The text of a manual · part 2 of 4
ALTISTART 48 Soft Start Catalogue, pages 10 to 18
Pages 10 to 18 of 36
The original document is the PDF (3.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Telemecanique Altistart 48 ATS48
Page 10
ALTISTART® 48 Soft Start Selection Selection Criteria
SPECIAL USES Other criteria can influence the selection of the ATS48 controller: Shorting/Bypass contactor Refer to the recommended wiring diagrams on pages 21 to 24. The starter can be bypassed by a contactor at the end of starting (to limit the heat dissipated by the starter). The shorting/bypass contactor is controlled by the starter and the current measurements and thermal protection remains active when the starter is bypassed. Multi Motors Motors may be connected in parallel provided that the power limit of the starter is not exceeded (the sum of the motor currents must not exceed the nominal current of the starter selected depending on the type of application). Individual thermal protection is required for each motor. Brush motor The ATS48 controller can operate with a bypassed stator resistance motor or with a resistance lug. The starting torque is modified in accordance with the rotor resistance. If necessary, maintain a low resistance in order to obtain the required torque to overcome the resistive torque on starting. A bypassed brush motor has a very low starting torque. A high stator current is required to obtain the sufficient starting torque. Oversize the starter in order that the value of the limiting current is 7 times that of the nominal current. NOTE: Ensure that the starting torque of the motor, equal to 7 times the nominal current, is greater than the resistive torque. NOTE: The ATS48 Soft Start torque control enables excellent soft starting despite the limiting current being 7 times the nominal current required to start the motor. 2-speed motor The ATS48 controller can operate with a 2-speed motor. A motor demagnetization period must elapse before changing from low speed to high speed in order to avoid antiphase between the line supply and the motor, which would generate very high currents. Select the starter using the 3 main criteria, see page 8. Long motor cable lengths Very long motor cables cause voltage drops due to the resistance of the cable. If the voltage drop is significant, it could affect the current consumption and the torque available. This criteria must be taken into account when selecting the motor and the starter. Miscellaneous application precautions Note: Do not use the ATS48 controller upstream of loads other than motors (for example transformers and resistors type loads). Do not connect power factor correction capacitors to the terminals of a motor controlled by an ATS48 Soft Start.
10
© 2002 Schneider Electric All Rights Reserved
09/02
Page 11
ALTISTART® 48 Soft Start Selection Selection
PRESENTATION The ATS48 controller can be connected directly to the MODBUS® System using an RJ45 connector and communicates using the RS-485 serial link (2-wire) and the MODBUS® Systems RTU protocol. The communication function provides access to the configuration, adjustment, control and signalling functions of the starter. Premium
1. MODBUS® Systems cable TSXSCAp00 1
3
2
2. Junction box TSXSCA50 3. Subscriber sockets TSXSCA62
4
4. MODBUS® Systems drop cable VW3A8306
5
5. MODBUS® Systems drop cable VW3A8306D30
ATS48
ATS48
ATS48
ATS48
ATS48
1. Communication module 2. MODBUS® Systems hub LU9GC3 3. MODBUS® Systems drop cable VW3A8306Rpp 3 6 2
4. Line terminator VW3A8306RC 5. MODBUS® Systems T-junction box VW3A8306TF3
5
4
1
6. To other buses or networks 4
The ATS48 controller can be connected to other buses or networks using the communication modules and accessories below.
