Manual · Square D
POWERLINK AS Control Module AS42C and AS42C-T
Manual28 pagesPDF 327 KB
Instruction bulletin for the Square D POWERLINK AS control modules AS42C and AS42C-T: installation, programming basics and troubleshooting.
Covers · 2 models
The models it covers
Summary
What is in it
A Square D instruction bulletin for the POWERLINK AS Control Module AS42C and the time-of-day version AS42C-T, which control remotely operated circuit breakers in a POWERLINK AS panelboard. It explains how to install and remove the module, the front panel indicators and selection keys, how to set communication parameters, and what to do for common problems. Appendices describe the system components, configuration worksheets, input operation, priorities and sunrise/sunset data tables for the AS42C-T.
Its parts
- General
- Installation
- Programming Basics
- Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
Square D user's guide (Bulletin 1210IM9502R12/97) for the POWERLINK AS Control Module, covering both the AS42C and the time-of-day AS42C-T. It shows how to install and remove the module, set its network address and baud rate from the front panel, read its indicators and troubleshoot common problems. Appendices describe the other system parts, how inputs behave and how conflicting commands are ranked.
- What it is
- Control module for a POWERLINK AS system; switches up to 42 independent branch circuits through remotely operated circuit breakers p. 3
- Serial port
- RS-232 port for a temporary local link; needs serial communications cable #AS42CMSC p. 3
- Network settings
- Network address and baud rate, set with the SETUP, SELECT and MODIFY keys p. 4, 5
- Front panel
- LED display for address or baud rate; five selection keys; CPU, RX and TX indicators p. 4
- Power and mounting
- Snaps onto the POWERLINK AS power interface module, which powers it p. 2, 6
- Programming software
- POWERLINK PLK101 Software (Class 3080, Type PLK101) or POWERLINK Circuit Manager Software (Class 3080, Type CMS-1000) on an IBM PC-compatible computer p. 3
- Inputs
- 64 input channels per panel; 16 wired to the eight input terminals in the power interface module, the rest for remote devices p. 15
- Input Expansion Cabinet
- Optional; up to 48 additional inputs and 42 outputs, mounted within 50 feet of the panelboard p. 7
- Module removed
- Breakers go to the Default Controller Action set in software: ALL ON, ALL OFF, NO CHANGES or RUN INPUTS p. 2
- Version display
- Version key blinks the control module, power interface module and expander versions p. 4
- Display codes
- "C – P" at power-up means checksum passed; "C –E" means checksum error (firmware incompatibility, upgrade required) p. 5, 6
- AS42C-T
- AS42C-T: time-of-day module; its CLK indicator lights, and sunrise/sunset programs apply to it p. 4, 6
- Barrier kit
- Class 2 barrier kit required for external control wiring; two kits (straight end and angle end) may be used p. 8
- Reset button
- Pressed with a paper clip; restarts the module without affecting the system configuration p. 3
What this manual walks you through
- Installing the control module onto the power interface module p. 2
- Removing the control module p. 2
- Reading the front panel indicators and display p. 4
- Setting the network address and baud rate p. 5
- Turning on the optional security feature and using the security key p. 5
- Troubleshooting a dark display, unresponsive breakers and random switching p. 6
- The parts of a POWERLINK AS system p. 7, 8
- How local and expansion cabinet inputs work together p. 15, 16, 17
- How conflicting commands are ranked by priority p. 18
Good to know
- The module goes on with the panelboard deadfront in place; the deadfront must not be removed, and no force goes on the display. p. 2
- SETUP mode closes by itself if no key is pressed for two and a half minutes. p. 5
- With the expansion cabinet's input range switch at 1-48, local inputs should not be used. p. 16
- Where switches work alongside time schedules, the guide calls for momentary switches, or maintained switches through the expansion cabinet. p. 16
- The manual states the equipment meets FCC part 15 rules for a Class A computing device and may interfere in a residential area. p. 24
Questions this manual answers
What cable connects a PC to the AS42C RS-232 port?
The guide calls for serial communications cable #AS42CMSC when using the RS-232 port. p. 3
What does C-E on the AS42C display mean?
"C –E" at power-up is a checksum error from a firmware incompatibility; the guide says an upgrade is required. p. 6
How many circuits can the POWERLINK AS control module control?
Up to 42 independent branch circuits, through remotely operated circuit breakers. p. 3
What happens to the breakers if the AS42C is removed?
They go to the Default Controller Action set in POWERLINK software: ALL ON, ALL OFF, NO CHANGES or RUN INPUTS. Power need not be turned off to remove it. p. 2
Contents
Chapters and sections
Each line opens the PDF at its page.
- COVER23
- SECTION 1 - GENERAL1
- SECTION 2 - INSTALLATION2
- SECTION 3 - PROGRAMMING BASICS3
- SECTION 4 - TROUBLESHOOTING6
- APPENDIX A - SYSTEM COMPONENTS7
- APPENDIX B - SYSTEM CONFIGURATION SHEETS9
- APPENDIX C - OPERATION OF INPUTS IN A POWERLINK AS SYSTEM15
- APPENDIX D - PRIORITIES18
- APPENDIX E - SUNRISE/SUNSET DATA TABLES (AS42C-T Only)19
- GLOSSARY21