For the Square D TBX-DMS1625 and Schneider TBX-DMS1625

Page 1

30598-376-01B1 Text Page 1 Saturday, July 26, 1997 10:12 AM

Instruction Bulletin 30598-376-01B1 July 1997

24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625

User’s Manual

Page 2

30598-376-01B1 Text Page 2 Saturday, July 26, 1997 10:12 AM

WARNING UNINTENTIONAL EQUIPMENT OPERATION To avoid improper handling of equipment: The application of this product requires expertise in the design and programming of control systems. Only persons with such expertise should be allowed to program, install, alter, and apply this product. Failure to observe this instruction can result in death or serious injury.

CAUTION EQUIPMENT DAMAGE HAZARD To avoid improper handling of equipment: 1.

Never remove this device while power is ON.

2.

Do not subject to static discharge. This module contains electronic components that are very susceptible to damage from electrostatic discharge.

Failure to observe this instruction can result in equipment damage.

SY/MAX, SY/NET, SY/LINK, and SY/MATE are registered trademarks of Square D Company. PASSPORT and IO/NET are trademarks of Square D Company.

© 1997 Schneider S.A. All rights reserved. This document may not be copied in whole or in part, or transferred to any other media, without the written permission of Schneider S.A. Electrical equipment should be serviced only by qualified electrical maintenance personnel. No responsibility is assumed by Schneider S.A. for any consequences arising out of the use of this material.

Page 3

30598-376-01B1 Text Page 3 Saturday, July 26, 1997 10:12 AM

Bulletin No. 30598-376-01B1 July 1997

24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625

DESCRIPTION The TBX DMS1625 is a distributed input/output base unit containing eight 24 VDC inputs and digital relay outputs. This base unit may be coupled with a compatible communications interface to form a complete distributed block, which is well suited for the control of discrete field devices located some distance from a host programmable logic controller (PLC). The application of distributed I/O blocks saves installation and maintenance cost, as compared to direct wiring of field devices to a centralized I/O system over long distances. The TBX DMS1625 base unit can be used with either SY/MAX® or Telemecanique PLCs, through the use of a compatible communications interface, or “top hat”. The interface mounts directly on the base unit, and allows the PLC to read and write to the I/O points through a suitable control network. The Class 8030 Type CRM275 Distributed Remote IO/NET™ Interface (DRIO) supports connection to the IO/NET control network as part of the PASSPORT™ I/O System. The TBX LEP020 and TBX LEP030 communications interfaces support connection to the FIPIO network. The TBX CBS010 Expansion Interface allows inexpensive connection of a second TBX base unit to a single communications top hat. The TBX DMS1625 base unit supports the following TBX I/O features: • Eight Input and Eight Relay Output Points - Suitable for use with discrete field devices such as solenoids, contactors and pilot lights. • Output Fallback State Control - Provides point-by-point control over output states when communication is lost. • 24 VDC Logic Power Supply - Converts to proper voltage levels for top hat and for on-board electronics; may be wired independently from input or output power supplies. • Removable Field Wiring Terminal Strip - Mounts securely to the base unit without use of screws or fasteners. This bulletin contains information on the installation and application of the TBX DMS1625 base unit with either SY/MAX or Telemecanique PLCs. For information about programming a SY/MAX PLC for use with the TBX DMS1625 base, refer to the Class 8030 Type CRM275 (DRIO) instruction bulletin (#30598-380). For information about programming a Telemecanique PLC for use with the TBX DMS1625 base, refer to the Telemecanique TBX Distributed I/O Modules manual (TSX DM TBXV52E). Please read and keep all the appropriate manuals close at hand when using TBX base units. The top hats receive +24 VDC from the primary base, which the top hat converts to logic power for the top hat and base units. For additional information on the DRIO Interface and the Expansion Interface, refer to bulletins 30598-380 and 30598-371 respectively. You may use the TBX SUP10 power supply to provide 24 VDC for TBX bases and sensors from an AC source.

