The text of a manual · part 2 of 2

Class 8010 Type SLM-100 Loader/Monitor, pages 7 to 12

Pages 7 to 12 of 12

The original document is the PDF (255 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D SLM-100

Page 7 read from a scan by OCR; it may hold reading errors

9.0 ALTER DATA (DECIMAL)

The following example outlines the steps for entering data into any given register. Protected registers, fenced registers and Processor; Loca! Interface control registers cannot be altered.

NOTE: Keyswitch must be in ALTER position to enter data.

Regosier Data

KEY OPERATION DISPLAY DESCRIPTION 1. Depress CLEAR xiv REGISTER ad- ENTRY Key B00} DEC edie dress display is set to B89)

30598-163-03 Page 7

10.0 DISPLAY DATA (BINARY)

Once a desired register is addressed and its contents displayed, the binary equivalent of the data can be shown in the display window. This mode is useful to monitor the ON-OFF status of !6 external MO or internal outpul points, as well as counter and timer information.

Example: To display the dala in register 23 in binary

2. Enter register address containing the data to be changed (i.e. register 20)

692% DEC 9g127

Register Dyuta

Loader’ Monitor displays current data in register $20 (in this case, 127)

3. Depress DATA Key

G92 DEC 96137

Revistet Data

Right-most digit flashes, indicating that data can now be entered.

4. Enter data (i.e. 2047)

BRB DEC M294f

Register Dyista

Number shifts in from right of DATA window

5. Depress ENTER Key p92 DEC 42947

Register Data

Number entered into Register S20 formal:

KEY OPERATION DISPLAY DESCRIPTION

1. Depress CLEAR NZ 5 REGISTER

ENTRY Key wy DEC all address counter Regnier | sets to the last register in which data has been entered

2. Enter register address to be we2y DEC 49999

Indicates that the decimal] number monitored (i.e. seen “1 |in register S23 register $23) is 999

Display shows 3. Depress BIN HOBBIT 1199111 the combination Key Reenter M8 Hof 16 ones and zeros which are the binary equivalent of the

9.1 Alter Data (Hexadecimal)

To enter Hexadecimal data. first depress the HEX key before entering the register address. Then follow steps 3, 4. and 5 of paragraph 9.0.

9.2 Altering Timer/Counter Decode Values

Since both timer and counter decode values are entered as fixed values when programming timer and counter rungs, they are not alterable by the Loader/ Monitor. Therefore, to provide Loader! Monitor, accessible decode points, the recommended approach would be to program an IF comparison rung inaddi-tion to the timer or counter rung. The IF rung would compare the timer or counter value to a storage register to provide another decoded output. The Loader; Monitor may then be used to alter the data in the storage register, thereby changing the decode point. For additional information, refer to the CRT ot Hand-Held Programmer Instruction Bulletin.

decimal number 999

NOTE: To display another register, the DECIMAL or HEX key must be pushed in order to enter another register address.

Individual BITS within the register can be altered by depressing the DATA key. See Section 11.0.

NOTE: Keyswitch must be in the ALTER position 1o enter data.

Page 8 read from a scan by OCR; it may hold reading errors

Page 8 30598-163-03

11.0 ALTER DATA (BINARY)

Bits of Processor! Local Interface, Control Registers, Protected Registers, and Fenced Registers cannot be altered.

NOTE: Keyswitch must be in she ALTER position to enter data.

When the DATA key is depressed (still in BINARY mode) the right-most digit will flash, indicating the Loader; Monitor will now accept dala. The right-most BIT can now be altered. At this time the only numerical keys which are active are the | and the 0 keys. If another BIT is to be altered, pushing the Left/ Up Arrow Key will cause the next significant BIT of flash. This indicates that the secund significant BIT can be altered by entering a loraQ. Fach time the Left! Up Arrow Key is depressed. the flashing digit will move one space to the left; each ume the Right/ Down Arrow Key is depressed, the flashing digit will move to the right. The digit which is flashing is the BIT to be altered. After the Left! Up Arrow Key is depressed 16 times, the flashing digit will loop around back to the least significant BIT on the right. Once the display bas been changed to the desired BIT pattern, the ENTER key must be pushed to transfer the data into the processor. Once ENTER has been pushed, no digits will flash, indicating that the new data has been loaded. Depressing the CLEAR ENTRY key anytime prior to pushing ENTER will set the flashing digit to the right-most positionand Testore the original data.

