For the Telemecanique Altistart 48 ATS48

Page 1 read from a scan by OCR; it may hold reading errors

ALTISTART® 48 Soft Start Taming Energy

Catalogue

September

Schneider

= Electric Building a New Electric World

Page 2

ALTISTART® 48 Soft Start Introduction Presentation

CONTENTS Description Page Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 Technical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-11 Voltage References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-13 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 POWERSUITE® Advanced Dialog Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-16 Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17-18 Mounting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19-20 Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21-24 Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26-33 Conventional Starting Curves. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34-35

AC Line Supply

Motor

2

© 2002 Schneider Electric All Rights Reserved

09/02

Page 3

ALTISTART® 48 Soft Start Introduction Presentation

Applications The ATS48 Soft Start is a controller with 6 thyristors. It is used for the torque-controlled soft starting and stopping of three-phase squirrel cage asynchronous motors in the power range between 3 and 1200 hp. It offers soft starting and deceleration functions along with machine and motor protection functions as well as functions for communicating with control systems. These functions are designed for use in state-of-theart applications in centrifugal machines, pumps, fans, compressors and conveyors, which are primarily used in the construction, food and beverages and chemical industries. The high-performance algorithms of the ATS48 controller contribute significantly to its robustness and ease of setup. The ATS48 controller is a cost-effective solution which can: • Reduce machine operating costs by reducing mechanical stress and improving machine availability • Reduce the stress placed on the electrical distribution system by reducing line current peaks and voltage drops during motor starts The ATS48 controller is rated for three-phase voltages 208 to 690 V, 50/60 Hz and are dimensioned for standard and severe duty applications. Functions The ATS48 controller is supplied ready for use in a standard duty application with Class 10 motor thermal overload protection. All devices include a built-in keypad display which can be used to modify programming, adjustment or monitoring functions in order to adapt and customize the application to meet individual customer requirements. Soft Start performance functions: • Exclusive torque control system (patented by Schneider Electric) • Constant control of the torque supplied to the motor during acceleration and deceleration periods (significantly reducing pressure surges)

• Adjustments for ramp and the starting torque • The starter can be bypassed using a contactor at the end of the starting period while maintaining electronic overload protection (bypass function) • Wider frequency tolerance for generator set (source) power supplies

Machine and motor protection functions: • Built-in motor thermal overload protection

• Monitoring of the starting time

• Processing of information from PTC thermal probes

• Protection against underloads and overcurrents during continuous operation

Extended I/O functions for integration into control systems: • 4 logic inputs, 2 logic outputs, 3 relay • Display of electrical values, running conditions and outputs and 1 analog output operating time • Pull-apart terminal connectors

• RS-485 serial link for connection to ® • Function for configuring a second set of motor MODBUS System parameters and easy-to-adapt settings Options A remote keypad display can be mounted on the door of a wall-mounted or floor-standing enclosure. POWERSUITE® advanced dialog solutions: • POWERSUITE® Pocket PC/PDA with PPC • A range of wiring accessories for connecting the type terminal. starter to PLCs via a MODBUS® Systems connection. • POWERSUITE® software workshop. (Version 1.30, build 5 or higher)

Characteristics: pages 4 to 7

09/02

• Bus communication and Ethernet, FIPIO®, DEVICENET™ and PROFIBUS® DP network communication options.

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

3

Page 4

ALTISTART® 48 Soft Start Technical Characteristics Technical Characteristics

Environment The electronic starters have been developed and performance tested in accordance with international standards, in particular with the starter product standard EN/IEC 60947-4-2.

Conformity to standards e marking

Products have CE marking in accordance with the harmonized standard EN/IEC 60947-4-2. UL, CSA Pending: DNV, C-Tick, Ghost, CCIB

Product approvals Degree of protection Vibration resistance Shock resistance

Starter noise level (2)

Fans

Ambient temperature around the unit

Maximum relative humidity

Starters ATS48D17Y to 48C11Y

IP 20 (IP 00 in the absence of connections)

Starters ATS48C14Y to 48M12Y (1)

IP 00

Conforming to IEC 60068-2-6

1.5 mm from 2 to 13 Hz 1 g from 13 to 200 Hz

Conforming to IEC 60068-2-27

15 g for 11 ms

Starters ATS48D32Y to D47Y dBA

52

Starters ATS48D62Y to C11Y dBA

58

Starters ATS48C14Y to C17Y dBA

50

Starters ATS48C21Y to C32Y dBA

54

Starters ATS48C41Y to C66Y dBA

55

Starters ATS48C79Y to M12Y dBA

60

Starters ATS48D17Y and D22Y

Natural convection

Starters ATS48D32Y to M12Y

Forced convection. The fans are activated automatically when a temperature threshold is reached. For flow rate see page 20.