174CEV30010
Communication modules
Cables to be connected
Catalog number Weight lb (kg)
Ethernet/MODBUS® Systems bridge with 1 x Ethernet 10baseT port (RJ45 type)
To be connected using cable VW3P10306R10
174CEV30010
1.10 (0.50)
FIPIO®/MODBUS® Systems gateway
To be connected using cables VW3A8306Rpp
LUFP1 r
0.53 (0.24)
DEVICENET™/MODBUS® Systems gateway
To be connected using cables VW3A8306Rpp
LUFP9 r
0.53 (0.24)
PROFIBUS® DP/MODBUS® Systems gateway
To be connected using cable VW3P07306R10
LA9P307
0.53 (0.24)
Connection accessories
Connectors
Catalog number Weight lb (kg)
Junction box (to be connected with cable VW3A8306D30)
3 screw terminals
TSXSCA50
2-channel subscriber sockets (to be connected with cable VW3A8306)
2 15-way female SUB-D connectors and 2 screw terminals
TSXSCA62
1.26 (0.57)
MODBUS® Systems hub
8 RJ45 connectors
LU9GC3 r
1.10 (0.50)
1.15 (0.52)
Line terminator
–
VW3A8306RC
–
MODBUS® Systems T-junction box
–
VW3A8306TF3
–
Connecting cables For bus and networks
Connectors
Catalog number Weight lb (kg)
3
1 RJ45 connector and one end stripped
VW3A8306D30
3
1 RJ45 connector and 1 15-way male SUB-D connector
VW3A8306
0.33 (0.15)
0.3
2 RJ45 connectors
VW3A8306R03
0.11 (0.05)
1
2 RJ45 connectors
VW3A8306R10
0.11 (0.05)
3
2 RJ45 connectors
VW3A8306R30
0.33 (0.15)
PROFIBUS® DP
1
2 RJ45 connectors
VW3P07306R10
0.11 (0.05)
Ethernet
1
2 RJ45 connectors
VW3P10306R10
0.11 (0.05)
MODBUS® Systems
FIPIO®, DEVICENET™ MODBUS® Systems
Length (m)
0.33 (0.15)
r Contact your local Square D sales office for availability.
LUFP1 Characteristics: pages 4 to 7
09/02
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
11
Page 12
ALTISTART® 48 Soft Start Selection Selection
Line Voltage 208 to 690 V, Motor Power in HP For standard duty applications Motor
Starter 208 to 690 V - 50/60 Hz
Motor power (1)
Nominal current (IcL) (2)
208 V
ATS48D17YU
230 V
460 V
575 V
Factory setting current (4)
Power dissipated at nominal load
Catalog number
Weight
HP
HP
HP
HP
A
A
W
3
5
10
15
17
14
59
ATS48D17YU
10.8 (4.9)
lb (kg)
5
7.5
15
20
22
21
74
ATS48D22YU
10.8 (4.9)
7.5
10
20
25
32
27
104
ATS48D32YU
10.8 (4.9)
10
–
25
30
38
34
116
ATS48D38YU
10.8 (4.9)
–
15
30
40
47
40
142
ATS48D47YU
10.8 (4.9)
15
20
40
50
62
52
201
ATS48D62YU
18.3 (8.3)
20
25
50
60
75
65
245
ATS48D75YU
18.3 (8.3)
25
30
60
75
88
77
290
ATS48D88YU
18.3 (8.3)
30
40
75
100
110
96
322
ATS48C11YU
18.3 (8.3)
40
50
100
125
140
124
391
ATS48C14YU
27.3 (12.4)
50
60
125
150
170
156
479
ATS48C17YU
27.3 (12.4)
60
75
150
200
210
180
580
ATS48C21YU
40.1 (18.2)
75
100
200
250
250
240
695
ATS48C25YU
40.1 (18.2)
100
125
250
300
320
302
902
ATS48C32YU
40.1 (18.2)
125
150
300
350
410
361
1339
ATS48C41YU
113.3 (51.4)
150
–
350
400
480
414
1386
ATS48C48YU
113.3 (51.4)
–
200
400
500
590
477
1731
ATS48C59YU
113.3 (51.4)
200
250
500
600
660
590
1958
ATS48C66YU
113.3 (51.4)
250
300
600
800
790
720
2537
ATS48C79YU
253.6 (115.0)
350
350
800
1000
1000
954
2865
ATS48M10YU
253.6 (115.0)
400
450
1000
1200
1200
1170
3497
ATS48M12YU
253.6 (115.0)
Catalog number
Weight
For severe duty applications Motor
Starter 208 to 690 V - 50/60 Hz
Motor power (1) ATS48C14YU 208 V
ATS48M12YU
230 V
575 V
Factory setting current (4)
Power dissipated at nominal load
HP
HP
HP
HP
A
A
W
2
3
7.5
10
12
14
46
ATS48D17YU
10.8 (4.9)
3
5
10
15
17
21
59
ATS48D22YU
10.8 (4.9)
