial communications cable #AS42CMSC is required.) The control module can be reset manually by depressing the reset button (C) with a paper clip or similar tool. This will restart operation without affecting system configuration.

–

+

–

+

–

+

STATUS

SETUP

–

+

–

+

CPU

RX

ADDRESS

–

+

–

+

CLK

TX

K BAUD

–

+

–

+

–

+

MODIFY

+

–

+

+ -

Figure 3

A C

B –

+

–

+

STATUS

–

+

CPU

–

+

CLK

–

+

–

+

–

+

SETUP

–

+

RX

ADDRESS

–

+

TX

K BAUD

–

+

COMMUNICATIONS

MODIFY

SELECT

–

+

–

+

+ -

AS

G

POWERLINK offers two software packages for programming control modules:

SELECT

–

AS

PROGRAMMING Control module programming is done locally using the RS-232 communications port or over a network via an IBM PC-compatible computer running POWERLINK software (refer to user’s guides).

COMMUNICATIONS

F

E

D

A - SELECTION KEYS B - LED DISPLAY C - RESET BUTTON D - DISPLAY MODE INDICATORS E - RS-232 COMMUNICATIONS PORT F - COMMUNICATIONS ACTIVITY INDICATORS G - STATUS INDICATORS

Figure 4

(1) POWERLINK PLK101 Software (Class 3080, Type PLK101) (2) POWERLINK Circuit Manager Software (Class 3080, Type CMS-1000)

1997 Square D All Rights Reserved

3

Page 4

Bulletin 1210IM9502R12/97 December 1997

SECTION 3 - P ROGRAMMING BASICS

TX: Flashes briefly any time the control module transmits communication information either over the network or using the RS-232 port.

FRONT PANEL DESCRIPTION The control module (figure 5) front panel (A ) has two main headings: status and communications.

The SETUP, SELECT, and MODIFY selecton keys are used to set or change communications values. (See the “Setting Communications” section on the following page for instructions on using these keys.)

The STATUS area monitors the operating status of the module by using the following indicators: Status Indicators (E): CPU: Flashes slowly when the control module is in normal operation CLK: Lights to indicate a “time of day” control module (AS42C-T) The COMMUNICATIONS area monitors communications activity and allows you to set the module’s parameter values. Functions are as follows:

SELECTION KEYS The selection keys are used for viewing and setting communications parameters. Five selection keys are used in operating the control module. They are as follows: The three communications setup keys – SETUP, SELECT, and MODIFY (marked by arrows)

The display mode indicators (C) correspond to the “Address” and “K Baud” parameters. An indicator is lit when its parameter value is displayed.

The system security key (G) (top left key), described in the “System Security” section on the following page

The LED display (B) shows the current address or baud rate, as indicated by the display mode indicators. Note: Pressing the SELECT (lower right) key toggles the indicator light between “Address” and “K Baud,”allowing you to see the current value for each parameter in the LED display. Communications Activity Indicators (D): RX: Flashes briefly anytime the control module receives communication information either over the network or using the RS-232 port.

Note: The keys stay in a neutral position until actuated. Except when pressing the MODIFY selection key (described in the following section), you may press either the minus (-) or plus (+) side of the keys when setting communications values.

A

G

F

The “version” key (F) (left side, third key down). Upon pressing this key, the LED display blinks three values: the control module version (first), the power interface module version (second), and the expander (if present) version (third).

–

+

–

+

STATUS

–

+

CPU

–

+

CLK

–

+

–

+

B

–

+

SETUP

–

+

RX

ADDRESS

–

+

TX

K BAUD

–

+

–

+

–

+

COMMUNICATIONS

MODIFY

SELECT

AS E

C

D Figure 5

4

1997 Square D All Rights Reserved

+ -

Page 5

Bulletin 1210IM9502R12/97 December 1997

SECTION 3 - PROGRAMMING BASICS

POWER-UP/INITIALIZATION

SETTING COMMUNICATIONS

Upon power-up or reset, the control module undergoes the following process:

Set or change the control module’s network address and baud rate by following these steps:

• All LEDs turn on momentarily.

