For the Storktronic ST96-35
Page 1
ST96-35.16 Four-stage controller Order number 900090.002
Wiring diagram
Product description The four-stage controller with 4-digit setpoint and actual value display, 3 keys and 4 relays was developed for the control of compressor groups of up to 4 machines. The switching exits can be programmed as thermostat controllers with additional protection times for the compressor. The switching input E1 allows change-over of the setpoint. The general functions which can be freely parametered open the way for a broad application area. Sensor: Pt100 Range: -99...300◦ C Front size: 96mm x 96mm Panel cut-out: 90.5mm x 90.5mm Connector: plug and socket
Page 2
ST 96...
82
96
06 g xew
90,5
96
&%
SOL
Page 3
SOFTWARE .16 Adjustment options Key UP Pressing this key you can increase the parameter or parameter value or scroll the parameter list.
Key DOWN Pressing this key you can decrease the parameter or parameter value or scroll the parameter list. At alarm the buzzer function can be switched off with this key. Key SET While SET key is pressed, the setpoint is indicated. In addition, the SET key is used for setting parameters.
First control level: Parameter setting of the main setpoint If none of the keys is pressed, the display indicates the actual value of the temperature. Pressing the SET key, the setpoint shows on the display. If the setpoint is to be changed, the SET key is to be kept pressed while adjusting the setpoint with the keys UP and DOWN. Please note that the setpoint can only be changed within the set setpoint limits
Parameter S1
Function description
Adjustment range
Setpoint
P12...P13
Standard setting 0.0°C
Custom setting
Page 4
Second control level (P parameters): Setting of control parameters Simultaneously pressing the UP and DOWN key for at least 4 seconds opens a parameter list containing control parameters. With the UP and DOWN keys the list can be scrolled in both directions. Pressing the SET key will give you the value of the respective parameter. Pressing also the UP or DOWN key at the same time the value can be adjusted. Return to the initial position takes place automatically, if no key is pressed for 60 seconds Parameter P1 P2* P3* P6** P7** P8** P9** P12 P13 P19 P20 P21 P30 P31 P32** P33*** P34*** P35*** P36*** P37*/*** P38*/*** P39*/*** P40*/***
Function description
Adjustment range
Delta W1 Delta W2 Delta W3 Hysteresis K1 Hysteresis K2 Hysteresis K3 Hysteresis K4 Control range limitation – minimum setpoint Control range limitation – maximum setpoint Key-lock
-99 ... 99.0 K -99 ... 99.0 K -99 ... 99.0 K 0.1 ... 99.0 K 0.1 ... 99.0 K 0.1 ... 99.0 K 0.1 ... 99.0 K -99 ... 999°C
Standard setting 10.0 K 20.0 K 30.0 K 1.0 K 1.0 K 1.0 K 1.0 K -99°C
-99 ... 999°C
999°C
0: no key-lock 1: key-lock N/A -10...+10 K -99...999°C -99...999°C 0.1...99.0 K 0 ... 25 years
0
0.0 K -99°C 999°C 1.0 K 0
0 ... 364 days
0
0 ... 25 years
0
0 ... 364 days
0
0 ... 25 years
0
0 ... 364 days
0
0 ... 25 years
0
0 ... 364 days
0
Indication actual value 1 Actual value correction Lower alarm value Upper alarm value Alarm hysteresis Total operating time contact K1 in years Total operating time contact K1 in days Total operating time contact K2 in years Total operating time contact K2 in days Total operating time contact K3 in years Total operating time contact K3 in days Total operating time contact K4 in years Total operating time contact K4 in days
Custom setting
* Some parameters are only effective if the corresponding outputs exist. ** The Hysterese is set symmetrically on the switching points. *** To delete or change the operating times P33-P34 parameter A42 must be set to “0”.