5
7.5
15
20
22
27
74
ATS48D32YU
10.8 (4.9)
7.5
10
20
25
32
34
99
ATS48D38YU
10.8 (4.9)
10
–
25
30
38
40
116
ATS48D47YU
10.8 (4.9)
–
15
30
40
47
52
153
ATS48D62YU
18.3 (8.3)
15
20
40
50
62
65
201
ATS48D75YU
18.3 (8.3)
20
25
50
60
75
77
245
ATS48D88YU
18.3 (8.3)
25
30
60
75
88
96
252
ATS48C11YU
18.3 (8.3)
30
40
75
100
110
124
306
ATS48C14YU
27.3 (12.4)
40
50
100
125
140
156
391
ATS48C17YU
27.3 (12.4)
50
60
125
150
170
180
468
ATS48C21YU
40.1 (18.2)
60
75
150
200
210
240
580
ATS48C25YU
40.1 (18.2)
75
100
200
250
250
302
695
ATS48C32YU
40.1 (18.2)
100
125
250
300
320
361
1017
ATS48C41YU
113.3 (51.4)
125
150
300
350
410
414
1172
ATS48C48YU
113.3 (51.4)
150
–
350
400
480
477
1386
ATS48C59YU
113.3 (51.4)
–
200
400
500
590
590
1731
ATS48C66YU
113.3 (51.4)
200
250
500
600
660
720
2073
ATS48C79YU
253.6 (115.0)
250
300
600
800
790
954
2225
ATS48M10YU
253.6 (115.0)
350
350
800
1000
1000
1170
2865
ATS48M12YU
253.6 (115.0)
(1) (2) (3) (4)
lb
Value indicated on the motor rating plate. Corresponds to the maximum permanent current in Class 10. IcL corresponds to the starter rating. Corresponds to the maximum permanent current in Class 20. The factory setting current corresponds to the value of the nominal current of a standard motor according to Canadian Electrical Code, 460 V, Class 10 (standard application). Adjust the settings in accordance with the motor nominal current.
Characteristics: pages 4 to 7
12
460 V
Nominal current (3)
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
09/02
Page 13
ALTISTART® 48 Soft Start Selection Selection
Line Voltage 208 to 690 V, Motor Power in kW For standard duty applications Motor
Starter 208 to 690 V - 50/60 Hz
Motor power (1)
Nominal current (IcL) (2)
230 V
400 V
440 V
500 V
525 V
660 V
690 V
Factory Power setting current dissipated at (4) nominal load kW kW kW kW kW kW kW
A
A
W
4
7.5
7.5
9
9
11
15
17
14
59
Catalog number
Weight
ATS48D17YU
10.8 (4.9)
lb
5.5
11
11
11
11
15
18.5
22
21
74
ATS48D22YU
10.8 (4.9)
7.5
15
15
18.5
18.5
22
22
32
27
104
ATS48D32YU
10.8 (4.9)
9
18.5
18.5
22
22
30
30
38
34
116
ATS48D38YU
10.8 (4.9)
11
22
22
30
30
37
37
47
40
142
ATS48D47YU
10.8 (4.9)
15
30
30
37
37
45
45
62
52
201
ATS48D62YU
18.3 (8.3)
18.5
37
37
45
45
55
55
75
65
245
ATS48D75YU
18.3 (8.3)
22
45
45
55
55
75
75
88
77
290
ATS48D88YU
18.3 (8.3)
30
55
55
75
75
90
90
110
96
322
ATS48C11YU
18.3 (8.3)
37
75
75
90
90
110
110
140
124
391
ATS48C14YU
27.3 (12.4)
45
90
90
110
110
132
160
170
156
479
ATS48C17YU
27.3 (12.4)
55
110
110
132
132
160
200
210
180
580
ATS48C21YU
40.1 (18.2)
75
132
132
160
160
220
250
250
240
695
ATS48C25YU
40.1 (18.2)
90
160
160
220
220
250
315
320
302
902
ATS48C32YU
40.1 (18.2)
110
220
220
250
250
355
400
410
361
1339
ATS48C41YU
113.3 (51.4)
132
250
250
315
315
400
500
480
414
1386
ATS48C48YU
113.3 (51.4)
160
315
355
400
400
560
560
590
477
1731
ATS48C59YU
113.3 (51.4)
–
355
400
–
–
630
630
660
590
1958
ATS48C66YU
113.3 (51.4)
220
400
500
500
500
710
710
790
720
2537
ATS48C79YU
253.6 (115.0)
250
500
630
630
630
900
900
1000
954
2865
ATS48M10YU
253.6 (115.0)
355
630
710
800
800
–
–
1200
1170
3497
ATS48M12YU
253.6 (115.0)
Catalog number
Weight
ATS48D17YU
10.8 (4.9)
For severe duty applications Motor
Starter 208 to 690 V - 50/60 Hz
Motor power (1)
Nominal current (3)
230 V
400 V
440 V
500 V
525 V
660 V
690 V