Operation

14 to 104 ˚F (-10 to 40 ˚C) without derating Up to 140 ˚F (60 ˚C), derate the current by 2% for each ˚C above 40 ˚C 14 to 122 ˚F (-10 to 50 ˚C) with user supplied shorting/bypass contactor

Storage, conforming to IEC 60947-4-2

-13 to 158 ˚F (- 25 to 70 ˚C)

Conforming to IEC 60068-2-3

95% without condensation or dripping water

Maximum ambient pollution Conforming to IEC 60664-1 Maximum operating altitude

Level 3 ft (m)

3300 ft (1000 m) without derating [above this, derate the nominal current of the ALTISTART by 2.2% for each additional 330 ft (100 m)] to a maximum of 6600 ft (2000 m).

Operating position Maximum permanent angle in relation to the normal vertical mounting position

Electrical characteristics Operating category

Conforming to IEC 60947-4-2

Three-phase supply voltage

Starters ATS48pppY

Frequency

208 - 15% to 690 + 10%

Hz

50/60 ± 5% (automatic) 50 or 60 ± 20% (must be set)

Nominal starter current

Starters ATS48pppY

A

17 to 1200

SCRs

Starters ATS48pppY

PIV

1800

Motor power

Starters ATS48pppY kW/HP 5.5 to 900/5 to 1200

Voltage indicated on the motor rating plate

Starters ATS48pppY

V

208 to 690

Starter control circuit supply Starters ATS48pppY voltage

V

110 - 15% to 230 + 10%, 50/60 Hz

Starters ATS48D17Y to C17Y

W

30

Starters ATS48C21Y to C32Y

W

50

Starters ATS48C41Y to M12Y

W

80

Maximum control circuit consumption (with fans operating)

Relay output (2 configurable outputs)

(1) (2)

3 relay outputs (R1, R2, R3), normally open contacts 1"N/O" Minimum switching capacity: 10 mA for 6 Vdc. Maximum switching capacity on inductive load: 1.8 A for 230 Vac and 30 Vdc (power factor= 0.5 and L/R=20 ms). Maximum nominal operating voltage 400 Vac. Factory setting: R1 assigned as the "fault relay" (configurable) R2 assigned as the "end of starting relay" to control the starter bypass relay R3 assigned as "motor powered" (configurable)

Protective covers can be fitted to the power terminals of ATS48C14Y to C32Y starters. ATS48C41Y to 48M12Y starters have protection on the front panel and on the sides. Starters located 3 ft. (1 m) away. The noise levels may change depending on the characteristics of the fans.

Characteristics: pages 4 to 7

4

AC-53a V

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

09/02

Page 5

ALTISTART® 48 Soft Start Technical Characteristics Technical Characteristics

Electrical characteristics (continued) Logic inputs LI (2 configurable inputs)

4 logic inputs, impedance 4.3 kΩ, isolated: Stop, Run, LI3, LI4. + 24 V power supply (maximum 30 V) I max. 8 mA State 0 if U < 5 V and I < 2 mA State 1 if U > 11 V and I > 5 mA

Internal source available

One 24 V output, isolated and protected against short-circuits and overloads. Accuracy ± 25%. Max. current 200 mA.

Logic outputs LO (configurable)

2 logic outputs LO1 and LO2 with 0 V common, compatible with level 1 PLC, according to standard IEC 65A-68. + 24 V power supply (minimum: +12 V, maximum: + 30 V). Maximum output current: 200 mA if supplied externally

Analog output AO (configurable)

Current output 0-20 mA or 4-20 mA Maximum load impedance: 500 Ω Accuracy ± 5% of the maximum value

Input for PTC probe

Total resistance of probe circuit 750 Ω at 25˚C, according to IEC 60 738-A

Maximum I/O connection capacity

12 AWG (2.5 mm2)

Communication

RS-485 multidrop serial link integrated in the starter, for MODBUS® Systems, with RJ45 type connector Transmission speed 4800, 9600 or 19200 bps Maximum number of ATS48 controller’s connected: 18 Other uses: - connection to a remote keypad display or - connection to a PC or - connection to other buses and networks via communication options.

Protection

Thermal

Built-in, starter and motor (calculated and/or thermal protection with PTC probes)

Line protection

Phase failure, indicated by output relay The nominal motor current In can be adjusted from 0.4 to 1.3 times the starter nominal current. Adjustment of the maximum starting current from 1.5 to 7 times the motor In, limited to 5 times the starter nominal current.

