For the Telemecanique Altistart 48 ATS48
Page 19
ALTISTART® 48 Soft Start Mounting Mounting
MOUNTING THE REMOTE KEYPAD DISPLAY VW3G48101
2.2 55.6
2.05 52
0.95 24
3.13 79.6 inches mm
4xØ3.5
A
Ø36
MOUNTING RECOMMENDATIONS • Install the ATS48 Soft Start vertically, within ± 10˚. • Do not place the ATS48 Soft Start adjacent to or above heating elements. • Leave sufficient free space to ensure that the air required for cooling can circulate from the bottom to the top of the unit.
4 100
Note: The IP 00 version of the ATS48 Soft Start must be fitted with a protective bar to protect personnel against electrical contact. Protective covers are available for the ATS48C14YU to ATS48C32YU. They should be ordered separately.
2 50
0.4 10
4 100
2 50 inches mm
Characteristics: pages 4 to 7
09/02
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
19
Page 20
ALTISTART® 48 Soft Start Mounting Mounting
MOUNTING IN A METAL WALL-MOUNTED OR FLOOR-STANDING ENCLOSURE WITH DEGREE OF PROTECTION TYPE 1 (IP 23) OR TYPE 12 (IP 54) • Observe the mounting recommendations on the previous page. • To ensure proper air circulation in the starter:, Fit ventilation grilles, Ensure that there is sufficient ventilation. If there is not, install forced ventilation with a filter. The openings and/or fans must provide a flow rate at least equal to that of the starter fans (see the table below) • Use special filters with Type 12 (IP 54) protection. Fan flow rate depending on the starter rating ATS48 starter
CFM
Flow rate m3/hour
ATS48D32YU and D38YU
24
14
ATS48D47YU
48
28
ATS48D62YU to C11YU
146
86
ATS48C14YU and C17YU
235
138
ATS48C21YU to C32YU
476
280
ATS48C41YU to C66YU
1020
600
ATS48C29YU to M12YU
2040
1200
Metal wall-mounted or floor-standing enclosure with Type 12 (IP 54) degree of protection For non-ventilated ATS48 controllers (ATS48D17YU and 48D22YU), install a fan ≤ 2" (50 mm) below the starter to circulate the air inside the enclosure in order to avoid hot spots. Calculating Enclosure Size The maximum allowable thermal resistance of the enclosure equation, Rth (˚C/W), is calculated as follows: Rth = θ – θe P
θ = maximum temperature inside enclosure in ˚C θe = maximum external temperature in ˚C P = total power dissipated in the enclosure in W
• The starter/motor combinations on pages 12 and 13 can be used in ambient temperatures ≤ 40 ˚C. • For temperatures between 40 ˚C and 60 ˚C, derate the maximum permanent current of the starter by 2% for every degree above 40 ˚C. • For the power dissipated by the starters at rated load: see pages 12 and 13. • If the starts are infrequent, it is recommended to use a shorting/bypass contactor with the ATS48 controller at the end of start to minimize heat dissipation. Calculate minimum useful heat exchange surface area requirement, S (in2): S=K Rth
Rth = Thermal resistance of the enclosure (calculated previously) K = Thermal resistance per square inch of the enclosure K = 186 with enclosure fan K = 233 without enclosure fan Compare to the effective heat exchange surface area to the proposed wall mounted enclosure, S (in2) which should be less than: S = (Front area) + (Top area) + 2 (Side area) Characteristics: pages 4 to 7
