For the Square D TBX-DMS1625 and Schneider TBX-DMS1625
Page 1
30598-376-01B1 Text Page 1 Saturday, July 26, 1997 10:12 AM
Instruction Bulletin 30598-376-01B1 July 1997
24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625
User’s Manual
Page 2
30598-376-01B1 Text Page 2 Saturday, July 26, 1997 10:12 AM
WARNING UNINTENTIONAL EQUIPMENT OPERATION To avoid improper handling of equipment: The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter, and apply this product. Failure to observe this instruction can result in death or serious injury.
CAUTION EQUIPMENT DAMAGE HAZARD To avoid improper handling of equipment: 1.
Never remove this device while power is ON.
2.
Do not subject to static discharge. This module contains electronic components that are very susceptible to damage from electrostatic discharge.
Failure to observe this instruction can result in equipment damage.
SY/MAX, SY/NET, SY/LINK, and SY/MATE are registered trademarks of Square D Company. PASSPORT and IO/NET are trademarks of Square D Company.
© 1997 Schneider S.A. All rights reserved. This document may not be copied in whole or in part, or transferred to any other media, without the written permission of Schneider S.A. Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Schneider S.A. for any consequences arising out of the use of this material.
Page 3
30598-376-01B1 Text Page 3 Saturday, July 26, 1997 10:12 AM
Bulletin No. 30598-376-01B1 July 1997
24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625
DESCRIPTION The TBX DMS1625 is a distributed input/output base unit containing eight 24 VDC inputs and digital relay outputs. This base unit may be coupled with a compatible communications interface to form a complete distributed block, which is well suited for the control of discrete field devices located some distance from a host programmable logic controller (PLC). The application of distributed I/O blocks saves installation and maintenance cost, as compared to direct wiring of field devices to a centralized I/O system over long distances. The TBX DMS1625 base unit can be used with either SY/MAX® or Telemecanique PLCs, through the use of a compatible communications interface, or “top hat”. The interface mounts directly on the base unit, and allows the PLC to read and write to the I/O points through a suitable control network. The Class 8030 Type CRM275 Distributed Remote IO/NET™ Interface (DRIO) supports connection to the IO/NET control network as part of the PASSPORT™ I/O System. The TBX LEP020 and TBX LEP030 communications interfaces support connection to the FIPIO network. The TBX CBS010 Expansion Interface allows inexpensive connection of a second TBX base unit to a single communications top hat. The TBX DMS1625 base unit supports the following TBX I/O features: • Eight Input and Eight Relay Output Points - Suitable for use with discrete field devices such as solenoids, contactors and pilot lights. • Output Fallback State Control - Provides point-by-point control over output states when communication is lost. • 24 VDC Logic Power Supply - Converts to proper voltage levels for top hat and for on-board electronics; may be wired independently from input or output power supplies. • Removable Field Wiring Terminal Strip - Mounts securely to the base unit without use of screws or fasteners. This bulletin contains information on the installation and application of the TBX DMS1625 base unit with either SY/MAX or Telemecanique PLCs. For information about programming a SY/MAX PLC for use with the TBX DMS1625 base, refer to the Class 8030 Type CRM275 (DRIO) instruction bulletin (#30598-380). For information about programming a Telemecanique PLC for use with the TBX DMS1625 base, refer to the Telemecanique TBX Distributed I/O Modules manual (TSX DM TBXV52E). Please read and keep all the appropriate manuals close at hand when using TBX base units. The top hats receive +24 VDC from the primary base, which the top hat converts to logic power for the top hat and base units. For additional information on the DRIO Interface and the Expansion Interface, refer to bulletins 30598-380 and 30598-371 respectively. You may use the TBX SUP10 power supply to provide 24 VDC for TBX bases and sensors from an AC source.
