Class 8010 Type SLM-100 Loader/Monitor, pages 1 to 6

Pages 1 to 6 of 12

The original document is the PDF (255 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Square D SLM-100

Page 1 read from a scan by OCR; it may hold reading errors

Bulletin: 30598-163-03

Pave: 1 of 12

Instruction Bulletin Date: August. 1986

Subject: SYWINAH ‘

CLASS 68010 TYPE SLM-100

LOADER /MONITOR DESCRIPTION: The following contains detailed information on the Class 8010 working knowledge of the various controllers’ addressing Type SLM-100 1 oader Manitor. Included are instructions on schemes ws assumed. For addressing information, the user its operation and installation. The Loader Monitor is designed should refer to the instruction bulletin which describes the ty work with the SY MAX® Programmable Contreller particular processor being used.

Family. A NEMA 12 lockable cover is optionally available. A

Copyright © Square D Company. 1986 Q U A R E Supersedes 30598-163-02. April 1982 G, - - - D

AJR Pimedin[ SA

Dedicated to Growth ©¢ Committed to Quality

Page 2 read from a scan by OCR; it may hold reading errors

Page 2 30598-163-03

TABLE OF CONTENTS

Section Number Title Page 1.0 INTRODUCTION epPmpeenenseepewpaeneeepeeeeveeaease e*eeanpseeoeoeoesvp cute eaeaweaeauenepaeee @eanseageagaanraeans 3 2.0 SPECIFICATIONS emeeenseseepwpaeeneeaeeee @satnoepoeoeeaenpupuppeeanepeuemewaenueeaepe @eeoenaeaeanu 4 3.0 KEY OPERATED SWITCH... cece cnc e ence ew manne ae neescceannan 5 3.1 Monitor .. cc ccccsncccsrnnaccesvenacse seep ep gecueepepueumpeaee @eaeeeeoeeeeoenpnupuuns 5 3.2 Alter. .ccansccsnnscenunecesssn eenpnpneepaeaea *enpnpnepewpmepaanaea @#eeeoeascanpnpaeoeeae 5 3.3 MeSSage ..ncsrccccsrnccccensvens sep aae seep emeenepeenseepewraea @eaeeeoeoeeea 5 4.0 KEYPAD ... cnn ccscvnncvunes ese neppmpeoeeesepepepeeeeeepewpeauaea @eaeseecooeoesenupnpoeoeeeeeeea 5 4.1 Decimal Mode...... erpvwvaea sp=eaeeeeaeaeseeoeoeenee sceoeerpteeeeeaweenune empaeaeneeageaan 5 4.2 Hexadecimal Mlode@ ... ccc eve nace nnacvsenane see ep ae eereeeweeae tut 5 4.3 BIT Mode, eweneanepnenpweaenseneeweweaenewsneawewes @eeoeoaeecaeseoeoeoeeoeeaeopeoeeeoeepenpeeeeesesegceE 5 4.4 Binary Mode ....... ccc ccc cere enn nenneeneeen @enpompeaenepeueepeepepepaeaeaauen 5 §.0 DISPLAY......... ee me dene ween mane ere eee eee nee pa eaeewees 5 6.0 CONNECTIONS . ww ww wcc vc cc cere ena ceeecanenvecareceascavevesccessy 6 7.0 POWER-UP.... ccc ccc can re ccarwnccaneccnnarenaceneneennsaaaaeeevaes 6 8.0 DISPLAY DATA (DECIMAL) LR RRR RERRRERARER RRR RR RRR ERR RE RAERER RR ERSRE RE RRR RRR RE FY 6 8.1 Display Data (Hexadecimal) ...-..sccacccccnvaccccnvcncunevansanvanea 6 9.0 ALTER DATA (DECIMAL) BESS R BOTT Ree eee RP Eee eee eee eee eee eee eee eee 7 9.1 Alter Data (Hexadecimal) ......cccsccscsrccvscnvveresnvccscenecnecune 7 9.2 Altering Timer/Counter Decode Values .......cccccsccssccnecnecsen 7 10.0 DISPLAY DATA (BINARY) eaeenee ee ene enaeeaeeeteaeeseeeaeeweeeseeseeseseeeeneeatne 7 11.0 ALTER DATA (BINARY) 2.20.2 cc eww ccc wcrc ccc w ccc nnnccccaretscesces 7 12.0 DISPLAY DATA (BIT) ....cccccewcc nnn nneenaeennnee eee eee eeanan 8 13.0 ALTER DATA (BIT) g@anpeuee@aeaaeaeewa#pwpepeanasewoaeaeeearppeeespteepeeeeeeeeepeweaeaaaeaanneee 9 14.0 REGISTER CAPACITY... .cccveess Benepaeaeaewepeepunea @#epeeppenpegcaaceanvneeea eae eepenesd 9 15.0 MESSAGE MODE epee evpepeeecesepeeeeetp PR BOepeaeeeeaeaawant @enpnpagcpepepeepeegeeeepeepwepeaeaangee 9 16.0 ERROR MESSAGES Seueaee eee eeeeaeeeeeee eee ee ene Pee eneaeeeaneereeneeceseaeectrnpeacne 10 17.0 NEMA 12 COVER SCC TCERP TEPER RSSESREC EES REE easeeeeee ree eee edentoeaeeanzoad 10 APPENDIX A, Remote Mounting eseeeeeeepeepevpeemueneaeeuaerpaenrpaepnaeaeecntana 11 APPENDIX B, Display for the D-Log Data Controller .............. 12