Factory setting Power current dissipated at (4) nominal load kW kW kW kW kW kW kW
A
A
W
3
5.5
5.5
7.5
7.5
9
11
12
14
46 lb
4
7.5
7.5
9
9
11
15
17
21
59
ATS48D22YU
10.8 (4.9)
5.5
11
11
11
11
15
18.5
22
27
74
ATS48D32YU
10.8 (4.9)
7.5
15
15
18.5
18.5
22
22
32
34
99
ATS48D38YU
10.8 (4.9)
9
18.5
18.5
22
22
30
30
38
40
116
ATS48D47YU
10.8 (4.9)
11
22
22
30
30
37
37
47
52
153
ATS48D62YU
18.3 (8.3)
15
30
30
37
37
45
45
62
65
201
ATS48D75YU
18.3 (8.3)
18.5
37
37
45
45
55
55
75
77
245
ATS48D88YU
18.3 (8.3)
22
45
45
55
55
75
75
88
96
252
ATS48C11YU
18.3 (8.3)
30
55
55
75
75
90
90
110
124
306
ATS48C14YU
27.3 (12.4)
37
75
75
90
90
110
110
140
156
391
ATS48C17YU
27.3 (12.4)
45
90
90
110
110
132
160
170
180
468
ATS48C21YU
40.1 (18.2)
55
110
110
132
132
160
200
210
240
580
ATS48C25YU
40.1 (18.2)
75
132
132
160
160
220
250
250
302
695
ATS48C32YU
40.1 (18.2)
90
160
160
220
220
250
315
320
361
1017
ATS48C41YU
113.3 (51.4)
110
220
220
250
250
355
400
410
414
1172
ATS48C48YU
113.3 (51.4)
132
250
250
315
315
400
500
480
477
1386
ATS48C59YU
113.3 (51.4)
160
315
355
400
400
560
560
590
590
1731
ATS48C66YU
113.3 (51.4)
–
355
400
–
–
630
630
660
720
2073
ATS48C79YU
253.6 (115.0)
220
400
500
500
500
710
710
790
954
2225
ATS48M10YU
253.6 (115.0)
250
500
630
630
630
900
900
1000
1170
2865
ATS48M12YU
253.6 (115.0)
(1) (2) (3) (4)
Value indicated on the motor rating plate. Corresponds to the maximum permanent current in Class 10. IcL corresponds to the starter rating. Corresponds to the maximum permanent current in Class 20. The factory setting current corresponds to the value of the nominal current of a standard motor according to CEC, 460 V, Class 10 (standard application). Adjust the settings in accordance with the motor nominal current. Characteristics: pages 4 to 7
09/02
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
13
Page 14
ALTISTART® 48 Soft Start Options: Remote Keypad Display, Protective Covers, Line Reactors Options: Remote Terminal/Keypad, Protective Covers, Documentation
REMOTE KEYPAD DISPLAY The keypad display can be mounted on the door of a wall-mounted or floor-standing enclosure. It has the same signalling display and configuration buttons as the keypad display integrated in the starter. A switch to lock access to the menu is located at the rear of the keypad display. The option includes: • the remote keypad display • a mounting kit containing a cover, screws and an IP 54 seal on the front panel • a 9.82 ft. (3 m) connecting cable with a 9-pin SUB-D connector for connecting to the keypad display and an RJ45 connector for connecting to the ATS48 controller. VW3G48101
1. Information is displayed in the form of codes or values in three “7-segment” displays
1
2. Buttons for scrolling through the menus or modifying values ESC
3
ENT
4
3. “ESC”: Button for exiting the menus (cannot be used for validation purposes) 4. “ENT”: Validation button for entering a menu or confirming the new value selected
2 Description
Catalog number
Weight lb (kg)
Remote keypad display
VW3G48101
0.44 (0.20)
PROTECTIVE COVERS FOR POWER TERMINALS To be used with tags closed For starters
Number of covers per set
Catalog number
Weight lb (kg)
ATS48C14Y and ATS48C17Y
6 (1)
LA9F702
0.6 (0.25)
ATS48C21Y, ATS48C25Y and ATS48C32Y
6 (1)
LA9F703
0.6 (0.25)
(1)
The starters have 9 unprotected power terminals.
