Page 1 of ST96-35.16 Four-stage controller

Manual · Storktronic

ST96-35.16 Four-stage controller

Manual13 pagesPDF 193 KB

Manual for the ST96-35.16 four-stage temperature controller for compressor groups: wiring, parameters, status messages and technical data.

Download the PDF193 KB

Covers · 1 model

The models it covers

Summary

What is in it

The manual for the ST96-35.16, a four-stage controller with a Pt100 sensor input, setpoint and actual value display, three keys and four relays, built to control compressor groups of up to four machines. It gives the wiring diagram and panel dimensions, explains the three control levels and every setpoint, P and A parameter (switching differences, hysteresis, alarms, operating time counters, minimum action times and load replacement), lists status and error messages, and ends with technical data.

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

Operating manual for the ST96-35.16 four-stage controller (software .16), a 96 x 96 mm panel controller that switches compressor groups of up to four machines from a Pt100 temperature sensor. It explains the keys and setpoint, the P and A parameter lists, alarms, compressor load balancing, status messages and technical data.

Device
Four-stage controller with 3 keys and 4 relays for compressor groups of up to 4 machines p. 1
Sensor
Pt100 resistance thermometer (Pt100-3L), -99°C to 300°C p. 1, 13
Relay outputs
K1 to K4: normally-open relay, 3(1)A 250V; K5: normally-open relay, 1A 24V p. 13
Switching input
E1: external potential-free contact, used to switch to a second setpoint S1' or as an alarm input p. 11, 13
Power supply
230V 50/60Hz p. 13
Panel size
Front 96 x 96 mm; panel cut-out 90.5 x 90.5 mm; depth ca. 105 mm with connector p. 13
Operating modes
2, 3 or 4 compressors, with the alarm on the next relay (K3, K4 or K5) p. 8
Accuracy
0.5K +/- 0.5 % of scale range, without sensor p. 13
Connectors
Plug and socket for cable up to 1.5 mm² p. 13
Enclosure
IP63, for an instrument panel p. 13
Weight
ca. 200g without sensor p. 13
Compressor balancing
Time-dependent load replacement and sequential operation spread running time across compressors p. 10
Run-time counters
Total on-time of each contact K1 to K4 in years and days (P33 to P40) p. 4, 6
Temperature scale
Celsius, Fahrenheit or Kelvin (parameter A10) p. 7

What this manual walks you through

  • Viewing and changing the main setpoint p. 3
  • Setting control parameters (P parameters): switching differences, hysteresis, setpoint limits, alarms p. 4, 5, 6
  • Setting boundary or range alarms p. 5
  • Opening the third level (A parameters) for relay modes, delays and locks p. 7, 8, 9
  • Setting minimum on and off times and start delays for compressors p. 9, 10
  • Choosing the operation mode for the number of compressors p. 11
  • Reading status messages and LEDs p. 12
  • Panel installation and technical data p. 13

Good to know

  • A small hysteresis gives tighter control but more frequent switching, which shortens relay life. p. 5
  • Changing the temperature scale keeps the numbers, so a 0°C setpoint becomes 0°F. p. 9
  • Run times are saved once a day, so up to 24 hours can be lost after a power failure. p. 6
  • The operation mode (A44) must match the number of connected loads, or the recorded run times will be wrong. p. 6

Questions this manual answers

What sensor does the ST96-35 controller use?

A Pt100 resistance thermometer (Pt100-3L) with a measuring range of -99°C to 300°C. p. 13

What do F1H and F1L mean on the ST96-35?

Both are sensor errors: F1H is an open circuit and F1L a short circuit; check the sensor. p. 12

How many compressors can the ST96-35 control?

Up to four, with operation modes for 2, 3 or 4 compressors plus an alarm relay. p. 1, 8

What are the ST96-35 relay ratings?

K1 to K4 are normally-open relays rated 3(1)A 250V; K5 is rated 1A 24V. p. 13

What panel cut-out does the ST96-35 need?

90.5 x 90.5 mm, for a 96 x 96 mm front. p. 13

The whole text · 2 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 71-7
  2. Pages 8 to 138-13

The file

Revision and size

RevisionOrder number 900090.002
Pages13
PDF193 KB