The products and services described in this manual are useful ina wide variety of different applications. Therefore, the user and others responsible for applying the products and services described herein are responsible for determining their acceptability for each application. Whik efforts have been made to provide accurate information within this manual, the Square D Company assumes no responsibility for whe accuracy, completeness. sufficiency or usefulness of the information contained herein.

Under no circumstances will the Square D Company or any of its subsidianes be responsible or liable for any damages or losses.

including indirect or consequential damages or losses. arising out of either the use of any information contained within this manual or the use of any products or services referenced herein.

No patent liability ts assumed by the Square D Company with respect 10 ihe use of any of the information. products. circuits, programming or services referenced herein.

The information contained within this manual is subject to change without notice.

Page 3 read from a scan by OCR; it may hold reading errors

30598-163-03 Page 3

1.0 INTRODUCTION

The S¥;MAX Loader; Monitor is a hand-held or panel-mounted device which provides easy access to data at a minimum cost. Any data registers within the processor can be monitored. The status of external I/O and internal outputs (relay equivalents) can also be monitored. The data within any register not protected by the processor's fencing capability can be altered (with the exception of processor control registers). The Loader! Monitor provides the user with the capability of changing timer delays. counter set-points, math constants, etc; without the need for any other programming equipment. It is also capable of displaying

.OADER © MONITOR

English language messages such as alarms. production reports. and machine diagnostic information,

The Type SLM-100 connects directly to the SY MAX Model 100, 300, 500, and 700 Processors. It is enclosed in sheet metal and designed to be panel-mounted within I0 feet of the processor. The addition of a power supply and special cabling will extend this distance up to 10,000 ft.: see Appendix A. The front panel contains a 16 character alphanumeric display, a key-operated selector switch, and a sealed keypad.

Sixteen character alpha- numeric fluorescent display.

Key-operated selector switch

MESSAGE - Display English language messages generated by the processor (Keyboard disabled).

ALTER - In addition to the Monitor operations, data may be altered in any unprotected register, or unfenced register.

MONITOR - Display the status of external I/O, inter- nal outputs, and data within any storage register. No data may be altered.

26 Key Sealed Keypad

Page 4 read from a scan by OCR; it may hold reading errors

Page 4 30598-163-03

2.0

Weight (Approx.).......... 3.4 ib/1.54kg.

SPECIFICATIONS

Rated Current Draw on SY/MAX Power Supply

Ambient Temperature Humidity Rating, - [(2) *g@-32 TAPS

.... 600mA Typical oo00 9.00 | 8.4 22a OOO UO 215 ! OU OOO UO HOO U CLIO OOO Oo | \ a, - 3.34 27 &5 7 6.69 170 oY po, 225 YY 8-32 TAPS i TO ss. Dual Dimensions: ae 4 39 T 2.67 6.45 ja 164

0 - 60°C 0 - 95% Non-condensing

Page 5 read from a scan by OCR; it may hold reading errors

30598-163-03 Page 5

3.0 KEY-OPERATED SWITCH

A key-operated selector switch determines the Loader Monitor’s function. The key can be removed in any one of the three positions.

3.1 Monitor

With the key switch in the MONITOR position, data and 1/0 status can be monitored by entering the address of the desired register. The Loader! Monitor then automatically displays this information. Data cannot be altered in this mode.

3.2 Alter

With the key switch in the ALTER position, the Loader; Monitor is still capable of monitoring data registers as described above. In addition, the user can enternew data from the keypad. Data can be altered only inthis mode. Data cannot be altered in protected registers, fenced registers, or in Processor} Local Interface control registers.