EXAMPLE:

To change BIT 3 of register $18 from a @ 10 a I.

KEY OPERATION) DISPLAY DESCRIPTION = - - REGISTER 1. Depress We} DEC B99 address display is CLEAR ENTRY] Hc rae | | set to the last Key address for which data was altered

Indicates that the decimal number

2. Enter register address containing the dala to in regisier be altered 18 is 0000 y Register Datia 18 & 77 ]] Rightmost bit 4, Depress SBBnIARORORAOIY, flashes, indicating DATA Key Beenie pe! gata can new be entered 5. Depress the st Moves flashing Lett Up Arrow ideale se digit to 3rd ey Twice posilion aoaeraasod! ¢ New data value 6. Depress | Key nie add placed in 3rd bit position (1 is now flashing) Flashing bit st 7. Depress FOREOBIARBOUE | 4 flashing. This ” ENTER Key Reghier ps? _J| indicates that the data has loaded into the processor

When in the binary mode of operation, the entire display is used to show the BIT pattern (£6 ones anu zeros} of a given register. Therefore the register address and mode of operation cannot be shown. To change an address, the user must first enter another mode (DECIMAL, HEX, or B!T) so he can then enter another address.

12.0 DISPLAY DATA (BIT)

The BIT mode lets the user access data BITS within a register one at a time. This mode is mast useful for displaying the ON-OFF status of a single external 1/O point or internal output. When the BIT kev is depressed. the Tegister that wus last displayed remains in the address window. The word “BIT-" is displayed where the word “DEC” or “HEX” would normally appear, Following the dash is the number @1, indicating that the data BIT displayed is the least significant BIT of the selected register.

For register S9, | 4099 BIT. ¢1 g Mode Bit# Data

Repister

The right-most digit (DATA) will contain a | or 0 representing the status of the BIT. If an internal or external 1/O address is being displayed, 1 indicates the particular 1;O is ON or energized. 0 indicates that the I/O is OFF or de-energized,

Pushing the Left! Up Arrow Key increments the BIT number and the new data is displayed at the right. Each time the

Lefti'Up Arrow Key is pushed the BIT number increments by one.

EXAMPLE:

Display BI! 5 of Register $52

KEY OPERATION DISPLAY DESCRIPTION 1. Depress BIT Key oat BIT-#| @ Loader Monitor | Register Osta (displays the same register which was last displayed) | 2. Enter Address ay Display shows to be Manitared WS 2 BIT# g current status of (i.e. $52) Beenie’ ~“1} BIT | register $52 3. Push Left/Up SV BIT number in- Arrow Key aS. BIT-A5 | crements to BIT 5 4 times Register Dara and the DATA of | indicates this BIT is ON or energized if BIT 16 is displayed and the Left/Up Arrow key is pushed, the register address will increment by one and BIT-@1 will be displayed for the next register. If BIT-@1 is displayed and the Right/Down Arrow key is pushed, the register address will decrement by one and BIT-16 will appear Holding the Arrow keys down wil! rapidly increment or decrement the display.

If an invalid address is centered while in the BIT mode, “ILLEGAL ADDRESS" will be displayed.

Page 9 read from a scan by OCR; it may hold reading errors

13.0 ALTER DATA (BIT)

New BIT cata can be entered via the following steps. NOTE: Keyswitch must be in ALTER position to enter data. Bits of Protected Registers, Fenced Registers and Processor Local Interface Control Registers cannot be altered.

EXAMPLE:

Change BIT 2 of Register S75 from | to §.

