ST96-35.16 Four-stage controller
Manual13 pagesPDF 193 KB
Manual for the ST96-35.16 four-stage temperature controller for compressor groups: wiring, parameters, status messages and technical data.
Covers · 1 model
The models it covers
Summary
What is in it
The manual for the ST96-35.16, a four-stage controller with a Pt100 sensor input, setpoint and actual value display, three keys and four relays, built to control compressor groups of up to four machines. It gives the wiring diagram and panel dimensions, explains the three control levels and every setpoint, P and A parameter (switching differences, hysteresis, alarms, operating time counters, minimum action times and load replacement), lists status and error messages, and ends with technical data.
From the manual · read page by page
Key facts from this manual
Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.
Operating manual for the ST96-35.16 four-stage controller (software .16), a 96 x 96 mm panel controller that switches compressor groups of up to four machines from a Pt100 temperature sensor. It explains the keys and setpoint, the P and A parameter lists, alarms, compressor load balancing, status messages and technical data.
- Device
- Four-stage controller with 3 keys and 4 relays for compressor groups of up to 4 machines p. 1
- Sensor
- Pt100 resistance thermometer (Pt100-3L), -99°C to 300°C p. 1, 13
- Relay outputs
- K1 to K4: normally-open relay, 3(1)A 250V; K5: normally-open relay, 1A 24V p. 13
- Switching input
- E1: external potential-free contact, used to switch to a second setpoint S1' or as an alarm input p. 11, 13
- Power supply
- 230V 50/60Hz p. 13
- Panel size
- Front 96 x 96 mm; panel cut-out 90.5 x 90.5 mm; depth ca. 105 mm with connector p. 13
- Operating modes
- 2, 3 or 4 compressors, with the alarm on the next relay (K3, K4 or K5) p. 8
- Accuracy
- 0.5K +/- 0.5 % of scale range, without sensor p. 13
- Connectors
- Plug and socket for cable up to 1.5 mm² p. 13
- Enclosure
- IP63, for an instrument panel p. 13
- Weight
- ca. 200g without sensor p. 13
- Compressor balancing
- Time-dependent load replacement and sequential operation spread running time across compressors p. 10
- Run-time counters
- Total on-time of each contact K1 to K4 in years and days (P33 to P40) p. 4, 6
- Temperature scale
- Celsius, Fahrenheit or Kelvin (parameter A10) p. 7
What this manual walks you through
- Viewing and changing the main setpoint p. 3
- Setting control parameters (P parameters): switching differences, hysteresis, setpoint limits, alarms p. 4, 5, 6
- Setting boundary or range alarms p. 5
- Opening the third level (A parameters) for relay modes, delays and locks p. 7, 8, 9
- Setting minimum on and off times and start delays for compressors p. 9, 10
- Choosing the operation mode for the number of compressors p. 11
- Reading status messages and LEDs p. 12
- Panel installation and technical data p. 13
Good to know
- A small hysteresis gives tighter control but more frequent switching, which shortens relay life. p. 5
- Changing the temperature scale keeps the numbers, so a 0°C setpoint becomes 0°F. p. 9
- Run times are saved once a day, so up to 24 hours can be lost after a power failure. p. 6
- The operation mode (A44) must match the number of connected loads, or the recorded run times will be wrong. p. 6
Questions this manual answers
What sensor does the ST96-35 controller use?
A Pt100 resistance thermometer (Pt100-3L) with a measuring range of -99°C to 300°C. p. 13
What do F1H and F1L mean on the ST96-35?
Both are sensor errors: F1H is an open circuit and F1L a short circuit; check the sensor. p. 12
How many compressors can the ST96-35 control?
Up to four, with operation modes for 2, 3 or 4 compressors plus an alarm relay. p. 1, 8
What are the ST96-35 relay ratings?
K1 to K4 are normally-open relays rated 3(1)A 250V; K5 is rated 1A 24V. p. 13
What panel cut-out does the ST96-35 need?
90.5 x 90.5 mm, for a 96 x 96 mm front. p. 13