The text of a manual · part 2 of 2
ST96-35.16 Four-stage controller, pages 8 to 13
Pages 8 to 13 of 13
The original document is the PDF (193 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Storktronic ST96-35
Page 8
Parameter A24 A25 A26* A27* A30 A31 A32 A33 A34 A40 A41 A42
Function description
Adjustment range
Minimum action time K1 ‘OFF’ Minimum action time K2 ‘OFF’ Minimum action time K3 ‘OFF’ Minimum action time K4 ‘OFF’ Mutual delay of contacts Delay after “Power-on” Alarm suppression after "Power-On" Operating time before time depending load replacement Time scale for parameter A33
0...999 sec. 0...999 sec. 0...999 sec. 0...999 sec. 0...999 sec. 0...999 sec. 0...999 sec.
Standard setting 0 0 0 0 0 0 0
0...999 sec. or min.
240
Time depending load replacement of the compressors Sequential operation mode
A43*
Interlocking of total operating times Function of switching input E1
A44
Operating mode
*
Custom setting
0: seconds 1: minutes 1 0: no load replacement 1: load replacement 1 0: not activated 1: activated 1 0: not locked 1: locked 1 0: no function 0 1: S1’ activated relative to setpoint S1 2: S1’ activated absolute (freely adjustable) 0: 2 compressors K1, K2 alarm at K3 1: 3 compressors K1, K2, K3 alarm at K4 2: 4 compressors K1, K2, K3, K4 2 alarm at K5
If parameter A43 is set to “0” the display will indicate an alarm message in case of closed switching input E1. Outputs K1…K4 will behave like set in parameters A5…A8. An alarm output defined with parameter A44 is not affected.
Page 9
Parameter description: The following values can change the equipment characteristics and are therefore to be set with utmost care. A1: Switch mode K1 A2: Switch mode K2 A3: Switch mode K3 A4: Switch mode K4 The switch mode for the relays, i.e. cooling or heating function, can be programmed independently at works. Heating function means that the contact opens as soon as the setpoint is reached, thus power interruption. At cooling function the contact closes, if the actual value is above the required setpoint. A5: Function of contact K1 at sensor error A6: Function of contact K2 at sensor error A7: Function of contact K3 at sensor error A8: Function of contact K4 at sensor error At sensor error the display indicates “F1-“ (flashing) and the selected relay falls back into the condition pre-set here. A80: Temperature scale Indication can be switched between Fahrenheit, Celsius and Kelvin. At conversion, the parameters and setpoints maintain their numerical value and adjustment range. (Example: A controller with the desired value of 0°C is switched to Fahrenheit. The new desired value is then interpreted as 0°F, which corresponds to a temperature of -18°C). NOTE: Indication limits with °F can be smaller than the actual measuring range! A11: Display mode The value can be indicated with or without decimal point and with or without leading zeros. A12: Alarm mode The alarm exit evaluates an upper and a lower limit value, whereas a selection is possible as to whether the alarm is a boundary or a range alarm. In case of sensor error the following applies: at boundary alarm the relay is on and at range alarm the relay is off. A13: Activation of the alarm The alarm can be deactivated. If activated a flashing display can be set. A19: Parameter lock This parameter enables locking of each parameter level. If third level is locked, only parameter A19 may be changed. A20: Minimum action time contact K1 "On" A21: Minimum action time contact K2 "On" A22: Minimum action time contact K3 "On" A23: Minimum action time contact K4 "On" These parameters permit a delay in switching off the relay in order to reduce the switching frequency. The adjusted time sets the entire minimum time period for a “switched-on” phase. Note: all delays are even effective after switching mains on, after an external error message or after the elimination of sensor errors. If available the Call-LED “C” flashes during the period where the output contacts are suppressed by the adjusted minimum action time.