KEY OPERATION DISPLAY DESCRIPTION

|. Depress BIT YY ny Displays last

Key dies BIT-# a register which Enter baler was shown

Display shows Status of BIT #1 register S75

2. Enter register we address (1.¢. 75) APS BIT-#1 @

Regnier ata

J. Depress Lelt/ Display shows

Up Arrow status of BIT #2

Key once ital mS} register S75

4. Depress DATA 5] j Status of BIT 2 9975 BIT-#2 A flashes indicating

Key

Repeater “lithe DATA can now be changed

5. Depress 0 svt) New DATA of BIT -#2 window {sull flashing}

The new DATA ig loaded into

4 Depress ENTER wns BIT V2 #

Kepter Vers the processor: DATA stops flashing

30598-163-03 Page 9

14.0 REGISTER CAPACITY

Any register monitored contans 16 BITS of information. Based on the address selected, this information can represent:

1. External VO (ie. a group of 16 inpuls and outputs?

2. Internal [/0 tic. a group of 16 relay cquivalents?

3. Data fie. a number within the register represent-img a timer value, counter value, math function, shifl register dala, ete.)

Data within any given regisier is stored in binary form, but can he displayed on the I.nader/Manitor jn binary, hex, or decimal format.

In the binary mode. data can range fram IIIT to CeepIpEeesE

In the hexadecimal mode, data can range trom FFFE to BAY.

In the decimal mode, data can range from 32,768 to 32.767.

The beft-most (most significant) BIT of the data register is used as the sign (-) BIT, when displaying numbers in the decimaf mode. When a negative number is displayed or entered, the most significant BIT of the register will be one (ij). Therefore any numbers larger than 7FFF (#7EX>} or PUIEVI TERA EEA (Binary) will appear as negative when displaying them in the decimal mode. This method of storing negative decimal data is teferred to as “two's complement”. For further explanation of two's complement. refer to Appendix A of the CRT or Hand- Heid Programmer Instruction Bulletin

15.0 MESSAGE MODE

The capabilities of the Loader Monitor can be extended beyond data entry and monitoring functions when put in the message mode. Placing the keyswitch in the MESSAGE position translorms the l.oader/Monitor into an alpha-numeric display, thus enabling the user to perform alarm annunciation and report generation at no extra cost. By utilizing a special PRNT command in the processors user program, any English language command up 1o 16 characters can be displayed. This message can be triggcred by a control action of the processor to produce messages such as “HIGH TEMP ALARM” or “CON- VEYOR 9 DOWN” for alarm annunciation. Numbers contained in data registers can also be printed on the display. This makes report generation messages such as “PARTS COUNT 4193” or “TIME 12.09" possible. Several PRNT statements can be programmed 10 produce extended messages by scrolling them across the screen or by flashing up successive messages.

NOTE: Refer tothe CRT programmer instruction bulletin for PRNT statement format. The port to which the Loader Monitor is connected to must be outputting the PRNT message at 9600 BAUD.

NOTE: In Loader Moniors with series designations A, B.C, or Da disable contact from an extemal | O must be programmed in scries with the PRNT INITIATE contact in the PRNT rung. Theexterna)] Odisadle contact must be opened before the keyswitch of the Loader Monitor is switched out of the message mode. This external contact serves to disable the PRNT message transmission when the keyswitch is placed in the Monttor or Data Enter position. If this ix not done, the loader! Monitor may lock up and can only be cleared by dis-connecting power from the Loader Monitor.

Example: MESSAGE PRINT MODE ENABLE INITIATE I 1 PANT

(EXTERNAL I/O} (ASDRese )

Page 10 read from a scan by OCR; it may hold reading errors

Page 10 30598-16303

16.0 ERROR MESSAGES

ILLEGAL ADDRESS, User attempted to enter an insalid register number (refer to Programmer Instruction Balletin for proper register addressing).

IPE FGALOATA User attempted to enter data greater than 32.767 of less than -32.768.

FENCED, Userattempted to enter data inte a register which has been protected Venced) by the programming equipment.

PROTECTED, () User attempted to enter data into registers SOO] thru 8192 (NOT ALLOWED), 2) User attempted toenter data after the REGISTER PROTECT command was entered bs the programming equipment.

READONLY, Userattempted te write to an external input. FORCED), 1) User aulempted ta change the status of an output while the processor was in HALT. 2} User attempted to change the status of an [ O which had been forced by the programming equipment. ROM CHECKSUM | Sell testerrer-faulty Loader Monitor, Nore: Depressing the CLEAR ENTRY key will clear the error message and restore original data. (if in the data mode) or display the last selected register (if in the display mode).