© 1997 Schneider S.A. All Rights Reserved

3

Page 4

30598-376-01B1 Text Page 4 Saturday, July 26, 1997 10:12 AM

24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625

Bulletin No. 30598-376-01B1 July 1997

SPECIFICATIONS Base Unit Power Operating voltage:

24 VDC nominal; 19-30 VDC

Operating current at nominal voltage: Configuration

Nominal

Base only

125 mA

Base with comms interface

195 mA

Base, interface and expansion base

310 mA

Inputs Inputs per base unit

8

Number of input commons

8

Isolation rating

1500 V rms between inputs and earth terminal

Voltage operating range

24 VDC nominal; 19-30 VDC

Nominal input current draw

15 mA

Must turn-on voltage

11 VDC

Must turn-on current

6mA

Must turn-off voltage

5 VDC

Maximum turn-on time

15 ms

Maximum turn-off time

17 ms

Control input voltage monitor trip threshold

18 VDC

I/O status indication

Visual indication provided by communications interface; 1 LED per input point

Outputs Outputs per base unit

8

Number of output commons

4

Isolation rating

2000 V from contacts to rest of circuit

Voltage operating range

24 VDC nominal (19-30 VDC); 24-240 VAC

Maximum output load ratings DC: Resistive

24 W (0.3 x 106 operations)

DC: Inductive (L/R = 60 ms)10 W (1 x 106 operations)

4

© 1997 Schneider S.A. All Rights Reserved

Page 5

30598-376-01B1 Text Page 5 Saturday, July 26, 1997 10:12 AM

Bulletin No. 30598-376-01B1 July 1997

24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625

AC: Resistive Load

Voltage

Operations

1A

110/220

0.2 x 106

0.5 A

110/220

2 x 106

1A

24/48

0.5 x 106

2A

24

0.2 x 106

Inductive Load

Voltage

Operations

50 VA

110/220

1 x 106

0.5 A

24/48

1 x 106

10 VA

48/220

1 x 107

1A

24

0.2 x 106

Maximum surge current

30 A

Maximum turn-on time

10 ms

Maximum turn-off time

20 ms

I/O status indication

Visual indication provided by communications interface; 1 LED per point

Output protection

Yes, see “INSTALLATION CONSIDERATIONS” on page 9.

Environmental and Physical Operating temperature rating 0 to 60 °C (32 to 140 °F) Storage temperature rating

-40 to 80 °C (-40 to 176 °F)

Humidity rating

5-95% RH, non-condensing

Dimensions (H x W x D):

See Figure 1

Base unit w/ terminal strip 3.43 x 9.25 x 2.4 in (87 x 235 x 61 mm) Base w/ comms. interface or Base w/ CBS Interface Weight (Base unit only)

3.43 x 9.25 x 2.91 in (87 x 235 x 73.9 mm) 1.3 lb (0.6 kg)

© 1997 Schneider S.A. All Rights Reserved

5

Page 6

30598-376-01B1 Text Page 6 Saturday, July 26, 1997 10:12 AM

24 VDC 8 Input/8 Output Relay Base Unit TBX DMS1625

Bulletin No. 30598-376-01B1 July 1997

Agency Compliance

0.24 6.1

Complies with UL508, CSA C22-2 requirements, and FM Class I, Division 2 Hazardous Locations approval requirements.

3.43 87 2.13 54

1.30 33

0.22 5.6

DIN Rail Center Line

40 Position I/O Terminal Strip 8.27 210

9.25 235 in mm

1.6 40.6

61

Top view with DIN rail mounting dimensions

2.4

Dimensions:

8.74 222

Side view Figure 1:

Dimensions

BASE UNIT WIRING Input and output devices are wired to the terminal strip on the top of the base unit. Figure 2 shows the terminal strip pin-out for the base unit. Two terminal strip labels are packaged with the base unit. If you are using the base unit with a SY/MAX system, use the terminal strip labels with I/O numbered from 1-16; if you have a Telemecanique system, use the terminal strip labels with I/O numbered from 0-15. These are both illustrated in Figure 2. The TBX DMS1625 provides separate terminals for base voltage and control output voltage. These terminals may be connected to a common 24 VDC supply or may be sourced by independent supplies (terminals 4 and 1 must be at the same potential).

6