For the Telemecanique Altistart 48 ATS48

Page 19

ALTISTART® 48 Soft Start Mounting Mounting

MOUNTING THE REMOTE KEYPAD DISPLAY VW3G48101

2.2 55.6

2.05 52

0.95 24

3.13 79.6 inches mm

4xØ3.5

A

Ø36

MOUNTING RECOMMENDATIONS • Install the ATS48 Soft Start vertically, within ± 10˚. • Do not place the ATS48 Soft Start adjacent to or above heating elements. • Leave sufficient free space to ensure that the air required for cooling can circulate from the bottom to the top of the unit.

4 100

Note: The IP 00 version of the ATS48 Soft Start must be fitted with a protective bar to protect personnel against electrical contact. Protective covers are available for the ATS48C14YU to ATS48C32YU. They should be ordered separately.

2 50

0.4 10

4 100

2 50 inches mm

Characteristics: pages 4 to 7

09/02

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

19

Page 20

ALTISTART® 48 Soft Start Mounting Mounting

MOUNTING IN A METAL WALL-MOUNTED OR FLOOR-STANDING ENCLOSURE WITH DEGREE OF PROTECTION TYPE 1 (IP 23) OR TYPE 12 (IP 54) • Observe the mounting recommendations on the previous page. • To ensure proper air circulation in the starter:, Fit ventilation grilles, Ensure that there is sufficient ventilation. If there is not, install forced ventilation with a filter. The openings and/or fans must provide a flow rate at least equal to that of the starter fans (see the table below) • Use special filters with Type 12 (IP 54) protection. Fan flow rate depending on the starter rating ATS48 starter

CFM

Flow rate m3/hour

ATS48D32YU and D38YU

24

14

ATS48D47YU

48

28

ATS48D62YU to C11YU

146

86

ATS48C14YU and C17YU

235

138

ATS48C21YU to C32YU

476

280

ATS48C41YU to C66YU

1020

600

ATS48C29YU to M12YU

2040

1200

Metal wall-mounted or floor-standing enclosure with Type 12 (IP 54) degree of protection For non-ventilated ATS48 controllers (ATS48D17YU and 48D22YU), install a fan ≤ 2" (50 mm) below the starter to circulate the air inside the enclosure in order to avoid hot spots. Calculating Enclosure Size The maximum allowable thermal resistance of the enclosure equation, Rth (˚C/W), is calculated as follows: Rth = θ – θe P

θ = maximum temperature inside enclosure in ˚C θe = maximum external temperature in ˚C P = total power dissipated in the enclosure in W

• The starter/motor combinations on pages 12 and 13 can be used in ambient temperatures ≤ 40 ˚C. • For temperatures between 40 ˚C and 60 ˚C, derate the maximum permanent current of the starter by 2% for every degree above 40 ˚C. • For the power dissipated by the starters at rated load: see pages 12 and 13. • If the starts are infrequent, it is recommended to use a shorting/bypass contactor with the ATS48 controller at the end of start to minimize heat dissipation. Calculate minimum useful heat exchange surface area requirement, S (in2): S=K Rth

Rth = Thermal resistance of the enclosure (calculated previously) K = Thermal resistance per square inch of the enclosure K = 186 with enclosure fan K = 233 without enclosure fan Compare to the effective heat exchange surface area to the proposed wall mounted enclosure, S (in2) which should be less than: S = (Front area) + (Top area) + 2 (Side area) Characteristics: pages 4 to 7

20

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

09/02

Page 21

ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams

Nonreversing with Shunt Trip Fault Isolation Circuit Breaker * w/Shunt Trip *

A2

A

1/L1

2/T1

3/L2

4/T2

B2

AC LINE SUPPLY

B

M

C2 5/L3

C

6/T3

FU4

SC 2

CL1

{

TO CONTROL POWER TRANSFORMER

GND

FU5 CL2 STOP

SC

STOP ATS48 CONTROLLER

RUN SC

RUN

1

RESET (IF USED)