© 1997 Schneider S.A. All Rights Reserved
3
Page 4
30598-376-01B1 Text Page 4 Saturday, July 26, 1997 10:12 AM
24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625
Bulletin No. 30598-376-01B1 July 1997
SPECIFICATIONS Base Unit Power Operating voltage:
24 VDC nominal; 19-30 VDC
Operating current at nominal voltage: Configuration
Nominal
Base only
125 mA
Base with comms interface
195 mA
Base, interface and expansion base
310 mA
Inputs Inputs per base unit
8
Number of input commons
8
Isolation rating
1500 V rms between inputs and earth terminal
Voltage operating range
24 VDC nominal; 19-30 VDC
Nominal input current draw
15 mA
Must turn-on voltage
11 VDC
Must turn-on current
6mA
Must turn-off voltage
5 VDC
Maximum turn-on time
15 ms
Maximum turn-off time
17 ms
Control input voltage monitor trip threshold
18 VDC
I/O status indication
Visual indication provided by communications interface; 1 LED per input point
Outputs Outputs per base unit
8
Number of output commons
4
Isolation rating
2000 V from contacts to rest of circuit
Voltage operating range
24 VDC nominal (19-30 VDC); 24-240 VAC
Maximum output load ratings DC: Resistive
24 W (0.3 x 106 operations)
DC: Inductive (L/R = 60 ms)10 W (1 x 106 operations)
4
© 1997 Schneider S.A. All Rights Reserved
Page 5
30598-376-01B1 Text Page 5 Saturday, July 26, 1997 10:12 AM
Bulletin No. 30598-376-01B1 July 1997
24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625
AC: Resistive Load
Voltage
Operations
1A
110/220
0.2 x 106
0.5 A
110/220
2 x 106
1A
24/48
0.5 x 106
2A
24
0.2 x 106
Inductive Load
Voltage
Operations
50 VA
110/220
1 x 106
0.5 A
24/48
1 x 106
10 VA
48/220
1 x 107
1A
24
0.2 x 106
Maximum surge current
30 A
Maximum turn-on time
10 ms
Maximum turn-off time
20 ms
I/O status indication
Visual indication provided by communications interface; 1 LED per point
Output protection
Yes, see “INSTALLATION CONSIDERATIONS” on page 9.
Environmental and Physical Operating temperature rating 0 to 60 °C (32 to 140 °F) Storage temperature rating
-40 to 80 °C (-40 to 176 °F)
Humidity rating
5-95% RH, non-condensing
Dimensions (H x W x D):
See Figure 1
Base unit w/ terminal strip 3.43 x 9.25 x 2.4 in (87 x 235 x 61 mm) Base w/ comms. interface or Base w/ CBS Interface Weight (Base unit only)
3.43 x 9.25 x 2.91 in (87 x 235 x 73.9 mm) 1.3 lb (0.6 kg)
© 1997 Schneider S.A. All Rights Reserved
5
Page 6
30598-376-01B1 Text Page 6 Saturday, July 26, 1997 10:12 AM
24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625
Bulletin No. 30598-376-01B1 July 1997
Agency Compliance
0.24 6.1
Complies with UL508, CSA C22-2 requirements, and FM Class I, Division 2 Hazardous Locations approval requirements.
3.43 87 2.13 54
1.30 33
0.22 5.6
DIN Rail Center Line
40 Position I/O Terminal Strip 8.27 210
9.25 235 in mm
1.6 40.6
61
Top view with DIN rail mounting dimensions
2.4
Dimensions:
8.74 222
Side view Figure 1:
Dimensions
BASE UNIT WIRING Input and output devices are wired to the terminal strip on the top of the base unit. Figure 2 shows the terminal strip pin-out for the base unit. Two terminal strip labels are packaged with the base unit. If you are using the base unit with a SY/MAX system, use the terminal strip labels with I/O numbered from 1-16; if you have a Telemecanique system, use the terminal strip labels with I/O numbered from 0-15. These are both illustrated in Figure 2. The TBX DMS1625 provides separate terminals for base voltage and control output voltage. These terminals may be connected to a common 24 VDC supply or may be sourced by independent supplies (terminals 4 and 1 must be at the same potential).
6
© 1997 Schneider S.A. All Rights Reserved