Current settings

Starting mode

Stopping mode

By torque control with starter current limited to 5 In maximum. Factory setting: 4 In for standard operation on 15 s torque ramp Freewheel stop

"Freewheel" stop (factory setting)

Controlled stop on torque ramp

Programmed between 0.5 and 60 s (for pump applications)

Braked stop

Controlled dynamically by the flux

Electromagnetic compatibility EMC (1)

Summary of immunity tests carried out with the ATS48 Soft Start

Standards

Test levels

Examples (sources of interference)

IEC 61000-4-2 level 3 Electrostatic discharge: - by contact - in the air

6 kV 8 kV

Contact off an electrically charged individual

IEC 61000-4-3 level 3 Radiated electromagnetic fields

10 V/m

Equipment transmitting radio frequencies

IEC 61000-4-4 level 4 Rapid electrical transients: - power supply cables - control cables

4 kV 2 kV

Opening/closing of a contactor

IEC 61000-4-5 level 3 Shock wave: - phase/phase - phase/ground

1 kV 2 kV

-

IEC 61000-4-12 level 3 Damped oscillating waves

1 kV - 1 M Hz

Oscillating circuit on the line supply

According to IEC 60947-4-2, class A, on all starters Radiated and conducted emissions (1)

According to IEC 60947-4-2, class B, on starters up to 170 A: ATS48D17p to 48C17p. Must be bypassed at the end of starting

The starters conform to IEC 60947-4-2 (EMC). This standard ensures a level of immunity for products and a level of emitted interference. In steady state, the interference emitted is below that required by the standard.

NOTE: • Power factor correction capacitors can only be used upstream of the ALTISTART and only powered up at the end of starting. • The starter must be grounded to conform to the regulations concerning leakage currents (≤ 30 mA). If the installation involves several starters on the same line supply, each starter must be grounded separately. Characteristics: pages 4 to 7

09/02

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

5

Page 6

ALTISTART® 48 Soft Start Technical Characteristics Technical Characteristics

TORQUE CHARACTERISTICS Curves indicating changes in the torque depending on the starting current of a three-phase asynchronous motor. Curves 1: full voltage starting Curves 2: starting in current limiting mode Torque curve Ts1 indicates the total torque range available depending on the limiting current Is1. Limiting the starting current Is to a preset value Is1 will reduce the starting torque Ts1 to a value which is almost equal to the square of currents Is1/Is. Example: For motor characteristics: Ts = 3 Tn for Is = 6 In, limit the current to Is1 = 3 In (0.5 Is) resulting in a starting torque Ts1 = Ts x (0.5)∑ = 3 Tn x 0.25 = 0.75 Tn

STARTING CURRENT 1) Full voltage starting current 2) Starting current limited to Is1

I/In 6

5

1

4

2

Id1

3

2

1

0 0

0.25

0.5

0.75

1 N/Ns

STARTING TORQUE TS1 1) Full voltage starting torque 2) Starting torque with current limited to Is1

C/Cn 6

5

4

1 3

2 2 Cr Cd1 1

0 0

0.25

Characteristics: pages 4 to 7

6

0.5

0.75

1 N/Ns

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

09/02

Page 7

ALTISTART® 48 Soft Start Technical Characteristics Technical Characteristics

CONVENTIONAL STARTING USING CURRENT LIMITATION OR VOLTAGE RAMP I/In 4

N/Ns 1

1 3

2

0.5

2

With current limitation Is1, the accelerating torque applied to the motor is equal to the motor torque Ts1 minus the resistive torque Tr. The accelerating torque increases in the starting range as the speed changes and is at its highest at the end of acceleration (curve 2). This characteristic means that the load is taken up very abruptly, which is not recommended for pump type applications. Example of speed curve for starting with current limitation 1) Current applied to the motor (I/In) 2) Motor speed N/Ns

1

0 t

STARTING WITH THE ATS48 SOFT START I/In 4

N/Ns 1

3

1

2

0.5

2

Torque control on the ATS48 controller applies the torque to the motor during the entire starting phase if the current required (curve 1) does not exceed the limiting current. The accelerating torque can be virtually constant over the entire speed range (curve 2). It is possible to set the ALTISTART in order to obtain a high torque on starting for a rapid motor speed rise while limiting its temperature rise, and a lower accelerating torque at the end of starting for gradual loading. This control function is ideal for centrifugal pumps or for machines with high resistive torque on starting.