T1

LI3 120V FU1

SEE DETAIL B

FU5

FU4

FAULT (R1C) (R1A)

LI4

+24V TRIP RELAY

*

TR

LO+

3 TS1

LO1

TR

CB SHUNT TRIP COIL

*

*

ST

LO2

(2 SEC) G MOTOR THERMAL SW 4

PROGRAMMABLE ANALOG OUTPUT (IF USED)

RUN

5

SEE DETAIL A (A)

*

AO1

{

COM

RUN COMMAND

*

RCR

RELAY

PTC1

(B) (C)

TS1

PTC2

RCR

R1A

END START UP (R2C) (R2A)

SHORTING CONTACTOR

*

SCA

FAULT R1C

PILOT RELAY

3

R2A

TS1 SCA

2

SHORTING CONTACTOR

*

SC

R2C

R3A

TS4

R

END START UP

R3C

*

PROGRAMMABLE N.O. CONTACT

POWER ON

DETAIL A 2-WIRE CONTROL W / O AUTO

2-WIRE CONTROL W / AUTO OFF HAND

ON

OFF

AUTO

STOP

(B)

START

(A) (A)

USER SUPPLIED

OR

(A)

1

Control circuit connection for 460 V operation. Reconnect as required for other voltages.

2

For shorting contactor operation, add SC with associated control circuit. Relay contact located on ATS48 controller.

3-WIRE CONTROL

(B)

(B)

OR

3 (C)

4

Located at motor. Jumper if switch not present.

5

Use RCR relay logic for ATS48 2-wire or 3-wire control when using shorting contactor.

DETAIL B

STOP

STOP

RUN

RUN OR

RCR +24V

Characteristics: pages 4 to 7

09/02

OFF

ON

* = User supplied

+24V

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

21

Page 22

ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams

Nonreversing with Isolation Contactor SW

*

A2

*

FU6 A

IC

*

1/L1

2/T1

IC

3/L2

4/T2

B2

FU7

AC LINE SUPPLY

B

M

C2

FU8

6/T3

5/L3

IC

C

FU4

SC FU2

CL1

{

TO CONTROL POWER TRANSFORMER

GND

FU5 CL2

FU3 2

SC

STOP ATS48 CONTROLLER

SC

RUN

1 T1

RESET (IF USED) LI3

120V FU4

FU1

LI4

RCR

FU5

+24V

MOTOR THERMAL SW

SEE DETAIL A (A)

4

RUN COMMAND RELAY

*

RCR

LO+

(B) (C)

TS1

LO1

RCR LO2

FAULT (R1C) (R1A)

FAULT RELAY

*

FR

PROGRAMMABLE ANALOG OUTPUT (IF USED)

3 TS1 FR

RCR IC

AO1

{

COM

ISOLATION

*

PTC1

CONTACTOR

PTC2

TS2

5 END START UP (R2C) (R2A)

R1A SCA

SHORTING CONTACTOR

*

FAULT R1C

PILOT RELAY

3 TS1 SCA SC

*

R2A 2

SHORTING CONTACTOR

R2C

TS4

R3A

*

POWER ON

W

*

FAULT

*

RUN

R

END START UP

R3C

PROGRAMMABLE N.O. CONTACT

FR

IC G

1

Control circuit connected for 460 V operation. Reconnect as required for other voltages.

2

For shorting contactor operation add SC with associated control wiring. Relay contact located on ATS48 controller.

3 DETAIL A 2-WIRE CONTROL W / O AUTO

2-WIRE CONTROL W / AUTO OFF HAND

OFF

AUTO

3-WIRE CONTROL

ON

STOP

(B)

START

(A) (A)

USER SUPPLIED

OR

(A)

(B)

(B)

OR (C)

Characteristics: pages 4 to 7

22

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

4

Located at motor. Jumper if switch not present.

5

Set RCR time slightly longer than expected deceleration time from rated speed to zero speed. The time delay RCR contact may be omitted if the configuration of the R1 relay is changed to isolating relay mode.