20
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
09/02
Page 21
ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams
Nonreversing with Shunt Trip Fault Isolation Circuit Breaker * w/Shunt Trip *
A2
A
1/L1
2/T1
3/L2
4/T2
B2
AC LINE SUPPLY
B
M
C2 5/L3
C
6/T3
FU4
SC 2
CL1
{
TO CONTROL POWER TRANSFORMER
GND
FU5 CL2 STOP
SC
STOP ATS48 CONTROLLER
RUN SC
RUN
1
RESET (IF USED)
T1
LI3 120V FU1
SEE DETAIL B
FU5
FU4
FAULT (R1C) (R1A)
LI4
+24V TRIP RELAY
*
TR
LO+
3 TS1
LO1
TR
CB SHUNT TRIP COIL
*
*
ST
LO2
(2 SEC) G MOTOR THERMAL SW 4
PROGRAMMABLE ANALOG OUTPUT (IF USED)
RUN
5
SEE DETAIL A (A)
*
AO1
{
COM
RUN COMMAND
*
RCR
RELAY
PTC1
(B) (C)
TS1
PTC2
RCR
R1A
END START UP (R2C) (R2A)
SHORTING CONTACTOR
*
SCA
FAULT R1C
PILOT RELAY
3
R2A
TS1 SCA
2
SHORTING CONTACTOR
*
SC
R2C
R3A
TS4
R
END START UP
R3C
*
PROGRAMMABLE N.O. CONTACT
POWER ON
DETAIL A 2-WIRE CONTROL W / O AUTO
2-WIRE CONTROL W / AUTO OFF HAND
ON
OFF
AUTO
STOP
(B)
START
(A) (A)
USER SUPPLIED
OR
(A)
1
Control circuit connection for 460 V operation. Reconnect as required for other voltages.
2
For shorting contactor operation, add SC with associated control circuit. Relay contact located on ATS48 controller.
3-WIRE CONTROL
(B)
(B)
OR
3 (C)
4
Located at motor. Jumper if switch not present.
5
Use RCR relay logic for ATS48 2-wire or 3-wire control when using shorting contactor.
DETAIL B
STOP
STOP
RUN
RUN OR
RCR +24V
Characteristics: pages 4 to 7
09/02
OFF
ON
* = User supplied
+24V
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
21
Page 22
ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams
Nonreversing with Isolation Contactor SW
*
A2
*
FU6 A
IC
*
1/L1
2/T1
IC
3/L2
4/T2
B2
FU7
AC LINE SUPPLY
B
M
C2
FU8
6/T3
5/L3
IC
C
FU4
SC FU2
CL1
{
TO CONTROL POWER TRANSFORMER
GND
FU5 CL2
FU3 2
SC
STOP ATS48 CONTROLLER
SC
RUN
1 T1
RESET (IF USED) LI3
120V FU4
FU1
LI4
RCR
FU5
+24V
MOTOR THERMAL SW
SEE DETAIL A (A)
4
RUN COMMAND RELAY
*
RCR
LO+
(B) (C)
TS1
LO1
RCR LO2
FAULT (R1C) (R1A)
FAULT RELAY
*
FR
PROGRAMMABLE ANALOG OUTPUT (IF USED)
3 TS1 FR
RCR IC
AO1
{
COM
ISOLATION
*
PTC1
CONTACTOR
PTC2
TS2
5 END START UP (R2C) (R2A)
R1A SCA
SHORTING CONTACTOR
*
FAULT R1C
PILOT RELAY
3 TS1 SCA SC
*
R2A 2
SHORTING CONTACTOR
R2C
TS4
R3A
*
POWER ON
W
*
FAULT
*
RUN
R
END START UP
R3C
PROGRAMMABLE N.O. CONTACT
FR
IC G
1
Control circuit connected for 460 V operation. Reconnect as required for other voltages.
2
For shorting contactor operation add SC with associated control wiring. Relay contact located on ATS48 controller.
3 DETAIL A 2-WIRE CONTROL W / O AUTO
2-WIRE CONTROL W / AUTO OFF HAND
OFF
AUTO
3-WIRE CONTROL
ON
STOP
(B)
START
(A) (A)
USER SUPPLIED
OR
(A)
(B)
(B)
OR (C)
Characteristics: pages 4 to 7
22
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
4
Located at motor. Jumper if switch not present.
5
Set RCR time slightly longer than expected deceleration time from rated speed to zero speed. The time delay RCR contact may be omitted if the configuration of the R1 relay is changed to isolating relay mode.