17.0 NEMA 12 COVER

The Class 8010 Type SILM-100 Loader. Monitor may be mounted in the Class 8010 Type SLM-110 NEMA 12 Cover. When the cover is mounted on toa NEMA L2 cabinet, NEMA 12 protection is provided to the Loader’ Monitor. The cover includes a plexiglass window to see the Loader! Monitor display, and a lockable door assembly used 10 access its keyboard. A user-supplied padlock may be used to restrict access to the keyboard.

} 2.83 | (4.5) 449 = 4 0061 9.94 (25.5) 7.00 (7@) wate. ia Bi

@

Cs v_) Lita) 204 DA. MTG. HOLE (.$2}

Welght oo. cee cece eee 9.5 Ib. 4.32 hy. Overall Dimensions (WHS DD). cee eee eee 10.25 x 13.58 x 4.50 inches

26.04 x 34.42 s 11.43 em

Mounting Dimensions (WAH) cic ee cece eee 7.00 x 12.55 inches 17.78 x 31.88 em

~ - 3.69, ™ {9.37)

zo 12. $5 tg, ie, Soo PI 13.9) HOLE

Page 11 read from a scan by OCR; it may hold reading errors

30598-163-03 Page It

APPENDIX A REMOTE MOUNTING

I1 is possible to locate the Loader’ Moniter up to 10,000 fect from the processor. This appendix will serve as a guide for wiring the remote Loader; Monitor (see Figure A.1). Because the Loader; Monitor is located remotely from the processor, a second source of 5 volts must be supplied. The Class 8030 Type PS-10 or Lype PS-40 Power Supply is recommended, however, another commervia] equivalent could be used, provided it is 5 volt DC capnble of 1.0 amp at 50°C, 50/60 cycle.

Necessary Equipment: Belden #8723 or #8728 Cable 1 Amphenol DE9P {Male) or equivalent 1 Amphenol DES (Female) or equivalent Class 9080 Type GM3 Terminal Block or equivalent 2 Cineth DES1218-L (Covers)

2 ITT CANNON DE 51224-1 (Slide Lock Connector)

yy o |> oO PS Type Supply |L, eS

1 Class 8030 Type CC-40 with a PS-10 or PS-40 or minimum If AWG wire if equivalent Power Supply is used 1 Class 8030 Type PS-10 or PS-4U or equivalent 9 two inch 22 AWG wires The connection between the 8030 PS-J0 or PS-40 and SY/MAX Processor must be constructed by the user. The connections are shown in Figure A.2.

NOTE: Pin 9 (shicid) must be carried through the entire cable.

The DC power is supplied to the Loader’ Monitor via pins 5, 6, 7, and 8.

For proper mounting of the PS-10 or PS-40 Power Supply see the Power Supply Instruction Bulletin 30598-156-XX.

coca d

Le

Amphenol DESP (maie)

Pn sar supplied cable

8030 {Belden #8723 or #8728) CG-40 Cabie

Terminal Block

40,000 tee ™ (- Amphenol DESS (femaie} att 16 ff. max. a ~

2 SLM-100 Loader/Monitor

Figure A.

KR O ; rie a i INCOMING POWER | Temas ' ‘ | he i | ! partie | |

Do omatrenr mace

7

8030

1 PS10 or PS40

Page 12 read from a scan by OCR; it may hold reading errors

Page 12 30598-163-03 ft. 1 To ° 2 Loader oO 43 Monitor °o 4 °o 5 Oo 6 Oo 7 o i] (oO Amphenol DESS (female)

r™~ 2 3 4 |\To gf Processor/ s D-LOG Module 2 1...7 Ampheno! 2...2 DESP (mate) ‘ . y Belden #8723 or "B728 5 ...5 6...6 Watt) 7 ...7 a...8 }(-} 9...9 CC-40 ee ee” 22 AWG PS10 Terminal or Block Remote Power Supply

CONNECTIONS Figure A.2

APPENDIX B

DISPLAY FOR THE D-LOG DATA CONTROLLER

The loader Monitor may be used to display PRNT messages generated by the Class 8030 Type DILM-110 or Type DLM-120 D-LOG Data Controller Modules. An external 5 volt power supply is necessary. The same configuration and connections mas be used as in Figure A.] and A.2 (see Appendix A}.