Note: If the system security feature is enabled, you must press the unlabeled security key immediately before pressing the “Setup” key in step 1.

• Checksum test is performed. The LED display briefly shows “C – P” to indicate that checksum has passed. • Initialization sequence begins. Decimal points in the LED display blink as the digits begin a countdown from 10 to 1. • Module begins normal mode of operation, as follows: – Address indicator is lit. – LED display shows the current Address. – CPU indicator flashes slowly. – CLK indicator (if a “time of day” module) is lit. – Communication activity indicators may blink periodically.

SYSTEM SECURITY An optional security feature can be implemented in the control module, using POWERLINK software. This feature, when enabled, requires a user to press an unlabeled key before entering the SETUP mode. Enabling the Security Feature To enable the security feature, refer to one of the POWERLINK Software User’s Guides: In both the PLK101 Software and Circuit Manager Software user’s guides, see “Defining Access Codes” in Chapter 5. Using the software, enter an access code (other than 0000) in the “Master” access code field; then send the information to the control module. To disable the security feature, re-enter “0000” in the “Master” access code field. Security Key

1. Press the SETUP key to enter the SETUP mode. The display mode indicator for the value shown in the LED display (Address or K Baud) blinks. 2. Press the SELECT key to display the value to be changed. (If the value to be changed is already displayed, go to step 3.) Pressing the SELECT key toggles between the current Address and K Baud values. 3. Press the MODIFY key to change the value displayed. Pressing the plus (+) position increases the numerical value, and pressing the minus (-) position decreases the numerical value. Press the key once for a single increment; hold the key down for fast movement through the available increments. To change the other value (Address or K Baud), press the SELECT key, and then follow instructions in the above paragraph again. 4. When you are satisfied that both communication values are correct, press the SETUP key to save the values and exit the SETUP mode. Upon exiting the SETUP mode, the LED display momentarily shows the selected parameter values. Note: While in SETUP mode, values may be changed as many times as needed; however, if no key is pressed for two and a half minutes, the module automatically exits SETUP mode.

GETTING STARTED

The security key is the top left key on the control module, as shown in the diagram on the previous page. If system security is enabled, you must press this key immediately (within 2.5 seconds) before pressing the SETUP key in the “Setting Communications” section. Otherwise, pressing the SETUP key results in a momentary display of “- - -,” indicating that access has been denied.

When programming the control module using POWERLINK software, use the system configuration sheets from Appendix B to lay out the system and define system operation. Keep these sheets with the user’s guide so that future changes can be noted.

1997 Square D All Rights Reserved

5

Page 6

Bulletin 1210IM9502R12/97 December 1997

SECTION 4 - TROUBLESHOOTING

SECTION 4 - TROUBLESHOOTING If solutions below do not correct the problem, refer to Section 1 - Technical Support for assistance.

CONDITION Control module LED and status indicators are not functional.

POSSIBLE CAUSES 1. Panelboard is not energized.

1. Energize panelboard.

2. Control module is not receiving power from the power interface module.

2. Verify that control module is properly seated.

3. Power interface module is not operating.

3. Verify that power interface module is properly installed.

Control module displays “C –E” on power-up (checksum error).

1. Control module firmware incompatibility.

1. Upgrade required. Contact Technical Support at (615) 287-3400.

Circuit breaker does not respond to input.

1. Circuit breaker is tripped.

1. Turn circuit breaker ON.

2. Circuit breaker handle is OFF.

2. Turn circuit breaker handle to ON.

3. Circuit breaker manual mode is engaged.

3. Disengage manual mode on circuit breaker.

4. Input not defined properly or is inhibited.

4. Define input type.

5. Input is not programmed to operate circuit breaker.

5. Create program to operate circuit breaker from input.

6. Circuit breaker is overridden.

6. Release override for circuit breaker, or, if circuit breaker is part of a zone, release override for that zone.

Circuit breaker remotely switching ON or OFF at random.

1. Improper or multiple program commands assigned to same circuit breaker.

1. Check input-based, time-based, and special date programs. Also check sunrise/ sunset data programs.

Circuit breaker not responding to network command.