* = User supplied
Wiring Diagrams: pages 21 to 24
09/02
Page 23
ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams
Reversing with Isolation Contactors SW
*
A2
*
FU6 A
IC1
*
1/L1
2/T1
IC1
3/L2
4/T2
B2
FU7
AC LINE SUPPLY
B
M
C2
FU8
IC1
C
*
IC2 FU2
6/T3
5/L3
SC
FU3
2
IC2
SC SC
IC2 1 T1
FU4
120V FU4
FU1
FU5
MOTOR THERMAL SW
(B)
(C) (D)
(R1A)
FAULT
RUN FWD
*
ATS48 CONTROLLER
RELAY RUN
RFR
TS1
1
RESET (IF USED)
RFR
LI3 RRR
(E)
CL2
STOP RFR
SEE DETAIL A
GND
FU5
RRR
(A) 4
CL1
{
TO CONTROL POWER TRANSFORMER
RUN REV RELAY
*
RRR
IC1
RFR
IC2
LI4 RRR
TS1
(R1C) FR
2 +24V
FAULT
*
RELAY
3
LO+
3
TS1 RFR
FR
KM2
5
IC1
LO1
FORWARD CONTACTOR
*
4
Located at motor. Jumper if switch not present.
5
Set RFR time slightly longer than the expected deceleration time from rated forward speed to zero speed.
6
Set RRR time slightly longer than the expected deceleration time from rated reverse speed to zero speed.
7
Remove these contacts to inhibit direction reversal without first depressing STOP push button.
LO2 TS2 RRR
6
KM1 IC2
REVERSING PROGRAMMABLE CONTACTOR ANALOG OUTPUT (IF USED)
*
AO1
{
COM
TS2
END START UP (R2C) (R2A)
SCA
*
3
SHORTING CONTACTOR
PTC1
PILOT RELAY
PTC2
TS1 SCA
R1A
2 SC
SHORTING
*
CONTACTOR R1C
FAULT
TS4 R2A R
*
POWER ON R2C
END START UP
FR
*
FAULT
*
RUN FORWARD
*
RUN REVERSE
W
R3A
Control circuit connected for 460 V operation. Reconnect as required for other voltages. For shorting contactor operation, add SC with associated circuitry. Relay contact located on ATS48 controller.
* = User supplied
R3C
IC1 G
PROGRAMMABLE N.O. CONTACT
IC2 A
DETAIL A 2-WIRE CONTROL W / AUTO START AUTO DIRECTION
HAND (A)
FWD
AUTO F
REV
FWD
(B)
OFF
REV
STOP (B) (A)
(A)
R
RUN REV
7
(D) USER SUPPLIED R
RUN FWD
OFF
USER SUPPLIED
HAND
(B)
AUTO
FWD
REV (B)
(A) (C) (D)
F
USER SUPPLIED (D)
7
09/02
2-WIRE CONTROL W / AUTO START MANUAL DIRECTION
3-WIRE CONTROL
2-WIRE CONTROL W / O AUTO
OFF
(D)
(E)
© 2002 Schneider Electric All Rights Reserved
23
Page 24
ALTISTART® 48 Soft Start Recommended Wiring Diagrams Recommended Wiring Diagrams
Description of Logic for Recommended Wiring Diagrams Item
Name
Description
IC1 IC1A
Isolation Contactor (Fwd)
The isolation contactor logic closes IC1 upon a start command and opens IC1 after the stop is complete. The RCR (or RFR and RRR for reversing) are timed contacts that must have a time delay greater than the deceleration ramp time or the dynamic braking time. When a coast stop is selected, the time delay must be set for a time that will allow a complete decay of the motor residual voltage. The isolation contactor will open immediately upon a fault. The pilot relay (IC1A) is required when the IC1 contactor coil exceeds the relay rating.