Page 5
Parameter description: P1-P3: Delta W1-W3 Main contact K1 and secondary contact K2 (K3, K4) are linked with one another via switching difference Delta W1 (W2, W3). This difference can take positive or negative values. Thus, a leading or following contact can be realised. In this configuration the controller can be also used as three-point controller. Note: Parameters P2 and P3 are only effective if the corresponding output exists and is included with parameter A44. P6-P9: Hysterese K1-K4 The hysteresis can be adjusted separately for all contacts and is set symmetrically at the setpoints, i.e. half of the hysteresis’ value is effective below and half of the value above the switching point. Note that a small hysteresis permits a more exact regulation, however also leads to more frequent switching frequency decreasing the lifetime of the relay. Under critical conditions the controller can be equipped with a semiconductor relay. Note: Parameters P8 and P9 are only effective if the corresponding output exists and is included with parameter A44. P12: Control range limitation – minimum setpoint P13: Control range limitation – maximum setpoint The adjustment range of the setpoint 1 can be limited in both directions. This is to prevent the end user of a unit from setting inadmissible or dangerous setpoints. P20: Actual value The here indicated temperature presents the actual measured value. P21: Actual value correction This parameter allows the correction of actual value deviations caused for example by sensor tolerances or extremely long sensor lines. The regulation measure value is increased or decreased by the here adjusted value. P30: Lower alarm value P31: Upper alarm value The exit alarm is a boundary alarm or a range alarm with adjustable hysteresis (see parameter P32). The required output contact is set with the operation mode selected with parameter A44. If boundary alarm is selected and only one switching point is required, you have to set the second switching point to a value above or below the operating range of the controller. Boundary alarm function (see fig. 1): The alarm contact is closed if the process temperature is above the upper or below the lower boundary value.
Range alarm function (see fig. 2): Opposite switching behaviour to the boundary value alarm. The alarm contact is closed if the actual value remains between the boundary values.
Fig. 1: Boundary alarm, rel. boundaries
Fig. 2: Range alarm, abs. boundaries
Page 6
P32: Alarm hysteresis Hysteresis is set symmetrically at the adjusted limit value. It becomes effective depending on alarm definition. The operating time recorded by parameters P33-P44 is mainly used in the field of refrigeration technology to register the operating time of the connected compressors. P33: Total operating time contact K1 in years P35: Total operating time contact K2 in years P37: Total operating time contact K3 in years P39: Total operating time contact K4 in years These parameters indicate the total operating times in years elapsed with the respective contact switched on. P34: Total operating time contact K1 in days P36: Total operating time contact K2 in days P38: Total operating time contact K3 in days P40: Total operating time contact K4 in days These parameters indicate the remaining total operating times in days elapsed with the respective contact switched on. Note: Time is recorded in minute cycles. Periods shorter than one minute are ignored. Storage in the non-volatile memory takes place daily, so that an inaccuracy of max. 24 hours may result if a power failure occurs. Caution: Parameters P37-P40 are only effective when the pertinent output is available and activated by parameter A44. To avoid statistical errors, it is essential that the operating mode set in parameter 44 corresponds to the number of external loads (e.g. compressors) that are connected. Failure to do this will result in incorrect operating times being recorded by parameter P33-P44. Operating times can be updated after replacement of components only if parameters P19 and A19 are unlocked together with parameter A42. Otherwise data can be irretrievable lost.
Page 7
Third control level, (A parameters): Setting of control parameters Access to the third control level is granted when selecting the last P-parameter on the second control level. Continue to press the UP key for approximately 10 seconds until “PA” appears. Continue to press the UP key and additionally press the DOWN key for about 4 seconds and the first A-parameter of the third control level is indicated. With the keys UP and DOWN you can scroll the list in both directions. Pressing the SET key will give you the value of the respective parameter. By pressing the UP or DOWN key at the same time the value can be adjusted. Return to the initial position takes place automatically, if no key is pressed for 60 seconds, or by simultaneously pressing the UP and DOWN key for approx. 4 seconds. Parameter A1
Function description
Adjustment range
Switch mode K1
A2
Switch mode K2
0: heating contact 1: cooling contact 0: heating contact 1: cooling contact 0: heating contact 1: cooling contact 0: heating contact 1: cooling contact 0: relay off 1: relay on 0: relay off 1: relay on 0: relay off 1: relay on 0: relay off 1: relay on 0: Celsius 1: Fahrenheit 2: Kelvin 0: without decimal point, without leading zeros 1: with decimal point, without leading zeros 2: without decimal point, with leading zeros 3: with decimal point, with leading zeros 0: Boundary alarm 1: Range alarm 0: not active 1: active, no flashing display 2: active, flashing display 0: no lock 1: A-parameter locked 2: A- and P-parameter locked 0...999 sec. 0...999 sec. 0...999 sec. 0...999 sec.
A3
Switch mode K3
A4
Switch mode K4
A5
A10
Function of contact K1 at sensor error Function of contact K2 at sensor error Function of contact K3 at sensor error Function of contact K4 at sensor error Temperature scale
A11
Display mode
A6 A7 A8
A12
Alarm mode
A13
Activation of alarm output
A19
Parameter lock
A20 A21 A22 A23
Minimum action time K1 ‘ON’ Minimum action time K2 ‘ON’ Minimum action time K3 ‘ON’ Minimum action time K4 ‘ON’
Standard setting 1 1 1 1 0 0 0 0 0
1
0
1 0
0 0 0 0
Custom setting