* = User supplied

Wiring Diagrams: pages 21 to 24

09/02

Page 23

ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams

Reversing with Isolation Contactors SW

*

A2

*

FU6 A

IC1

*

1/L1

2/T1

IC1

3/L2

4/T2

B2

FU7

AC LINE SUPPLY

B

M

C2

FU8

IC1

C

*

IC2 FU2

6/T3

5/L3

SC

FU3

2

IC2

SC SC

IC2 1 T1

FU4

120V FU4

FU1

FU5

MOTOR THERMAL SW

(B)

(C) (D)

(R1A)

FAULT

RUN FWD

*

ATS48 CONTROLLER

RELAY RUN

RFR

TS1

1

RESET (IF USED)

RFR

LI3 RRR

(E)

CL2

STOP RFR

SEE DETAIL A

GND

FU5

RRR

(A) 4

CL1

{

TO CONTROL POWER TRANSFORMER

RUN REV RELAY

*

RRR

IC1

RFR

IC2

LI4 RRR

TS1

(R1C) FR

2 +24V

FAULT

*

RELAY

3

LO+

3

TS1 RFR

FR

KM2

5

IC1

LO1

FORWARD CONTACTOR

*

4

Located at motor. Jumper if switch not present.

5

Set RFR time slightly longer than the expected deceleration time from rated forward speed to zero speed.

6

Set RRR time slightly longer than the expected deceleration time from rated reverse speed to zero speed.

7

Remove these contacts to inhibit direction reversal without first depressing STOP push button.

LO2 TS2 RRR

6

KM1 IC2

REVERSING PROGRAMMABLE CONTACTOR ANALOG OUTPUT (IF USED)

*

AO1

{

COM

TS2

END START UP (R2C) (R2A)

SCA

*

3

SHORTING CONTACTOR

PTC1

PILOT RELAY

PTC2

TS1 SCA

R1A

2 SC

SHORTING

*

CONTACTOR R1C

FAULT

TS4 R2A R

*

POWER ON R2C

END START UP

FR

*

FAULT

*

RUN FORWARD

*

RUN REVERSE

W

R3A

Control circuit connected for 460 V operation. Reconnect as required for other voltages. For shorting contactor operation, add SC with associated circuitry. Relay contact located on ATS48 controller.

* = User supplied

R3C

IC1 G

PROGRAMMABLE N.O. CONTACT

IC2 A

DETAIL A 2-WIRE CONTROL W / AUTO START AUTO DIRECTION

HAND (A)

FWD

AUTO F

REV

FWD

(B)

OFF

REV

STOP (B) (A)

(A)

R

RUN REV

7

(D) USER SUPPLIED R

RUN FWD

OFF

USER SUPPLIED

HAND

(B)

AUTO

FWD

REV (B)

(A) (C) (D)

F

USER SUPPLIED (D)

7

09/02

2-WIRE CONTROL W / AUTO START MANUAL DIRECTION

3-WIRE CONTROL

2-WIRE CONTROL W / O AUTO

OFF

(D)

(E)

© 2002 Schneider Electric All Rights Reserved

23

Page 24

ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams

Description of Logic for Recommended Wiring Diagrams Item

Name

Description

IC1 IC1A

Isolation Contactor (Fwd)

The isolation contactor logic closes IC1 upon a start command and opens IC1 after the stop is complete. The RCR (or RFR and RRR for reversing) are timed contacts that must have a time delay greater than the deceleration ramp time or the dynamic braking time. When a coast stop is selected, the time delay must be set for a time that will allow a complete decay of the motor residual voltage. The isolation contactor will open immediately upon a fault. The pilot relay (IC1A) is required when the IC1 contactor coil exceeds the relay rating.

IC2 IC2A

Isolation Contactor (Rev)

Used for reversing applications only, the IC2 must be mechanically interlocked to IC1. A reversing contactor may be used for the combination of IC1 and IC2. In general, the operation of IC2 is identical to IC1. The pilot relay (IC1A) is required when the IC1 contactor coil exceeds the relay rating.