IC2 IC2A
Isolation Contactor (Rev)
Used for reversing applications only, the IC2 must be mechanically interlocked to IC1. A reversing contactor may be used for the combination of IC1 and IC2. In general, the operation of IC2 is identical to IC1. The pilot relay (IC1A) is required when the IC1 contactor coil exceeds the relay rating.
SC SCA
Shorting Contactor & Pilot Relay
The shorting contactor is used to reduce the heat dissipated by the controller when the motor is operating at full speed and voltage. The starter provides proper sequencing of this contactor by the “end-start-up” relay. When the start is completed, the shorting contactor will be commanded to close. The starter will continue to monitor the motor thermal state and provide motor overload protection. Upon a stop command, the SC contactor will open, transferring the motor current to the Scars to allow for controlled deceleration if desired. The pilot relay (SCA) is required when the SC contactor coil exceeds the relay rating.
TS
Transient Suppressors
Transient suppression of all relay and contactor coils (except ST) is recommended to minimize the possibility of electrical interference with the starter electronics and to increase relay contact life.
RCR
Run Command Relay
Used in all non-reversing logic (optional in shunt trip) for proper sequencing of contactor logic. When energized, RCR initiates the start sequence. When de-energized, stopping is initiated. Operator controls can be either on/off selector switch, HOA selector switch or start/stop push buttons. RCR remains energized during a fault. Once the fault condition has been cleared, RCR must be de-energized by a “stop” command then re-energized to restart the controller.
RFR
Run Forward Relay
Used for reversing applications only, this coil duplicates the functionality of RCR for the forward direction and is interlocked with the RFR relay.
RRR
Run Reverse Relay
Used for reversing applications only, this coil duplicates the functionality of RCR for the reverse direction and is interlocked with the RRR relay.
ST
Shunt Trip Coil
This coil is attached to the shunt trip coil on the disconnect and will energize 2 seconds after a starter fault by the TR timer contact. The time delay is to prevent nuisance tripping of the circuit breaker during controller power-up or during line undervoltage conditions.
TR
Trip Relay
Used in shunt trip circuit breaker logic only; coil energized upon a starter fault.
FR
Fault Relay
Used with logic diagrams that use an isolation contactor. The fault relay is energized during normal operation and deenergizes if the starter fault contacts open or if the motor thermal switch (if supplied) opens. FR also provides additional contacts for the starter fault output.
Suggested Components for Standard Duty Applications
575 V
ALTISTART® Controller ATS ATS48 Soft Starter Device Rated Current Model @40 ˚C ■
FU4/FU5 ATS Control Power Burden (VA)
Class CC Control Fuse Size @208/230 V @460/575 V
10
15
ATS48D17YU
17
25
0.25 A
0.25 A
15
20
ATS48D22YU
22
25
0.25 A
0.25 A
10
20
25
ATS48D32YU
32
25
0.25 A
0.25 A
10, 25
30
ATS48D38YU
38
25
0.25 A
0.25 A, 15
30
40
ATS48D47YU
47
25
0.25 A
0.25 A
15
20
40
50
ATS48D62YU
62
25
0.25 A
0.25 A
20
25
50
60
ATS48D75YU
75
25
0.25 A
0.25 A
25
30
60
75
ATS48D88YU
88
25
0.25 A
0.25 A
30
40
75
100
ATS48C11YU
110
25
0.25 A
0.25 A
40
50
100
125
ATS48C14YU
145
25
0.25 A
0.25 A
50
60
125
150
ATS48C17YU
170
25
0.25 A
0.25 A
60
75
150
200
ATS48C21YU
210
25
0.25 A
0.25 A
75
100
200
250
ATS48C25YU
250
25
0.25 A
0.25 A
100
125
250
300
ATS48C32YU
320
25
0.25 A
0.25 A
125
150
300
350
ATS48C41YU
410
25
0.25 A
0.25 A
150, 350
400
ATS48C48YU
480
25
0.25 A
0.25 A, 200
400
500
ATS48C59YU
590
25
0.25 A
0.25 A
200
250
500
600
ATS48C66YU
660
25
0.25 A
0.25 A
250
300
600
800
ATS48C79YU
790
25
0.25 A
0.25 A
350
350
800
1000
ATS48M10YU
1000
25
0.25 A
0.25 A
450
1000
1200
ATS48M12YU
1200
25
0.25 A
0.25 A
Induction Motor M Rated hp r 208 V 230 V
460 V
3
5
5
7.5
7.5
400 r ■
Motor full load currents through 500 hp @ 460/575 V, 250 hp @ 230 V, and 200 hp @ 208 V are taken from the Canadian Electrical Code. Above these ratings, motor full load currents are calculated based upon 1.2 A/hp for 460 V and 2.4 A/hp for 230 V. Motors listed are for standard duty applications. For severe duty applications, select the next larger controller size. The ambient temperature indicated in the table represents the temperature of the air surrounding the ATS48 controller. Any additional temperature factors associated with the enclosure system or actual installation ambient temperature must be considered when determining the actual rated current (ICL) of the starter. For operating ambient above 40 ˚C without a shorting/ bypass contactor and 50 ˚C with a shorting/bypass contactor but not exceeding 60 ˚C, the rated current (ICL) of the starter must be de-rated by 2% per ˚C.