Key Switch

3.3 Message

If the key switch is placed in the MESSAGE pasition, the keyboard is disabled. In this position the Loader’ Monitor will display any alphanumeric message generated by the processor. [ising the loader; Monitor in this manner provides alarm annunciation and report generation without the need for any expensive, additional hardware.

4.0 KEYPAD

Key Pad

A numerical keypad (0 to 9) is used to enter the address of the data register to be monitored or altered. The Left/Up Arrow Key and Right! Down Arrow Key may be used to increment or decrement through the registers being examined. Once displayed, register data can be altered (keyswitch in ALTER posi-tinn) by using the DATA and ENTER keys. The four keys labeled BINARY, BIT, HEX, DECIMAL determine the Loader; Monitor’s mode of operation. The A, B,C, D, E,and F keys are used to enter hexadecimal information.

If the DATA key is mistakenly struck, then the DATA mode can be caited by pushing the DATA kcy again.

4.1 Decimal Mode

For normal operation, the Loader; Monitor wil] be in the decimal mode. When first initialized it automatically enters the decima! mode. Registers are addressed, and data displayed, in the decimal numbering system. If the Loader’ Monitor is in another mode, it can be returned to the decimal mode by depressing the DECIMAL key. 4.2 Hexadecimal Mode

Depressing the HEX key puts the Loader; Monitor in the hexadecimal made. Allfunctions are the same as when operating in decimal mede, except all data is displayed and entered using the hexadecimal numbering system.

4.3 Bit Mode

Placing the Loader; Monitor :n the BET mode allows the user to display the ON-OFF status or alter a single 1; © point or bit of any given register.

4.4 Binary Mode

Once the desired data in a register is displayed, the binary equivalent of that decimal or hexadecimal] number can be shown by depressing the BINARY key. In this mode, 16 ones and zeros will appear, representing the binary data in the register.

5.0 DISPLAY

A bright fluorescent display is visible in any type of lighting environment. This display not only shows numerical data, but is also capable of disptaying alphanumeric messages generated by the processor.

Display

Page 6 read from a scan by OCR; it may hold reading errors

Page 6 30598-163-03

7 2 ra) 3

S Pin OFFERENTIAL rive

|

XN,

6.0 CONNECTIONS

A single 9 pin differential plug provides the only needed connection to the processor. All communications and necessary power are provided through this connector. The Louder/Monitor plugs directly into the PROGRAMMER or COMM port on the processor via this plug. No additional interface or AC power source is needed.

The addition of a power supply and special cabling enables the mounting distance to be extended up to 10,000 ft. See Appendix A.

7.0 POWER-UP

Because no additional power source is needed for the I oader; Monitor. it will autemancally power up when connected to the processor. Initially the display will show “SY;MAX REV _™ where the, will contain a software revision letter or number, e.g. E, t.l, etc. This letter identifies the specific version of operational software contained in the unit. All kevs on the kev-pad will be disabled except for the CLEAR ENTRY key. Depressing the CLEAR ENTRY key will put the Loader: Monitor in the decimal mode, the register address valuc will sct to BABI, with is contents appearing in the DATA window.

aon | DATA

| 9aa1 DEC REGISTER

(The data displayed for register | will be O#Y provided all of the inputs and outputs assigned to register | are OFF.)

8.0 DISPLAY DATA (DECIMAL)

The following example outlines the steps for displaying data in the decimal mode.

NOTE: The keyswitch must be in either the MONITOR or ALTER positions.

KEY OPERATION DISPLAY DESCRIPTION 1 Depress CLEAR 7 REGISTER ad- ENTRY Key acl DEC me dress display is set

Repiver The to $91

2. Enter register address to be monitored

(i.e. register 17)

The data display indicates that the decimal number in register S17 is 4192 wif DEC $4192

Regusier Daw

ENTERING AN INVALID ADDRESS WILL. CAUSE THE LOADER;MONITOR TO DISPLAY “ILLEGAL ADDRESS”.

Subsequent repister data can be displayed by depressing the CLEAR ENTRY key again and entering in the next address to be monitored. The Loader/Monitor will immedi-alely index 1o that address and display the register’s contents.

Registers can be sequentially displayed by depressing the Arrow keys. Fach time the Arrow keys are depressed, the register address will increment or decrement by ane and the DATA display will show the new data value. Holding cither key down will cause the Loader Munitor to rapidly increment or decrement the cegister address.

8.1 Display Data (Hexadecimal)

If is it desired to display data in hexadecimal format, simply depress the HEX key before entering in the register address. When this is done, the value in the data window will be the hexadecimal equivalent of the decimal number in that register The Arrow keys operate as described in paragraph 8.0.