1

Example of speed curve for starting with torque control 0 t

1) Current applied to the motor (I/In) 2) Motor speed N/Ns

STOPPING WITH THE ATS48 SOFT START • Freewheel stop: the motor comes to a freewheel stop. • Decelerated stop: this type of stop is ideal for pumps and can be used to effectively reduce pressure surges. Torque control on the ATS48 controller reduces the effect of hydraulic transients even if the load increases. This type of control makes adjustment easy. • Braked stop: this type of stop is suitable for high inertia applications because it reduces the stopping time of the machine.

Characteristics: pages 4 to 7

09/02

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

7

Page 8

ALTISTART® 48 Soft Start Selection Selection

SELECTION CRITERIA FOR AN ATS48 SOFT START UNIT The ATS48 controller must be selected on the basis of 3 main criteria: • Low voltage power supply range acceptable for selection:, Three-phase AC voltage: 208 - 690 V • The power and the nominal current (motor FLA) indicated on the motor nameplate • The type of application and the operating cycle: To simplify selection, the applications are categorized as 2 types:, Standard duty applications, Severe duty applications Standard or severe duty applications define the limiting values of the current and the duty cycle ratings. Standard duty application In standard duty applications, the ATS48 controller is designed to provide: • Starting at 4x In for 23 seconds or at 3x In for 46 seconds from a cold state • Starting at 3x In for 23 seconds or at 4x In for 12 seconds with a load factor of 50% and 10 starts per hour or an equivalent thermal cycling The motor thermal protection conforms to Class 10 overload protection (see page 28). Example: Centrifugal pump Severe duty application In severe duty applications, the ATS48 controller is designed to provide: • Starting at 4x In for 48 seconds or at 3x In for 90 seconds from a cold state • Starting at 4x In for 25 seconds with a load factor of 50% and 5 starts per hour or an equivalent thermal cycling The motor thermal protection conforms to Class 20 overload protection (see page 28). Example: Grinder Selecting the starter Once the appropriate application has been selected from the following page, select the starter from pages 12 to 13 according to the supply voltage and the motor power. Caution: If the ATS48 Soft Start is installed inside an enclosure, observe the mounting and derating recommendations (see pages 19 to 20).

8

© 2002 Schneider Electric All Rights Reserved

09/02

Page 9

ALTISTART® 48 Soft Start Selection Selection Criteria

APPLICATION AREAS Depending on the type of machine, the applications are categorized as standard or severe duty based on the starting characteristics, which are given by example, in the table below.

09/02

Type of machine

Application

Functions performed by the ATS48 Controller

Centrifugal pump

Standard

Deceleration (reduction in pressure surges) Protection against underloads or inversion of the phase 300 rotation direction

5 to 15

Piston pump

Standard

Control of running dry and direction of rotation of the pump

350

5 to 10

Fan

Standard Severe if > 30 s

Detection of overloads caused by clogging or underloads (motor fan transmission broken) Braking torque on 300 stopping

10 to 40

Cold compressor

Standard

Protection, even for special motors

300

5 to 10

Screw compressor

Standard

Protection against inversion of direction of phase rotation 300 Contact for automatic draining on stopping

3 to 20

Centrifugal compressor

Standard Severe if > 30 s

Protection against inversion of direction of phase rotation 350 Contact for automatic emptying on stopping

10 to 40

Piston compressor

Standard

Protection against inversion of direction of phase rotation 350 Contact for automatic emptying on stopping

5 to 10

Conveyor, transporter

Standard

Overload control for detecting faults or underload control 300 for detecting breaks

3 to 10

Lifting screw

Standard

Overload control for detecting hard spots or underload control for detecting breaks

300

3 to 10

Drag lift

Standard

Overload control for detecting jamming or underload control for detecting breaks

400

2 to 10

Lift

Standard

Overload control for detecting jamming or underload control for detecting breaks Constant starting with variable load

350

5 to 10

Circular saw, band saw

Standard Severe if > 30 s

Braking for fast stop

300

10 to 60

Pulper, butchery knife

Severe

Torque control on starting

400

3 to 10

Agitator

Standard

The current display indicates the density of the product

350

5 to 20

Mixer

Standard

The current display indicates the density of the product

350

5 to 10

Grinder

Severe

Braking to limit vibrations during stopping, overload control to detect jamming

450

5 to 60

Crusher

Severe

Braking to limit vibrations during stopping, overload control to detect jamming

400

10 to 40

Refiner

Standard

Torque control on starting and stopping

300

5 to 30

Press

Severe

Braking to increase the number of cycles

400

20 to 60

© 2002 Schneider Electric All Rights Reserved

Starting current Starting time (% In) (s)

9