The text of a manual · part 4 of 4
ALTISTART 48 Soft Start Catalogue, pages 28 to 36
Pages 28 to 36 of 36
The original document is the PDF (3.6 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Telemecanique Altistart 48 ATS48
Page 28
ALTISTART® 48 Soft Start Functions Functions
Protection Functions t(s) 10000
The ATS48 Soft Start offers functions for protecting the motor and the machine.
1000
100
Class 30 25 20 15 10
10
10A
2
1 0.5 1.12
2.00
3.00
4.00
5.00
6.00
7.00
Id/In 8.00
Motor thermal protection curves (cold)
• Calculated motor thermal protection The starter continuously calculates the temperature rise of the motor based on the nominal current which has been set and the actual current absorbed. In order to adapt the ALTISTART to individual motors and applications, several protection classes are offered in accordance with standard IEC 60947-4-2: Class 30, Class 25, Class 20 (severe duty application), Class 15, Class 10 (standard duty application), Class 10 A, sub-class 2. Different protection classes are defined for the starting capacities of the motor: - cold start without thermal fault (corresponding to a stabilized motor thermal state, motor switched off) - warm start without thermal fault (corresponding to a stabilized motor thermal state, at nominal power) The motor thermal protection function can be disabled. After the motor has stopped or the starter has been switched off, the thermal state is calculated even if the control circuit is not energized. The ATS48 controller’s thermal control prevents the motor from restarting if the temperature rise is too high. If special motors are used which do not have thermal protection via curves, provide external thermal protection via probes or thermal overload relays. The starter is factory preset to Class 10. The tripping curves are based on the relationship between the starting current Is and the (adjustable) nominal motor current In. Trip time (cold) Trip time for a standard duty application (class 10) Is = 3 In Is = 4 In Is = 5 In 46 s 23 s 15 s t(s) 10000
Trip time for a severe duty application (class 20) Is = 3.5 In Is = 4 In Is = 5 In 63 s 48 s 29 s
Trip time (warm) 1000
Trip time for a standard duty application (class 10) Is = 3 In Is = 4 In Is = 5 In 23 s 12 s 7.5 s
Trip time for a severe duty application (class 20) Is = 3.5 In Is = 4 In Is = 5 In 32 s 25 s 15 s
100
• Reset motor thermal state Activating the function resets the motor thermal state calculated by the starter to zero.
Class
• Motor thermal protection with PTC (1) probes The starter integrates the processing of PTC probes, thus avoiding the use of an external device. The “PTC probe thermal overshoot” fault or alarm can be indicated using a configurable logic output or displayed via the serial link. The 30 function can be disabled. 25 20 Note: The “PTC probe protection” and “calculated motor thermal protection” 15 functions are independent and can be active simultaneously. 10
10
10A 1 0.5 1.12
2.00
3.00
4.00
5.00
6.00
Motor thermal protection curves (warm)
7.00
2 8.00 Id/In
• Starter ventilation The cooling fan on the starter is switched on as soon as the heatsink temperature reaches 50 ˚C. It is switched off when the temperature returns to 40 ˚C. Starter thermal protection The starter is protected against thermal overloads by an analog thermal probe. (1)
28
PTC: Positive Temperature Coefficient
© 2002 Schneider Electric All Rights Reserved
09/02
Page 29
ALTISTART® 48 Soft Start Functions Functions
Protection functions (continued) C
• Motor underload protection The starter detects a motor underload if the motor torque falls below a preset torque threshold (LUL) for a specific (adjustable) period of time (tUL). The motor underload threshold can be set between 20% and 100% of the nominal motor torque. The permissible underload duration can be set between 1 and 60 s. The detection function can trigger an alarm or a fault. The detection function can be disabled. The “motor underload detected” alarm can be ULL t indicated by a configurable logic output and/or displayed via the serial link in the state of the starter. The “motor underload detected” fault (ULF) locks the starter and can be displayed via the serial link.
(Cn) 100 % LUL + 10 % LUL t < tUL tUL
20 %
Motor underload detection (ULL)
• Excessive acceleration time protection This protection function can be used to detect a start which takes place in adverse conditions. Examples of such conditions include a locked rotor or a motor unable to reach its nominal rotation speed. If the start duration is greater than the value set (between 10 and 999 s), the drive changes to fault mode. The function can be disabled.
I 300 %
LOC LOC -10 % 50 % t < tOL tOL t
OIL Motor overcurrent detection (OIL)
• Current overload protection The starter detects a current overload if the motor current exceeds a preset overcurrent threshold (LOC) for a specific (adjustable) period of time (tOL). The overcurrent threshold can be set between 50% and 300% of the nominal motor current. The permissible overcurrent duration can be set between 0.1 and 60 s. This function is only active in steady state. The detection function can trigger an alarm or a fault. It can also be disabled. The “current overload detected” alarm can be indicated by a configurable logic output and/or displayed via the serial link. The “current overload detected” fault (OLC) locks the starter and can be displayed via the serial link in the state of the starter. • Protection against line phase inversion This function can be used to detect the direction of rotation of the motor phases and, if it is enabled, to indicate a fault when the direction of rotation is reversed. • Time before restarting This function can be used to avoid several consecutive starts which may cause: - the thermal overheating of the application, which is not permitted - a thermal fault which will require maintenance work to be carried out - overcurrents (if the direction of rotation is reversed) or repeats (run/stop commands) Following a stop command, the motor can only restart once the preset time delay has elapsed. The motor is restarted once the time delay has elapsed if a run command is still valid or if a new run command is sent. Adjustment range: 0 to 999 s.