SC SCA

Shorting Contactor & Pilot Relay

The shorting contactor is used to reduce the heat dissipated by the controller when the motor is operating at full speed and voltage. The starter provides proper sequencing of this contactor by the “end-start-up” relay. When the start is completed, the shorting contactor will be commanded to close. The starter will continue to monitor the motor thermal state and provide motor overload protection. Upon a stop command, the SC contactor will open, transferring the motor current to the Scars to allow for controlled deceleration if desired. The pilot relay (SCA) is required when the SC contactor coil exceeds the relay rating.

TS

Transient Suppressors

Transient suppression of all relay and contactor coils (except ST) is recommended to minimize the possibility of electrical interference with the starter electronics and to increase relay contact life.

RCR

Run Command Relay

Used in all non-reversing logic (optional in shunt trip) for proper sequencing of contactor logic. When energized, RCR initiates the start sequence. When de-energized, stopping is initiated. Operator controls can be either on/off selector switch, HOA selector switch or start/stop push buttons. RCR remains energized during a fault. Once the fault condition has been cleared, RCR must be de-energized by a “stop” command then re-energized to restart the controller.

RFR

Run Forward Relay

Used for reversing applications only, this coil duplicates the functionality of RCR for the forward direction and is interlocked with the RFR relay.

RRR

Run Reverse Relay

Used for reversing applications only, this coil duplicates the functionality of RCR for the reverse direction and is interlocked with the RRR relay.

ST

Shunt Trip Coil

This coil is attached to the shunt trip coil on the disconnect and will energize 2 seconds after a starter fault by the TR timer contact. The time delay is to prevent nuisance tripping of the circuit breaker during controller power-up or during line undervoltage conditions.

TR

Trip Relay

Used in shunt trip circuit breaker logic only; coil energized upon a starter fault.

FR

Fault Relay

Used with logic diagrams that use an isolation contactor. The fault relay is energized during normal operation and deenergizes if the starter fault contacts open or if the motor thermal switch (if supplied) opens. FR also provides additional contacts for the starter fault output.

Suggested Components for Standard Duty Applications

575 V

ALTISTART® Controller ATS ATS48 Soft Starter Device Rated Current Model @40 ˚C ■

FU4/FU5 ATS Control Power Burden (VA)

