Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact
Page 1 of 24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625 User's Manual

Manual · Square D

24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625 User's Manual

Manual12 pagesPDF 394 KB

User's manual for the TBX DMS1625 distributed I/O base unit with eight 24 VDC inputs and eight relay outputs (SY/MAX, Telemecanique).

Download the PDF394 KB

Covers · 2 models

The models it covers

Summary

What is in it

Instruction bulletin for the TBX DMS1625, a distributed I/O base unit with eight 24 VDC inputs and eight relay outputs that works with SY/MAX or Telemecanique PLCs through a communications interface such as the Class 8030 Type CRM275 DRIO. It gives the specifications for base power, inputs, outputs and environment, dimensions, terminal strip wiring for SY/MAX and Telemecanique labels, DIN rail mounting and removal, installation considerations, and register usage with the CRM275.

Its parts

  1. Description
  2. Specifications
  3. Base Unit Wiring
  4. Mounting Instructions
  5. Installation Considerations
  6. Register Usage with the SY/MAX Class 8030 Type CRM275 DRIO Module

From the manual · read page by page

Key facts from this manual

Each line names its page in the PDF.

Square D instruction bulletin 30598-376-01B1 (July 1997) for the TBX DMS1625, a 24 VDC 8 input / 8 relay output distributed I/O base unit. With a communications interface mounted on top it serves SY/MAX or Telemecanique PLCs. It gives the specifications, terminal wiring, mounting, installation rules and register use with the CRM275 DRIO.

What it is
Distributed I/O base unit with eight 24 VDC inputs and eight relay outputs, for SY/MAX or Telemecanique PLCs through a communications interface (top hat) p. 3
Base power
24 VDC nominal, 19-30 VDC; 125 mA base only, 195 mA with comms interface, 310 mA with interface and expansion base p. 4
Inputs
8 inputs, 8 commons, 24 VDC nominal (19-30 VDC), 15 mA; turn-on 11 VDC, turn-off 5 VDC; 1500 V rms isolation p. 4
Outputs
8 relay outputs, 4 output commons (one per two outputs); 24 VDC nominal (19-30 VDC) or 24-240 VAC; 2000 V isolation p. 4, 9
Output loads
DC: 24 W resistive, 10 W inductive (L/R = 60 ms); maximum surge current 30 A p. 4, 5
Interfaces
Class 8030 Type CRM275 DRIO (IO/NET); TBX LEP020 and TBX LEP030 (FIPIO); TBX CBS010 Expansion Interface for a second base p. 3
Switching times
Inputs: 15 ms on, 17 ms off maximum; outputs: 10 ms on, 20 ms off maximum p. 4, 5
Dimensions
3.43 x 9.25 x 2.4 in (87 x 235 x 61 mm) H x W x D with terminal strip; 2.91 in (73.9 mm) deep with an interface p. 5
Weight
1.3 lb (0.6 kg), base unit only p. 5
Temperature
Operating 0 to 60 °C (32 to 140 °F); storage -40 to 80 °C (-40 to 176 °F); 5-95% RH non-condensing p. 5
Mounting
35-mm DIN rail or panel, horizontal or vertical, 1 in (25 mm) spacing p. 8, 9
Wiring
40 position removable terminal strip; up to two #16 AWG wires per terminal; #16 AWG jumper between terminals 2 and 40 p. 6, 9
Power supply
TBX SUP10 can provide 24 VDC for TBX bases and sensors from an AC source p. 3
Agency compliance
The manual states it complies with UL508, CSA C22-2 and FM Class I, Division 2 Hazardous Locations approval requirements p. 6

What this manual walks you through

  • Wiring inputs and outputs with the SY/MAX or Telemecanique terminal label p. 6, 7, 8
  • Mounting the base unit on a DIN rail or panel and removing it p. 8, 9
  • Connecting base voltage, control output power, jumpers and fusing p. 9
  • Setting output fallback states for loss of communication p. 9, 10
  • Connecting loads to the relay outputs p. 10
  • Register usage with the SY/MAX Class 8030 Type CRM275 DRIO p. 10

Good to know

  • The base unit is not compatible with the Type CRM270 interface module. p. 9
  • The base and control power lines must be fused externally by the user. p. 9
  • Ground the base with the screw provided before applying power; metallic conduit is not a ground conductor. p. 7
  • Use the terminal label numbered 1-16 with SY/MAX and the one numbered 0-15 with Telemecanique. p. 8
  • In high-vibration places, panel mounting gives more stability than a DIN rail. p. 9

Questions this manual answers

What power does the TBX DMS1625 need?

24 VDC nominal (19-30 VDC) between terminals 3 and 1. It draws 125 mA alone and 195 mA with a communications interface. p. 4, 9

Which communication modules fit the TBX DMS1625?

The Class 8030 Type CRM275 DRIO for IO/NET, the TBX LEP020 and TBX LEP030 for FIPIO, and the TBX CBS010 Expansion Interface. p. 3

Does the TBX DMS1625 work with the CRM270?

No. The bulletin says the base unit is not compatible with the Type CRM270 interface module. p. 9

What voltages can the TBX DMS1625 relay outputs switch?

24 VDC nominal (19-30 VDC) or 24-240 VAC, with a maximum surge current of 30 A. p. 4, 5

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. DESCRIPTION3
  2. SPECIFICATIONS4
    1. Base Unit Power4
    2. Inputs4
    3. Outputs4
    4. Environmental and Physical5
    5. Agency Compliance6
    6. BASE UNIT WIRING6
    7. MOUNTING INSTRUCTIONS8
    8. 1. Press down on the base unit.9

From the PDF’s own bookmarks.

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 61-6
  2. Pages 7 to 127-12

The file

Revision and size

RevisionInstruction Bulletin 30598-376-01B1, July 1997
PublisherSquare D (Schneider S.A.)
Pages12
PDF394 KB
TextText from the PDF itself.