LA9F702
LINE REACTORS The use of line reactors is recommended in particular when installing several electronic starters on the same line supply. The inductance values are defined for a voltage drop between 3% and 5% of the nominal line voltage. Install the line reactor between the line contactor and the starter. Reference
Value of the Inductance mH
A
ATS48D17YU
2.5
18
Degree of protection
Reference
Weight
Open type
RL-01803
16/7.3 lb/kg
ATS48D22YU
2.0
25
Open type
RL-02503
18/8.1
ATS48D32YU and D38YU
1.2
45
Open type
RL-04503
39/18
ATS48D47YU and D62YU
0.7
80
Open type
RL-08003
55/25
ATS48D75YU and D88YU
0.45
100
Open type
RL-10003
74/33 67/31
ATS48C11YU and C14YU
0.23
160
Open type
RL-16003
ATS48C17YU and C25YU
0.15
250
Open type
RL-25003
140/64
ATS48C32YU
0.125
320
Open type
RL-32003
190/86
ATS48C41YU and C48YU
0.085
500
Open type
RL-50003
290/132
ATS48C59YU
0.065
600
Open type
RL-60003
290/132
ATS48C66YU and M12YU
14
Nominal current
Consult Schneider Electric for information
© 2002 Schneider Electric All Rights Reserved
08/02
Page 15
ALTISTART® 48 Soft Start POWERSUITE® Advanced Dialog Solutions PowerSuite Advanced dialog Solutions
The POWERSUITE® advanced dialog solutions can be used for Schneider Electric drives and starters. They enable communication with the product from a Pocket PC/PDA, Personal Computer or a dedicated terminal. The solutions, with a Pocket PC or PC, enable files to be prepared for uploading to the drives and the starters. The POWERSUITE® software creates its files ensuring consistency between the configuration/adjustment functions of the product. POWERSUITE® Pocket PC/PDA The Pocket PC/PDA can be used during preparation, programming, setup and maintenance. It comprises a Palm size PC terminal and corresponding connection accessories. The software is integrated into a Windows CE environment, for which the operating system language can be selected on ordering (English, French, German, Spanish, Italian). The software incorporates all the functions of integrated and remote terminals (drive or starter configuration and adjustment, control, signalling, etc). The Pocket PC/PDA can be used: • alone to prepare and store configuration/adjustment files (integral battery or line supply) • connected to a PC for uploading configuration/adjustment files from the Pocket PC to the PC or downloading from the PC to the Pocket PC • connected to the drive or to the starter for configuration, adjustment or control purposes or to upload a configuration/adjustment file from the Pocket PC to the product or download a configuration/ adjustment file from the product to the Pocket PC. POWERSUITE® software workshop for PC The POWERSUITE® software workshop is used to set up a drive or a starter from a PC in a MICROSOFT® Windows 95, 98, NT4 or 2000 environment. The software incorporates all the functions of integrated and remote terminals (drive or starter configuration and adjustment, control, signalling, etc.) with assisted, guided operator dialog in 5 languages (English, French, German, Spanish, Italian) in a Windows environment. It can be used: • alone to prepare and store drive or starter configuration files on diskette, CD-ROM or hard disk. The drive or starter configuration can be printed out on paper or can be exported to office automation software. • connected to the drive or starter for configuration, adjustment or control purposes, or for uploading a configuration/adjustment file from the PC to the product or downloading from the product to the PC. Connection is via a link between the drive or starter connector and the serial port on the PC. MAGELIS® display unit with matrix screen The MAGELIS® display unit with matrix screen can be used to monitor, diagnose and adjust up to 8 Altivar 28, 38, 58 or 58F drives in 5 languages (English, French, German, Spanish, Italian). It can display variables in alphanumeric format with European, Cyrillic or Asian fonts in 4 sizes, or it can display icons or background images in black and white as well as animations in barchart or gauge format. The application is preloaded in the factory. Compatibility Drives ATV28, ATV58, ATV58F