Class CC Control Fuse Size @208/230 V @460/575 V

10

15

ATS48D17YU

17

25

0.25 A

0.25 A

15

20

ATS48D22YU

22

25

0.25 A

0.25 A

10

20

25

ATS48D32YU

32

25

0.25 A

0.25 A

10, 25

30

ATS48D38YU

38

25

0.25 A

0.25 A, 15

30

40

ATS48D47YU

47

25

0.25 A

0.25 A

15

20

40

50

ATS48D62YU

62

25

0.25 A

0.25 A

20

25

50

60

ATS48D75YU

75

25

0.25 A

0.25 A

25

30

60

75

ATS48D88YU

88

25

0.25 A

0.25 A

30

40

75

100

ATS48C11YU

110

25

0.25 A

0.25 A

40

50

100

125

ATS48C14YU

145

25

0.25 A

0.25 A

50

60

125

150

ATS48C17YU

170

25

0.25 A

0.25 A

60

75

150

200

ATS48C21YU

210

25

0.25 A

0.25 A

75

100

200

250

ATS48C25YU

250

25

0.25 A

0.25 A

100

125

250

300

ATS48C32YU

320

25

0.25 A

0.25 A

125

150

300

350

ATS48C41YU

410

25

0.25 A

0.25 A

150, 350

400

ATS48C48YU

480

25

0.25 A

0.25 A, 200

400

500

ATS48C59YU

590

25

0.25 A

0.25 A

200

250

500

600

ATS48C66YU

660

25

0.25 A

0.25 A

250

300

600

800

ATS48C79YU

790

25

0.25 A

0.25 A

350

350

800

1000

ATS48M10YU

1000

25

0.25 A

0.25 A

450

1000

1200

ATS48M12YU

1200

25

0.25 A

0.25 A

Induction Motor M Rated hp r 208 V 230 V

460 V

3

5

5

7.5

7.5

400 r ■

Motor full load currents through 500 hp @ 460/575 V, 250 hp @ 230 V, and 200 hp @ 208 V are taken from the Canadian Electrical Code. Above these ratings, motor full load currents are calculated based upon 1.2 A/hp for 460 V and 2.4 A/hp for 230 V. Motors listed are for standard duty applications. For severe duty applications, select the next larger controller size. The ambient temperature indicated in the table represents the temperature of the air surrounding the ATS48 controller. Any additional temperature factors associated with the enclosure system or actual installation ambient temperature must be considered when determining the actual rated current (ICL) of the starter. For operating ambient above 40 ˚C without a shorting/ bypass contactor and 50 ˚C with a shorting/bypass contactor but not exceeding 60 ˚C, the rated current (ICL) of the starter must be de-rated by 2% per ˚C.

NOTE: To select control operators (push buttons, pilot lamps, and selector switches), control power transformers, and wire management devices (control and power terminal strips, wire terminations) indicated on the recommended wiring diagram configurations, visit www.schneider-electric.ca.

24

© 2002 Schneider Electric All Rights Reserved

09/02

Page 25

ALTISTART® 48 Soft Start Recommended Component Lists Recommended Component Lists

Additional Suggested Components for Standard Duty Applications Contactors a, b, c

