The text of a manual · part 2 of 4

POWERLINK AS Control Module AS42C and AS42C-T, pages 9 to 16

Pages 9 to 16 of 28

The original document is the PDF (327 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D AS42C and Schneider AS42C

Page 9

APPENDIX B - SYSTEM CONFIGURATION SHEETS

Bulletin 1210IM9502R12/97 December 1997

APPENDIX B, SYSTEM CONFIGURATION SHEETS Use the system configuration sheets in this section during programming of the control module using POWERLINK software. Keep the completed configuration sheets with the software user’s guide for use when making programming changes. There is one copy of each sheet. Make copies of each sheet to use during programming. Retain the originals with this manual.

1997 Square D All Rights Reserved

9

Page 10

®

10

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41

1997 Square D All Rights Reserved

Conduit Wire kVA PHASE

Software Filename

Options kVA

Wire

Conduit Wire

3

Breaker Options

Bkr. Size ▲

System File Name

Load Description Zone Zone Description

Interface Module Location

Short Circuit Current Rating

PNIM #, Network Address

B A B A B A B A B A B A B A B A B A B A B

Recommended Location For Power Interface Module And Control Module

Breaker Options

1

Mains Rating

Phase

Control Module Model ________________ Serial Number ______________________ Date of Manufacture _________________ Hardware Series ____________________ Firmware: U4: _________ U8: ________

Power Interface Model________________ Serial Number ______________________ Date of Manufacture _________________ Hardware Series ____________________ Firmware: U7: _____________________

Breaker Options AS, POWERLINK AS BREAKER LO, Handle lock-off device PA, Handle Padlock Attachment ST - Shunt Trip Type AUX, Auxiliary Contacts GFCI, Ground Fault Circuit Interrupter

■ Optional Location For Power Interface Module And Control Module

■

Bkr. Size ▲

Notes ■ Power interface module occupies 6 pole spaces. ▲ All circuit breakers to be 20-Amp, 1-pole unless otherwise noted. Totals: ØA kVA ØB kVA Total kVA

Load Description Zone Description

Mounting

NEMA Type Enclosure

Zone

Mains

Panel Type

Ckt No.

Voltage

Panelboard

POWERLINK AS Panel Wiring Schedule (1-Phase)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42

Ckt No.

Bulletin 1210IM9502R12/97 December 1997

APPENDIX B - SYSTEM CONFIGURATION SHEETS

Page 11

®

1997 Square D All Rights Reserved

Conduit Wire kVA PHASE

Software Filename

Options kVA

Wire

Conduit Wire

4

Breaker Options

Bkr. Size ▲

System File Name

Load Description Zone Zone Description

Interface Module Location

Short Circuit Current Rating

PNIM #, Network Address

A B C A B C A B C A B C A B C A B C A B C

Recommended Location For Power Interface Module And Control Module

Breaker Options

3

Mains Rating

Phase kVA

Breaker Options AS, POWERLINK AS BREAKER LO, Handle lock-off device PA, Handle Padlock Attachment ST - Shunt Trip Type AUX, Auxiliary Contacts GFCI, Ground Fault Circuit Interrupter

Power Interface Model________________ Serial Number ______________________ Date of Manufacture _________________ Hardware Series ____________________ Firmware: U7: _____________________

Notes ■ Power interface module occupies 6 pole spaces. ▲ All circuit breakers to be 20-Amp, 1-pole unless otherwise noted. Totals: ØA kVA ØB kVA kVA Total ØC

■ Optional Location For Power Interface Module And Control Module

■

Bkr. Size ▲

Control Module Model ________________ Serial Number ______________________ Date of Manufacture _________________ Hardware Series ____________________ Firmware: U4: _________ U8: ________

1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 37 39 41

Load Description Zone Description

Mounting

NEMA Type Enclosure

Zone

Mains

Panel Type

Ckt No.

Voltage

Panelboard

POWERLINK AS Panel Wiring Schedule (3-Phase)

2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42

Ckt No.