NOTE: To select control operators (push buttons, pilot lamps, and selector switches), control power transformers, and wire management devices (control and power terminal strips, wire terminations) indicated on the recommended wiring diagram configurations, visit www.schneider-electric.ca.
24
© 2002 Schneider Electric All Rights Reserved
09/02
Page 25
ALTISTART® 48 Soft Start Recommended Component Lists Recommended Component Lists
Additional Suggested Components for Standard Duty Applications Contactors a, b, c
ATS
Disconnect d
IC2
Isolation Contactor
Reversing Contactor e
Mechanical Interlock
Shorting Power Fuses Contactor (AC1) Class/Rating
Ferraz Shawmut fuses or Fuse Block f equivalent
Molded Case Switch g
Thermal Magnetic g
D17Y
LC1D18
LC1D18 h
LC1D18
J / 25
AJT25
60308J
FHL36000M
FAL36030
D22Y
LC1D25
LC1D25 h
LC1D25
J / 30
AJT30
60308J
FHL36000M
FAL36040
D32Y
LC1D32
LC1D32 h
LC1D32
J / 40
AJT40
60608J
FHL36000M
FAL36050
D38Y
LC1D40
LC1D40 h
LC1D40
J / 50
AJT50
60608J
FHL36000M
FAL36060
D47Y
LC1D50
LC1D50 h
LC1D50
J / 60
AJT60
60608J
FHL36000M
FAL36080
D62Y
LC1D65
LC1D65 h
LC1D65
J / 80
AJT80
61038J
FHL36000M
FAL36090
D75Y
LC1D80
LC1D80 h
LC1D80
J / 100
AJT100
61038J
FHL36000M
FAL36100
D88Y
LC1D80
LC1D80 h
LC1D80
J / 120
AJT125
62003J
KHL36000M
KAL36110
C11Y
LC1D115
LC1D115 h
LC1D115
J / 150
AJT150
62003J
KHL36000M
KAL36150
C14Y
LC1D150
LC1D150 h
LC1D150
J / 200
AJT200
62003J
KHL36000M
KAL36200
C17Y
LC1F185
LC1F185
LA9FF970
LC1F185
J / 225
AJT225
64033J
LHL36000M
LAL36225
C21Y
LC1F265
LC1F265
LA9FG970
LC1F265
J / 300
AJT300
64033J
LHL36000M
LAL36250
C25Y
LC1F265
LC1F265
LA9FJ970
LC1F265
J / 350
AJT350
64033J
LHL36000M
LAL36350
C32Y
LC1F400
LC1F400
LA9FJ970
LC1F400
J / 400
AJT400
64033J
LHL36000M
LAL36400
C41Y
LC1F400
LC1F400
LA9FJ970
LC1F400
J / 500
AJT500
6633J
MHL36000M
MAL36500
C48Y
LC1F500
LC1F500
LA9FJ970
LC1F500
J / 600
AJT600
6633J
MHL360006M
MAL36600
C59Y
LC1F630
LC1F630
LA9FJ970
LC1F630
L / 700
A4BQ700 f
MHL360008M
MAL36800
C66Y
LC1F800
LC1F800
LA9FJ970
LC1F800
L / 900
A4BQ900 f
MHL360008M
MAL36900
C79Y
LC1BL33
LC1BL33
LA9FL970
LC1BL33
L / 1100
A4BQ1200 f
MHL36000M i
M10Y
LC1BL33
LC1BL33
LA9FL970
LC1BL33
L / 1350
A4BQ1350 f
MHL36000M i
M12Y
LC1BP33
LC1BP33
LA9FX970
LC1BP33
L / 1600
A4BQ1600 f
NCL3600012M i
ATS48 Model a. b. c. d. e.