ATS

Disconnect d

IC2

Isolation Contactor

Reversing Contactor e

Mechanical Interlock

Shorting Power Fuses Contactor (AC1) Class/Rating

Ferraz Shawmut fuses or Fuse Block f equivalent

Molded Case Switch g

Thermal Magnetic g

D17Y

LC1D18

LC1D18 h

LC1D18

J / 25

AJT25

60308J

FHL36000M

FAL36030

D22Y

LC1D25

LC1D25 h

LC1D25

J / 30

AJT30

60308J

FHL36000M

FAL36040

D32Y

LC1D32

LC1D32 h

LC1D32

J / 40

AJT40

60608J

FHL36000M

FAL36050

D38Y

LC1D40

LC1D40 h

LC1D40

J / 50

AJT50

60608J

FHL36000M

FAL36060

D47Y

LC1D50

LC1D50 h

LC1D50

J / 60

AJT60

60608J

FHL36000M

FAL36080

D62Y

LC1D65

LC1D65 h

LC1D65

J / 80

AJT80

61038J

FHL36000M

FAL36090

D75Y

LC1D80

LC1D80 h

LC1D80

J / 100

AJT100

61038J

FHL36000M

FAL36100

D88Y

LC1D80

LC1D80 h

LC1D80

J / 120

AJT125

62003J

KHL36000M

KAL36110

C11Y

LC1D115

LC1D115 h

LC1D115

J / 150

AJT150

62003J

KHL36000M

KAL36150

C14Y

LC1D150

LC1D150 h

LC1D150

J / 200

AJT200

62003J

KHL36000M

KAL36200

C17Y

LC1F185

LC1F185

LA9FF970

LC1F185

J / 225

AJT225

64033J

LHL36000M

LAL36225

C21Y

LC1F265

LC1F265

LA9FG970

LC1F265

J / 300

AJT300

64033J

LHL36000M

LAL36250

C25Y

LC1F265

LC1F265

LA9FJ970

LC1F265

J / 350

AJT350

64033J

LHL36000M

LAL36350

C32Y

LC1F400

LC1F400

LA9FJ970

LC1F400

J / 400

AJT400

64033J

LHL36000M

LAL36400

C41Y

LC1F400

LC1F400

LA9FJ970

LC1F400

J / 500

AJT500

6633J

MHL36000M

MAL36500

C48Y

LC1F500

LC1F500

LA9FJ970

LC1F500

J / 600

AJT600

6633J

MHL360006M

MAL36600

C59Y

LC1F630

LC1F630

LA9FJ970

LC1F630

L / 700

A4BQ700 f

MHL360008M

MAL36800

C66Y

LC1F800

LC1F800

LA9FJ970

LC1F800

L / 900

A4BQ900 f

MHL360008M

MAL36900

C79Y

LC1BL33

LC1BL33

LA9FL970

LC1BL33

L / 1100

A4BQ1200 f

MHL36000M i

M10Y

LC1BL33

LC1BL33

LA9FL970

LC1BL33

L / 1350

A4BQ1350 f

MHL36000M i

M12Y

LC1BP33

LC1BP33

LA9FX970

LC1BP33

L / 1600

A4BQ1600 f

NCL3600012M i

ATS48 Model a. b. c. d. e.

f. g.

h. i.

SC

Circuit Breaker

IC1

Fusible Disconnect

All coils are selected for 120 V, 60 Hz operation. Refer to the Industrial Control Products Catalogue for additional coil voltages or auxiliary contact configurations. One block may be added to each contactor. Power terminals are not included with LC1-F contactors. For additional ordering information visit www.schneider-electric.ca. The use of transient suppressors across all contactor coils is recommended. Refer to the latest editions of Schneider Electric’s full line product catalogs for selection of transient suppressors. According to the Canadian Electrical Code, branch circuit overcurrent protection must be provided for each controller. Short circuit protective devices recommended in this table are within CEC requirements for Type 1 coordination. Reversing contactors for C11 through M12 controllers must be assembled from components. Parts quantities for a basic contactor assembly, minus the power connection links and terminals, are indicated before each part number. Refer to the latest editions of Schneider Electric’s full line product catalogs for power connector link and terminal kits. Reversing contactor interlock units used for the C79 through M12 controllers are designed for vertical interlocking of the individual contactors. Horizontally interlocked contactors are used for D17 through C59 controllers. Fuse holder part number references are for Class J fuses only based on Ferraz Shawmut spring reinforced with box type connectors acceptable for Al/Cu wiring. Class L fuses require bolton connections to user-supplied power bus work. The molded case switches and circuit breakers selected require the addition of operator mechanisms to allow operation from the exterior of an enclosure. Refer to the latest editions of Schneider Electric’s full line product catalogs for operator mechanism information. When using a shunt trip relay for SCR fault isolation, order a disconnect switch with suffix -1021 for addition of shunt trip coil. The D Line contactor is available as a reversing configuration. For these applications, change the IC1 part number prefix from LC1- to LC2- to order the IC1 and IC2 combination complete with mechanical interlocks. Devices rated above 660 A have not been coordinated with circuit breakers. You must use a Class L fuse for overcurrent protection with ATS48 soft starter models C79, M10, and M12.

Characteristics: pages 4 to 7

09/02

Dimensions: pages 17 to 18

© 2002 Schneider Electric All Rights Reserved

Wiring Diagrams: pages 21 to 24

25

Page 26

ALTISTART® 48 Soft Start Functions Functions

Summary of functions Description

See pages

Starter factory setting p. 27

Adjustment functions

Protection functions

Advanced adjustment functions

Nominal motor current (maximum permanent current)