APPENDIX B - SYSTEM CONFIGURATION SHEETS Bulletin 1210IM9502R12/97 December 1997

11

Page 12

12 System Filename

PNIM, Network Address

*

1997 Square D All Rights Reserved

0

0 to 60 minutes (+/-) 0 to 60 minutes (+/-)

Sunrise Offset

Sunset Offset *AS42CM and AS42CM-T only Circuits / Zones Affected

1 to 42

0

1 to 12

Latitude Band

6

Hours, Minutes

0:00

1

9600

0000

0000

0000

Send

Run Inputs

Today's Sunrise Time

Sunrise/Sunset

0 to 199 (0 = point to point)

Network Address

0000-9999

Master

1200, 2400, 4800, 9600

0000-9999

Baud Rate

Communications

Access Codes Supervisor

Send, Get

Initialization Mode 0000-9999

Run Inputs, All On, All Off, No Change

No Controller Present

Operator

0.25 to 10.00 seconds, 0.25 increments

Sequence Delay

0.25

0

0 - 60 minutes (0 = disabled)

Blink Notice

Default 1

Selection

Software Filename

Panel Designation

1 to 53 (odd numbers only)

First Breaker Location

System Response

®

POWERLINK AS Global Setup Schedule

Bulletin 1210IM9502R12/97 December 1997

APPENDIX B - SYSTEM CONFIGURATION SHEETS

Page 13

®

Special Date 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

Start Date (MM/DD) End Date (MM/DD) Description

POWERLINK AS Special Date Schedule

Special Date 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 End Date (MM/DD)

Description

System File Name

PNIM, Network Address

Start Date (MM/DD)

Software Filename

Panel Designation

APPENDIX B - SYSTEM CONFIGURATION SHEETS

1997 Square D All Rights Reserved

Bulletin 1210IM9502R12/97 December 1997

13

Page 14

14 Input Type

INPUT Timer

TIME Day(s) SMTWTFS

Time HH:MM

EVENT

Notes: Refer to Special Date schedule for Special Date periods. Blink Notice applies only to scheduled "OFF" events and inputs with timed "OFF".

Input # Program # Special #

DESCRIPTION Name

®

POWERLINK AS Input/Event Schedule

Special Dates Zone(s)

ON Circuit(s) Zone(s)

OFF Circuit(s)

PNIM, Network Address

System File Name OUTPUT ACTION

Panel Designation

Software File Name

Blink Notice

Bulletin 1210IM9502R12/97 December 1997

APPENDIX B - SYSTEM CONFIGURATION SHEETS

1997 Square D All Rights Reserved

Page 15

Bulletin 1210IM9502R12/97 December 1997

APPENDIX C - OPERATION OF INPUTS

APPENDIX C - OPERATION OF INPUTS IN A POWERLINK AS SYSTEM INPUT SOURCES

INPUT STATUS VIA NETWORK

A typical POWERLINK AS panel may have one or more of its 16 local inputs connected to a wall switch or other dry-contact device. However, POWERLINK AS can also accept input signals from remote sources, such as the POWERLINK AS Input Expansion Cabinet. It is important to understand the interaction of input sources when configuring a POWERLINK AS system.

Input status can be monitored via network communications (for example, using POWERLINK software). However, since more than one source may be controlling the same input, it is very important to understand what the status bits for an input represent.

Input control is handled within the power interface module. When an input changes state, all breakers programmed to respond to that input change state. The transition of the input source, not the final input state, is important to system operation. An OFF-to-ON transition is interpreted as an ON event, and an ON-to-OFF transition is interpreted as an OFF event. By triggering breaker operation via input transition, multiple sources can operate the same input, with breakers responding to the last command. There are 64 input “channels” in each POWERLINK AS panel. Of these channels, 16 are internally connected to the eight input terminals inside the power interface module. The remaining channels are only available to remote devices.