1. Network is not operating.

1. Check input connections and personal computer software diagnostic screens.

2. Wrong address.

2. Verify correct address is set.

3. Wrong baud rate.

3. Verify baud rate matches network baud rate.

1. Wrong day, date, or time (AS42C-T Only).

1. Enter correct day, date, and time.

2. Special holiday period (AS42C-T Only).

2. If current date is within a special date period, verify that a program is entered for that special date period.

3. Improper days of week selected(AS42C-T Only).

3. A day of the week must be selected for a time-based program.

4. Circuit breaker is overridden OFF by sunrise/sunset program (AS42C-T Only).

4. Check to see if circuit breaker is assigned to Sunrise/Sunset Circuits.

5. Circuit breaker is tripped.

5. Turn circuit breaker ON.

6. Circuit breaker handle is OFF.

6. Turn circuit breaker handle to ON.

7. Circuit breaker manual mode is engaged.

7. Disengage manual mode on circuit breaker.

8. Circuit breaker is overridden.

8. Release override for circuit breaker, or, if circuit breaker is part of a zone, release override for that zone.

Circuit breakers do not switch at desired times.

Table 1

6

SOLUTION

1997 Square D All Rights Reserved

Page 7

Bulletin 1210IM9502R12/97 December 1997

APPENDIX A - SYSTEM COMPONENTS

APPENDIX A, SYSTEM COMPONENTS POWERLINK AS SYSTEM

F

The POWERLINK AS system (figure 6) consists of two control buses (A), a panelboard (B), remotely operated circuit breakers (C), a power interface module (D), and a control module (E). If external control wiring is needed, a Class 2 wire barrier kit (F) is required. An alignment fixture (G) is provided with the control bus package. The Input Expansion Cabinet is an optional, separate item that provides up to 48 additional inputs and 42 outputs. Refer to the POWERLINK Input Expansion Cabinet instruction bulletin. The cabinet is separately mounted within 50 feet of the panelboard.

E D RESET

C

AS

B A G EH1017A.0

Figure 6

CONTROL BUS The control buses (figure 7) provide a control power data highway between POWERLINK AS remotely operated circuit breakers and the POWERLINK AS power interface module. Installed control buses will not interfere with the installation of standard circuit breakers into the panelboard.

NOTE: Always install identical control buses on the left and right sides of the panelboard. Control buses are shipped as matching pairs.

PL1003A.0

Figure 7

REMOTELY OPERATED CIRCUIT BREAKERS POWERLINK AS remotely operated Circuit Breakers (figure 8) provide the same overcurrent protection as standard circuit breakers, and have an integral operator which can remotely switch the circuit breaker ON and OFF. The circuit breaker works with POWERLINK AS control and power interface modules and control buses to provide a remote power switching system in a panelboard. Each remotely operated circuit breaker has a switching mode button (H) to choose between automatic and manual modes. In automatic mode, the circuit breaker responds to signals from the power interface module. In manual mode, the circuit breaker will not respond to commands issued from the power interface module and assumes the status indicated by its handle. 1997 Square D All Rights Reserved

PL1056A.0

Figure 8

7

Page 8

Bulletin 1210IM9502R12/97 December 1997

APPENDIX A - SYSTEM COMPONENTS

POWER INTERFACE MODULE The POWERLINK AS Power Interface Module (figure 9) provides power to the POWERLINK AS system and connections for field-installed external control devices.

EH1006A.0

Figure 9

CONTROL MODULE The POWERLINK AS Control Module (figure 10) provides programmable control for POWERLINK AS remotely operated circuit breakers.

–

+

–

+

STATUS

–

+

CPU

–

+

CLK

–

+

–

+

–

+

SETUP

–

+

RX

ADDRESS

–

+

TX

K BAUD

–

+

COMMUNICATIONS

MODIFY

SELECT

–

+

–

+

+ -

AS

Figure 10

BARRIER KIT If external control wiring is used, a Class 2 barrier kit (figure 11) is required. If necessary, two barrier kits (one straight end and one angle end) may be used.

Figure 11

8

1997 Square D All Rights Reserved

EH1006A.0