p. 27

Limiting current p. 27

Acceleration ramp time p. 27

Initial starting torque p. 27

Selection of the type of stop p. 28

Calculated motor thermal protection p. 28

Reset motor thermal state p. 28

Motor thermal protection with PTC probes p. 28

Starter thermal protection p. 28

Motor underload protection p. 29

Excessive acceleration time protection p. 29

Current overload protection p. 29

Protection against line phase inversion p. 29

Time before restarting p. 29

Motor phase loss detection p. 29

Automatic restart p. 29

Torque limit p. 30

Voltage boost level p. 30

Test on low power motor p. 30

Activation of the cascade function p. 30

Line frequency p. 30

Reset kWh or the operating time p. 30

Return to factory settings p. 30

2nd motor adjustment functions p. 30

Communication functions p. 31

POWERSUITE® advanced dialog solutions p. 31

Application monitoring functions

Logic input application functions p. 31 2-wire/3-wire control p. 32

Freewheel stop p. 32

External fault p. 32

Force to local control mode p. 32

Reset motor thermal fault p. 32

Activation of the cascade function p. 32

Reset all faults p. 32

Logic output application functions p. 33

Relay and analog output application functions p. 33

Function compatibility table p. 33

Starter factory setting The starter is supplied ready for use in most applications. The main functions enabled and the default function values are as follows:

Current setting with POWERSUITE® on PPC

26

• Nominal motor current (depends on the starter rating)

• RUN and STOP logic inputs: 2-wire or 3-wire control via wiring

• Limiting current: 400%

• Logic input LI3: forced freewheel stop

• Acceleration ramp time: 15 s • Initial starting torque: 20%

• Logic input LI4: local mode control (serial link disabled)

• Selection of the type of stop: freewheel stop

• Logic output LO1: thermal motor alarm

• Motor thermal protection: class 10

• Logic output LO2: motor powered

• Time before restarting: 2 s

• Relay output R1: fault relay

• Motor phase loss threshold: 10%

• Relay output R3: motor powered

• Line frequency: automatic

• Analog output: motor current

© 2002 Schneider Electric All Rights Reserved

09/02

Page 27

ALTISTART® 48 Soft Start Functions Functions

Adjustment functions

Cn

• Nominal motor current (maximum continuous current) The nominal current of the starter can be adapted to the nominal motor current indicated on the rating plate. Adjustment range: 0.4 to 1.3 times the starter nominal current.

100 80 60

• Limiting current The maximum starting current can be adjusted. Adjustment range: 150% to 700% of the nominal motor current set and limited to 500% of the maximum permanent current defined for the starter rating.

tq0 = 40

40 20 0 0

• Acceleration ramp time During the starting phase, the ATS48 controller applies a torque ramp to the motor. The time (ACC) set corresponds to the time taken by the ramp to reach the nominal torque (starting at 0). Adjustment range: 1 to 60 s.

ACC

Acceleration ramp during time ACC with initial starting torque Iq0 = 40% of the nominal motor torque

• Initial starting torque The initial torque tq0 applied to the motor can be used to instantly overcome any resistive starting torque. Adjustment range: 0 to 100% of the nominal motor torque.

% Cn 100

• Selection of the type of stop Three types of stop are available for selection:

80

40, Freewheel motor stop

End of controlled deceleration

60 EdC

20 0 t dEC Decelerated stop by torque control during time dEC with threshold Edc for changing to freewheel stop mode Edc = 40% of nominal motor torque, Motor stop by deceleration via torque control (pump application) This type of stop enables a centrifugal pump to be decelerated gradually on a ramp in order to avoid a sudden stop. It can be used to dampen the hydraulic transient in order to significantly reduce pressure surges. The deceleration ramp time (dEC) can be adjusted. During deceleration, the pump flow rate decreases and becomes negligible at a certain speed. To continue to decelerate would serve no purpose. A torque threshold (EdC) can be set at which the motor will change to freewheel stop mode, avoiding the unnecessary heating of the motor and the pump., INTELE™ braking The braking torque level (brc) can be adjusted. The dynamic braking time (T1) corresponds to the time taken to decelerate from 100% to 20% of the nominal motor speed. To improve braking at the end of deceleration, the starter injects a DC current for an adjustable period of time (T2). It produces less motor heating than traditional DC injection braking.

100 % brc = 20

Consult the Square D/Schneider Electric Product Support Group (1-800565-6699) for criteria to be met for this feature.

brc = 100

20 %

0 T1

T2 t

INTELE™ braking stops for different braking torque levels brc

09/02

© 2002 Schneider Electric All Rights Reserved

27