Manual · Square D
Class 8010 Type SLM-100 Loader/Monitor
Manual12 pagesPDF 255 KB
Instruction bulletin for the Square D SY/MAX Class 8010 SLM-100 Loader/Monitor, a hand-held or panel-mounted data access unit.
Covers · 1 model
The models it covers
Summary
What is in it
Square D instruction bulletin for the Class 8010 Type SLM-100 Loader/Monitor, a hand-held or panel-mounted unit for SY/MAX programmable controllers that monitors and alters processor registers and I/O status and displays English messages sent by the processor. It covers specifications, the key-operated MONITOR, ALTER and MESSAGE switch, keypad modes (decimal, hexadecimal, bit, binary), the display, connections and power-up, examples for displaying and altering data, register capacity, message mode, error messages, the NEMA 12 cover, remote mounting and use with the D-LOG data controller.
Its parts
- Introduction
- Specifications
- Key-Operated Switch
- Keypad
- Display
- Connections
- Power-Up
- Display Data (Decimal)
- Alter Data (Decimal)
- Display Data (Binary)
- Alter Data (Binary)
- Display Data (Bit)
- Alter Data (Bit)
- Register Capacity
- Message Mode
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Instruction bulletin 30598-163-03 (August 1986) for the Square D Class 8010 Type SLM-100 Loader/Monitor, a keypad and display unit for SY/MAX programmable controllers. It explains the key switch positions, how to view and change register data in decimal, hex, binary and bit form, the message display, error messages, the NEMA 12 cover and remote mounting. Every page is a scan read by OCR, so some figures and tables are not usable.
- Device
- Hand-held or panel-mounted loader/monitor for viewing and changing data registers and I/O status in a SY/MAX processor p. 3
- Processors
- SY/MAX Model 100, 300, 500 and 700 Processors p. 3
- Connection
- Single 9 pin differential plug into the processor's PROGRAMMER or COMM port; it carries both communications and power p. 6
- Display
- 16-character alphanumeric fluorescent display p. 3, 5
- Keypad
- 26-key sealed keypad with 0 to 9, A to F, arrow, DATA, ENTER, CLEAR ENTRY and BINARY, BIT, HEX, DECIMAL mode keys p. 3, 5, 6
- Key switch
- Three positions: MONITOR (view only), ALTER (view and change data), MESSAGE (shows processor messages, keypad disabled) p. 3, 5
- Mounting distance
- Within 10 feet of the processor; up to 10,000 ft with an added power supply and special cabling p. 3, 11
- Remote power
- Second 5 volt DC source, 1.0 amp at 50°C; Class 8030 Type PS-10 or PS-40 recommended p. 11
- Remote cabling
- Belden #8723 or #8728 cable, Class 8030 Type CC-40 cable, Class 9080 Type GM3 terminal block or equivalent p. 11
- Messages
- Shows processor messages of up to 16 characters sent with the PRNT command; the port must output at 9600 baud p. 9
- NEMA 12 cover
- Class 8010 Type SLM-110 cover with plexiglass window and lockable door; 10.25 x 13.58 x 4.50 inches overall p. 10
- Weight
- About 3.4 lb (1.54 kg) p. 4
- Registers
- Each register holds 16 bits, shown in binary, hex or decimal p. 9
What this manual walks you through
- Displaying register data in decimal or hexadecimal p. 6
- Changing register data in decimal or hexadecimal p. 7
- Viewing and changing data in binary p. 7, 8
- Viewing and changing single bits of a register p. 8, 9
- Showing alarm and report messages with PRNT statements p. 9
- Reading error messages p. 10
- Fitting the NEMA 12 cover p. 10
- Wiring a remote Loader/Monitor up to 10,000 feet away p. 11, 12
- Displaying D-LOG Data Controller messages p. 12
Good to know
- Protected registers, fenced registers and processor control registers cannot be altered. p. 5
- Timer and counter decode values cannot be changed from the Loader/Monitor; the bulletin suggests an IF comparison rung with a storage register instead. p. 7
- On units of series A, B, C or D, an external disable contact must be programmed in the PRNT rung, or the unit may lock up until power is removed. p. 9
- In remote wiring, pin 9 (shield) must run through the whole cable. p. 11
Questions this manual answers
Which processors does the Square D SLM-100 work with?
It connects directly to SY/MAX Model 100, 300, 500 and 700 Processors, plugging into the PROGRAMMER or COMM port. p. 3, 6
Does the SLM-100 Loader/Monitor need its own power supply?
Not when connected directly: power comes through the 9 pin plug from the processor. A remote unit needs a separate 5 volt DC supply. p. 6, 11
How far from the processor can the SLM-100 be mounted?
Within 10 feet normally, or up to 10,000 ft with an added power supply and special cabling. p. 3, 11
Why can't I change a register value with the SLM-100?
Data can be changed only with the key switch in ALTER, and never in protected, fenced or processor control registers. p. 5
What does ROM CHECKSUM mean on the SLM-100 display?
The bulletin lists it as a self-test error meaning a faulty Loader/Monitor. p. 10
Contents
Chapters and sections
Each line opens the PDF at its page.
- Class 8010 Type SLM-1001
- Loader/Monitor1
- Description1
- 1: Introduction3
- 2: Specifications4
- 3: Key-Operated Switch5
- 4: Keypad5
- 5: Display5
- 6: Connections6
- 7: Power-Up6
- 8: Display Data (Decimal)6
- 9: Alter Data (Decimal)7
- 10: Display Data (Binary)7
- 11: Alter Data (Binary)8
- 12: Display Data (Bit)8
- 13: Alter Data (Bit)9
- 14: Register Capacity9
- 15: Message Mode9
- 16: Error Messages10
- 17: NEMA 12 Cover10
- Appendix A11
- Appendix B12
The whole text · 2 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.