f. g.
h. i.
SC
Circuit Breaker
IC1
Fusible Disconnect
All coils are selected for 120 V, 60 Hz operation. Refer to the Industrial Control Products Catalogue for additional coil voltages or auxiliary contact configurations. One block may be added to each contactor. Power terminals are not included with LC1-F contactors. For additional ordering information visit www.schneider-electric.ca. The use of transient suppressors across all contactor coils is recommended. Refer to the latest editions of Schneider Electric’s full line product catalogs for selection of transient suppressors. According to the Canadian Electrical Code, branch circuit overcurrent protection must be provided for each controller. Short circuit protective devices recommended in this table are within CEC requirements for Type 1 coordination. Reversing contactors for C11 through M12 controllers must be assembled from components. Parts quantities for a basic contactor assembly, minus the power connection links and terminals, are indicated before each part number. Refer to the latest editions of Schneider Electric’s full line product catalogs for power connector link and terminal kits. Reversing contactor interlock units used for the C79 through M12 controllers are designed for vertical interlocking of the individual contactors. Horizontally interlocked contactors are used for D17 through C59 controllers. Fuse holder part number references are for Class J fuses only based on Ferraz Shawmut spring reinforced with box type connectors acceptable for Al/Cu wiring. Class L fuses require bolton connections to user-supplied power bus work. The molded case switches and circuit breakers selected require the addition of operator mechanisms to allow operation from the exterior of an enclosure. Refer to the latest editions of Schneider Electric’s full line product catalogs for operator mechanism information. When using a shunt trip relay for SCR fault isolation, order a disconnect switch with suffix -1021 for addition of shunt trip coil. The D Line contactor is available as a reversing configuration. For these applications, change the IC1 part number prefix from LC1- to LC2- to order the IC1 and IC2 combination complete with mechanical interlocks. Devices rated above 660 A have not been coordinated with circuit breakers. You must use a Class L fuse for overcurrent protection with ATS48 soft starter models C79, M10, and M12.