Starter ATS48
VW3A8108pp VW3A8102 VW3A8111 VW3A8104 VW3A8106
■ ■ ■ ■ ≥ V 1.0 ■
■ ■ ■ ■ ≥ V 1.30 ■
Display unit
XBTHM017010A8
■
Upgrade CD-ROM Pocket PC Jornada Operator terminal
VW3A8105 ■ ≥ V 1.0 VW3A8103pp ■ ■ Compatible products and versions
Compatibility of advanced dialog solutions with drives and starters POWERSUITE® Pocket PC POWERSUITE® software workshop for PC MAGELIS® display unit with matrix screen Accessories ▼ Incompatible products
09/02
Pocket PC Setup kit Connection kit CD-ROM Connection kit
© 2002 Schneider Electric All Rights Reserved
■ ≥ V 1.40 ■ ≥ V 1.30 ■
15
Page 16
ALTISTART® 48 Soft Start POWERSUITE® Advanced Dialog Solutions PowerSuite Advanced dialog Solutions
POWERSUITE® Pocket PC/PDA Several solutions are available to meet the needs of individual users: • The complete Pocket PC/PDA
• 1 CD-ROM containing the multilingual (1) setup software which can be ordered separately
• The setup kit
• 1 connection kit for the Palm size PC terminal
• The connection kit
The connection kit for the Palm size PC terminal comprises:
The complete Pocket PC is used to set up drives and starters. It comprises: VW3A8103pp
The setup kit comprises:
• 2 connection cables, length 0.6 m, with 2 RJ45 connectors, marked respectively • 1 Palm size “Jornada 525” PC terminal, with “POWERSUITE®” and “ATV 28 before 09/01” multilingual operating system (1), supplied with PC synchronization cable and mains power supply
• 1 RJ45/9-way SUB-D adaptor for connecting ATV58 and ATV58F
• 1 CD-ROM containing the multilingual (1) setup • 1 converter marked “RS 232/RS-485 PPC” with software which can be ordered separately one 9-way male SUB-D connector and 1 RJ45 connector. • 1 connection kit for the Palm size PC terminal Description
Catalog Number
Weight - lb (kg)
Complete Pocket PC
VW3A8108pp (2)
2.2 (1.00)
Setup kit
VW3A8102
0.9 (0.40)
Connection kit for the Palm size PC terminal
VW3A8111
0.7 (0.30)
POWERSUITE® software workshop for PC The software workshop is used to set up the drives and starters from a PC. It comprises: • 1 CD-ROM containing the multilingual (1) setup software • 1 connection kit for PC
The PC connection kit comprises: • 2 connection cables, length 3 m, with 2 RJ45 connectors, marked respectively “POWERSUITE®” and “ATV 28 before 09/01” • 1 RJ45/9-way SUB-D adaptor for connection of ATV58 and ATV58F drives • 1 converter marked “RS-232/RS-485 PC” with one 9-way male SUB-D connector and 1 RJ45 connector
XBTHM017010A8
Description
Catalog Number
Weight - lb (kg)
1 CD-ROM containing the multilingual setup software (1)
VW3A8104
2.2 (0.10)
Connection kit for PC
VW3A8106
0.8 (0.35)
MAGELIS® display unit with matrix screen The terminal has a backlit LCD with 8 lines of 40 characters. The RS-458 connection kits for ATV28 (VW3A28301), ATV38 and ATV58 (VW3A58306) drives, as well as other connection accessories, should be ordered separately according to the number and type of drives connected. Please consult your Regional Sales Office. Description
Catalog Number
Weight - lb (kg)
MAGELIS® display unit with matrix screen
XBTHM017010A8
1.3 (0.60)
Accessories Description
Catalog Number
Weight - lb (kg)
1 upgrade CD-ROM for multilingual (1) setup software (3)
VW3A8105
0.22 (0.10)
Palm size “Jornada 525” PC terminal supplied with PC synchronization cable and mains power supply
VW3A8103pp (2)
0.7 (0.30)
VW3A8103pp (2)
VW3A8110
0.22 (0.10)
(1) English, French, German, Spanish, Italian. (2) To order the operating system in your chosen language, replace pp by EN for English, FR for French, DE for German, SP for Spanish and IT for Italian. (3) To find out about the latest available version, please consult your Regional Sales Office.