Two bits of information represent each input: the “last input command state bit” and the “input command state unknown bit.” The power interface module interprets an input transition as an ON or OFF command. This command is recorded as the “last input command state.” For all input types except “priority maintained,” if panel power is interrupted, the last command state is lost and, therefore, the state is unknown when power is restored. This condition is indicated in the second of the two bits. The input command state unknown bit is available through communications, and should be used to qualify information contained in the last input command state bit. Any new transition of the input causes the system to learn a command state, and the input state is known again. “Priority maintained” inputs control breakers with a priority level above that of other input types and time programs and below that of continuous overrides. The action of a priority maintained input is much like an override effected by turning on an input. When the input is ON (the last input command state is ON), the breakers are placed in the states indicated by the program; when the input is OFF (the last input command state is OFF), the program is ignored.

Input Operation Table General Rules On Reset: Source Local Expander

Exceptions

State 0 0

Unknown 1 1

On Reset, if Input Type = Priority Maintained Source State Unknown Local (State) 0 Expander N/A N/A

On Transition: Source State Local (State) Expander (State)

Unknown 0 0

If Input Type = Inhibit Source State Local N.C. Expander N.C.

Unknown N.C. N.C.

Table 2 Notes: Local = Physical input connection to power interface module Expander = Input activity from expander (State) = State of input signal either ON (1) or OFF (0) N.C. = No change in bit status

1997 Square D All Rights Reserved

15

Page 16

Bulletin 1210IM9502R12/97 December 1997

APPENDIX C - OPERATION OF INPUTS

The action of a priority maintained input in its OFF state is different from that of other input types. For other input types, (when an input is OFF), the breakers assume a state opposite of that indicated by the program. Also, priority maintained programs, unlike programs for other input types, take effect immediately after a program is created and the physical input is ON.

This feature is useful when it is important that the breakers synchronize themselves to the state of a switch on power-up. For example, contacts from a photosensor may transition ON at dusk, but this transition would be missed if the panel were being serviced at that time. When power is re-applied, this feature causes the lights by the photosensor to turn ON.

Do not confuse the input command state with the physical position of a switch. Momentary switches are closed only briefly, but the switch closures are translated into ON or OFF command states. Maintained switches stay closed when turned ON, but they only update the input command state when a transition occurs. The input command state may be turned OFF afterwards by another source. The control module, for example, commands an input programmed with an input timer OFF when the timer expires, changing the last input command state to OFF. It is possible for the input command state to be OFF, while the maintained switch connected to that input is closed.

This feature may cause undesired operation in other applications. For example, if lights are commanded ON via a time event, but maintained wall switches are used to control the same lights, the state of the wall switch controls the lights after a power interruption. If the switch state is OFF, the lights turn off in response to the switch. For this reason, use momentary switches in applications where switches are used interactively with time schedules, or connect maintained switches through the input expansion cabinet.

Whenever an input type is changed to a type other than priority maintained, the input command state unknown bit is set, and the last input command state is set to OFF. For priority maintained inputs, because an internal command is generated during initialization, the input command state unknown bit is always clear. Input transitions, from any source, are ignored if the input type is set to “inhibit.”

POWER-UP OPERATION During power-up, the input command state unknown bits for inputs (except priority maintained inputs) are set, indicating the last input command state is not known. Priority maintained inputs (available for inputs 1–8 and 57–64 in the power interface module) are “automatically transitioned” after power interruption. This is useful in some applications. For example, if a priority maintained switch is closed at the time the panel is energized, this “automatic transition” causes breakers programmed to that input to respond as if the switch had transitioned closed. (If more than one local maintained input is assigned to control the same breaker, and the states of the inputs conflict, the lowest numbered input has priority.)

16

OPERATION WITH INPUT EXPANSION CABINET Inputs connected to the input expansion cabinet are remote inputs, which only affect the input command state when the commands are received. The input expansion cabinet only sends input information on transitions. Set the input range switch on the input expansion cabinet to the “9–56” position if any local inputs or maintained inputs are used (see figure 12). If the input range switch is in the “1–48” position, remote input 1 controls the same breakers as local input 1. Therefore, do not use local inputs if the input range switch is in the “1–48” position (see figure 13).

1997 Square D All Rights Reserved