Characteristics: pages 4 to 7
09/02
Dimensions: pages 17 to 18
© 2002 Schneider Electric All Rights Reserved
Wiring Diagrams: pages 21 to 24
25
Page 26
ALTISTART® 48 Soft Start Functions Functions
Summary of functions Description
See pages
Starter factory setting p. 27
Adjustment functions
Protection functions
Advanced adjustment functions
Nominal motor current (maximum permanent current)
p. 27
Limiting current p. 27
Acceleration ramp time p. 27
Initial starting torque p. 27
Selection of the type of stop p. 28
Calculated motor thermal protection p. 28
Reset motor thermal state p. 28
Motor thermal protection with PTC probes p. 28
Starter thermal protection p. 28
Motor underload protection p. 29
Excessive acceleration time protection p. 29
Current overload protection p. 29
Protection against line phase inversion p. 29
Time before restarting p. 29
Motor phase loss detection p. 29
Automatic restart p. 29
Torque limit p. 30
Voltage boost level p. 30
Test on low power motor p. 30
Activation of the cascade function p. 30
Line frequency p. 30
Reset kWh or the operating time p. 30
Return to factory settings p. 30
2nd motor adjustment functions p. 30
Communication functions p. 31
POWERSUITE® advanced dialog solutions p. 31
Application monitoring functions
Logic input application functions p. 31 2-wire/3-wire control p. 32
Freewheel stop p. 32
External fault p. 32
Force to local control mode p. 32
Reset motor thermal fault p. 32
Activation of the cascade function p. 32
Reset all faults p. 32
Logic output application functions p. 33
Relay and analog output application functions p. 33
Function compatibility table p. 33
Starter factory setting The starter is supplied ready for use in most applications. The main functions enabled and the default function values are as follows:
Current setting with POWERSUITE® on PPC
26
• Nominal motor current (depends on the starter rating)
• RUN and STOP logic inputs: 2-wire or 3-wire control via wiring
• Limiting current: 400%
• Logic input LI3: forced freewheel stop
• Acceleration ramp time: 15 s • Initial starting torque: 20%
• Logic input LI4: local mode control (serial link disabled)
• Selection of the type of stop: freewheel stop
• Logic output LO1: thermal motor alarm
• Motor thermal protection: class 10
• Logic output LO2: motor powered
• Time before restarting: 2 s
• Relay output R1: fault relay
• Motor phase loss threshold: 10%
• Relay output R3: motor powered
• Line frequency: automatic
• Analog output: motor current
© 2002 Schneider Electric All Rights Reserved
09/02
Page 27
ALTISTART® 48 Soft Start Functions Functions
Adjustment functions
Cn
• Nominal motor current (maximum continuous current) The nominal current of the starter can be adapted to the nominal motor current indicated on the rating plate. Adjustment range: 0.4 to 1.3 times the starter nominal current.
100 80 60
• Limiting current The maximum starting current can be adjusted. Adjustment range: 150% to 700% of the nominal motor current set and limited to 500% of the maximum permanent current defined for the starter rating.
tq0 = 40
40 20 0 0
• Acceleration ramp time During the starting phase, the ATS48 controller applies a torque ramp to the motor. The time (ACC) set corresponds to the time taken by the ramp to reach the nominal torque (starting at 0). Adjustment range: 1 to 60 s.
ACC
Acceleration ramp during time ACC with initial starting torque Iq0 = 40% of the nominal motor torque
• Initial starting torque The initial torque tq0 applied to the motor can be used to instantly overcome any resistive starting torque. Adjustment range: 0 to 100% of the nominal motor torque.
% Cn 100
• Selection of the type of stop Three types of stop are available for selection:
80
40, Freewheel motor stop
End of controlled deceleration
60 EdC
20 0 t dEC Decelerated stop by torque control during time dEC with threshold Edc for changing to freewheel stop mode Edc = 40% of nominal motor torque, Motor stop by deceleration via torque control (pump application) This type of stop enables a centrifugal pump to be decelerated gradually on a ramp in order to avoid a sudden stop. It can be used to dampen the hydraulic transient in order to significantly reduce pressure surges. The deceleration ramp time (dEC) can be adjusted. During deceleration, the pump flow rate decreases and becomes negligible at a certain speed. To continue to decelerate would serve no purpose. A torque threshold (EdC) can be set at which the motor will change to freewheel stop mode, avoiding the unnecessary heating of the motor and the pump., INTELE™ braking The braking torque level (brc) can be adjusted. The dynamic braking time (T1) corresponds to the time taken to decelerate from 100% to 20% of the nominal motor speed. To improve braking at the end of deceleration, the starter injects a DC current for an adjustable period of time (T2). It produces less motor heating than traditional DC injection braking.
100 % brc = 20
Consult the Square D/Schneider Electric Product Support Group (1-800565-6699) for criteria to be met for this feature.
brc = 100
20 %
0 T1
T2 t
INTELE™ braking stops for different braking torque levels brc
09/02
© 2002 Schneider Electric All Rights Reserved
27