16
© 2002 Schneider Electric All Rights Reserved
09/02
Page 17
ALTISTART® 48 Soft Start Dimensions Dimensions
=
3.94 = 100 6.3
10.63 270
11.42 290
M6
7.48 190
5.9 150 M6
4x 7
10.24 260
10.83 275
M6 inches mm
M6 7.48 190
9.25 235
160 Maximum connection capacity: Ground connections: 8 AWG (10 mm2) Power terminals: 8 AWG (16 mm2)
0.39 10
ATS48D62YU to ATS48C11YU
4x 7
0.26 6.6
ATS48D17YU to ATS48D47YU inches mm
Maximum connection capacity: Ground connections: 4 AWG (16 mm2) Power terminals: 2/0 (50 mm2 )
ATS48C14YU to ATS48C17YU
3/L2
5/L3
Maximum connection capacity: Ground connections: Busbar (120 mm2 ) Power terminals: 2/0 (95 mm2 )
0.55 0.04 14 1
13.39 340
12.6 320
1/L1
0.79 20 4x 7
0.4 10
6.26 159
=
160 1.58 40 M6
0.08 2
0.2 5
6.30
=
0.04 1
0.71 18
9x 8 M6 1.5 2.44 2.44 38 62 62 7.87 200
0.2 4.59 0.2 5 6.38 116.5 5 10.43 162 265 inches mm
ATS48C21YU to ATS48C32YU
9x 12
1/L1
3/L2
5/L3
4x 9 0.08 2
M10
Maximum connection capacity: Ground connections: Busbar (120 mm2 ) Power terminals: Busbar (240 mm2)
0.39 10
5.37 136.5
=
9.84 250
2.6 66
0.2 5.37 5 7.74 136.5 0.2 5 10.43 196.5 265
2.76 70
M10 3.54 90
320 Characteristics: pages 4 to 7
09/02
0.79 3.5420 90 12.6
0.04 1
0.71 18
14.96 380
0.2 5
=
13.78 350
1.38 35 inches mm Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
17
Page 18
ALTISTART® 48 Soft Start Dimensions Dimensions
ATS48C41YU to C66YU
= 4.72 120 4x 9
2.72127 M10 69 1L1 3L2
0.8 20
6.5 165
=
Maximum connection capacity: Ground connections: Busbar (240 mm2) Power terminals: Busbar (2 x 240 mm2)
5L3
24.02 610
26.38 670
0.2 5
0.2 5
11.8 4.53 300 4.53 115 5 115
0.2 5 0.2 5 11.8 300
0.06 1.5
1.57 40
58
6.5 8.5 165 216
0.01
M10
1.98 0.25 50.25
4.53 115
1.57 40 4.53 115 15.75 400 inches mm
ATS48C79YU to M12YU
0.8 20
6.69 170
6.46129 164 6x 9
=
13.78 350 1.02 26 8.25
26 8.8 223.5 M10
Maximum connection capacity: Ground connections: Busbar (2 x 240 mm2 ) Power terminals: Busbar (4 x 240 mm2)
1.02 26
209.5 18x 14
6.1 155
7.09 180
8.03 1.02 204 26
8.98 1.02 228 26
26
1.02
5
1.02 26
0.95 26 1.02 24
33.46 850
35.04 890
.08 2
0.2 5
13.78 10.12 350 5.08 2571.02
1.02 26
=
0.2 4.59 116.5 0.2 57.74 196.5 5 12.4 315
2.36 3.74 60 95 7.4 188
Characteristics: pages 4 to 7
18
M10
2.36 60
30.31 770 Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved inches mm
Wiring Diagrams: pages 21 to 24
09/02