Page 10
A24: Minimum action time contact K1 "Off" A25: Minimum action time contact K2 "Off " A26: Minimum action time contact K3 "Off " A27: Minimum action time contact K4 "Off " These parameters permit a delay in switching on the relay in order to reduce the switching frequency. The adjusted time sets the entire minimum time period for a “switched-off” phase. Caution: Parameters A3, A4, A7, A8, A22, A23, A26 und A27 are only effective if the corresponding output exists and is activated with A44. A30: Mutual delay of contacts This parameter makes a mutual switching-on delay of relays possible, depending on whichever contact is switched first. It ensures that two output contacts do not switch simultaneously. The mutual delay affects no free contacts that are not involved in the load replacement. With A44=0 the delay is always effective. A31: Delay after “Power-on” This parameter allows a switching-on delay of relays after switching-on the mains voltage. This delay corresponds with the time set here. A mutual delay set by parameter A30 becomes effective as soon as the first contact is switched on. A32: Alarm suppression after "Power-On" This parameter allows a switching-on delay of the alarm contact after switching on the mains voltage. This delay corresponds with the time set here. This suppression does not apply to sensor error alarm or, if activated, external alarms. A33: Operating time before time depending load replacement Load replacement depending on time is mainly used in the field of refrigeration technology to balance the use of the connected compressors. If only some of the outputs are continuously active, outputs that have not yet been activated will be used. This parameter determines the time to elapse before outputs are changed for the first time. If available the Replace-LED “R” lights up as soon as the first replacement occurs and signals the continuous operation of some of the outputs in power stages below 100%. The LED goes out if power stage 0% or 100% is reached and no more load replacement is possible. A34: Operating time range If operating mode with time-dependent load replacement is activated these time ranges are available for parameter A33. A40: Activation of time-dependent load replacement This parameter either activates or deactivates time-dependent load replacement to balance the use of the connected compressors. The replacement takes place after the operating time set with parameter A33. A41: Sequential operation mode This parameter either activates or deactivates the sequential operation mode. If this mode is activated different compressors will be activated or deactivated (if possible) at each change of output stage to ensure an even load of the compressors. Concerning the switching of the compressors the following applies: It several compressors are activated the first started unit will be deactivated first. It several units are deactivated the first stopped unit will be activated first. Note: The time-dependent load replacement and the sequential operation mode only make sense if there is a control circuit with several components of the same power.
Page 11
A42: Interlocking of total operating times This parameter releases the locking of the total operating times in parameters P33-P40. The adjustment of time values resulting from time registration is only necessary for updating purposes when plant components are replaces. A43: Adjustment of setpoint S1‘ (not available on all types of controllers) By closing switching input E1, setpoint S1 can be switched to a setpoint S1’. Setpoint S1’ can be either relative to setpoint S1 or an independent, freely adjustable, control setting. The setpoint S1’ can only be accessed if input E1 is closed. If setpoint S1’ is deactivated and the switching input is closed, the display indicates “FEH” or “FEHL” and the output relays fall back in the condition set with parameters A5-A8. This setting does not effect an alarm output. A44: Operation mode The control program is intended for a maximum of four regulating output contacts plus one alarm contact. In this case 5 power stages with 0%, 25%, 50%, 75% and 100% are available. If less output contacts are available the operation mode can be adjusted with this parameter, namely for four power stages with 0%. 33%, 66% and 100% or for three power stages with 0%, 50% and 100% (with additional alarm contact each). A change of the operation mode may also be considered if the system has to be operated with a different number of controlling components. The contact following the last controlling output is always the alarm contact.
Page 12
Status messages Message
Cause
Error elimination
F1H
Sensor error, open circuit
Check sensor
F1L
Sensor error, short circuit
Check sensor
FEHL
Closed switching input while setpoint S1’ is deactivated Key lock see parameter P19 and/or A19
___ Flashing display EP
Temperature alarm
LED "C" flashes during a minimum action time, if a switching request is executed. Example: A20=20, K1 is switched on, LED “C” flashes for 20 seconds..
LED "R" flashes as soon as the first compressor is replaced in sequential operation mode. As a compressor replacement occurs only in partial load operation (25%-75%) the LED don’t flash in power stage 0% and 100%.
LED "S" lights up if the switching input is closed. Depending on parameter A43 it has different functions: A43=0: alarm function A43=1 or A43=2: if switching input is closed, a new main setpoint is effective that can be adjusted by the SET key. The LED lights up if the switching input is closed and also enabled with parameter A43=1 or 2.
Data loss at parameter memory
If error cannot be eliminated by switching on/off, the controller must be repaired
Page 13
Technical data of ST96-35.16 Input E1: External potential-free switching contact Measuring input F1: Resistance thermometer Pt100-3L Measuring range: -99°C...300°C Measuring accuracy: 0.5K +/- 0.5 % of scale range, without sensor Outputs K1: Relay, normally-open contact, 3(1)A 250V K2: Relay, normally-open contact, 3(1)A 250V K3: Relay, normally-open contact, 3(1)A 250V K4: Relay, normally-open contact, 3(1)A 250V K5: Relay, normally-open contact, 1A 24V Display One 3-digit LED-Display, height 13mm, for temperature display, colour red One 4-digit LED-Display, height 10 mm, colour red 7 LEDs, diameter 3mm, for status display Power supply 230V 50/60Hz Ambient conditions: Storage temperature: Operating temperature: Relative humidity:
-20...+70°C 0...+55°C max. 75% without dew
Weight ca. 200g, without sensor Connectors Plug and socket for cable up to 1.5 mm² Enclosure IP63 Installation data Unit is to be installed in an instrument panel. Front size: 96 x 96 mm Panel cut-out: 90.5 x 90.5 mm Installation depth: ca. 105 mm with connector
Order No.: 152652