Configuring the starter overload and underload with POWERSUITE® on a PC
• Motor phase loss detection The function is used to adjust the sensitivity of the protection function in order to detect a loss of current or a low current in one of the three motor phases for at least 0.5 s or in all three motor phases for at least 0.2 s. The value of the minimum current level can be set between 5% and 10% of the starter nominal current. • Automatic restart After locking on a fault, the function permits up to six restart attempts at intervals of 60 s if the fault has disappeared and the run commands are still present. After the sixth attempt, the starter will remain locked and the fault will have to be reset before a restart is permitted. If the function is active, the fault relay remains activated if line phase loss, motor phase loss or line frequency out of tolerance faults are detected. This function can only be used in 2-wire control.
09/02
© 2002 Schneider Electric All Rights Reserved
29
Page 30
ALTISTART® 48 Soft Start Functions Functions
Advanced adjustment functions • Torque limit Designed primarily for high inertia and constant torque conveyor applications, the function restricts the torque ramp reference to the preset value. For example, the function can be used to limit the torque to a constant value throughout the starting period. Adjustment range: 10% to 200% of the nominal motor torque. C
• Voltage boost level The function can be used to avoid any “starting” torque (phenomenon caused by friction on stopping or by mechanical play). When a run command is sent, the starter applies a fixed voltage to the motor for a limited period of time before starting. The function can be disabled. The voltage setting value varies between 50% and 100% of the nominal motor voltage.
Cd
100 % Un
Torque Ramperamp de couple 50 % Un
100 ms
Application of a voltage boost equal to 100% of the nominal motor voltage t
• Test on low power motor This function can be used to test a starter on a motor whose power is very much lower that of the starter. It can be used for example to check the electrical wiring of a device. The function is automatically cancelled when the starter is switched off. The next time the starter is switched on, the starter returns to its initial configuration. • Activation of the cascade function This function can be used to start and decelerate several cascaded motors with a single starter. In order to gain maximum benefit from torque control, it is advisable to use motors with powers between 0.5 and 1 times the power of the motor. • Line frequency The following frequencies can be selected for the function: - 50 Hz. The frequency fault monitoring tolerance is ± 20%. - 60 Hz. The frequency fault monitoring tolerance is ± 20%. - Automatic detection of the line frequency by the starter The frequency fault monitoring tolerance is ± 6%., 50 Hz and 60 Hz are recommended if the power supply is provided by a emergency standby generator set, given their high tolerance. • Reset kWh or the operating time Sets the value of the power in kW/h or the operating time value to 0. The calculation of the values is updated once the reset command has been sent. • Return to factory settings The function can be used to reset each setting to its initial value (starter factory setting, see page 26). 2nd motor adjustment functions In order to access the 2nd motor adjustment functions, one logic input must be assigned to the second set of motor parameters function. The adjustment functions and ranges are identical for both sets of motor parameters. The settings are as follows (see page 27):, Nominal motor current, Limiting current, Acceleration ramp time, Initial starting torque, Deceleration ramp time, Threshold for changing to freewheel stop mode at the end of deceleration, Maximum torque limit
30
© 2002 Schneider Electric All Rights Reserved
09/02
Page 31
ALTISTART® 48 Soft Start Functions Functions
Communication functions The ATS48 Soft Start is supplied with an RS-485 multidrop serial link with MODBUS® Systems protocol as standard. The serial link is configured in the Communication menu using: • The address of the starter, which can be set between 0 and 31 • The communication speed, which can be set at: 4800, 9600 or 19200 bps • The format of the communication data. The following formats can be selected: - 8 data bits, odd parity, 1 stop bit - 8 data bits, even parity, 1 stop bit - 8 data bits, no parity, 1 stop bit - 8 data bits, no parity, 2 stop bits • The time-out, which can be set between 1 and 60 s POWERSUITE® advanced dialog solutions The POWERSUITE® advanced dialog solutions (see pages 15 and 16) offer the following advantages: • Connection to the ATS48 Soft Start and access to the adjustment, monitoring and control functions • Display of messages in plain text in 5 languages (English, French, German, Spanish and Italian) • Preparation and saving of settings to hard disk • Comparison and editing of settings using office automation tools • Downloading of starter settings to the PC and uploading from the PC to the starter Application monitoring functions The monitoring functions provide the following information: • Power factor, displayed between 0.00 and 1.00 Displaying the commands and settings with POWERSUITE® on PC
• Motor thermal state: 100% corresponds to the thermal state of the motor consuming the permanently set nominal current • Motor current: displayed in amperes between 0 and 999 A and in kA between 1000 and 9999 A • The operating time corresponding to the total number of starter operating hours during heating, acceleration, steady state, deceleration, braking and continuous bypass operation. It is displayed in hours between 0 and 999 hours and in kilo hours between 1000 and 65536 hours.The active power is displayed between 0 and 255%, where 100% corresponds to the power at the set nominal current and at full voltage. • The motor torque is displayed between 0 and 255%, where 100% corresponds to the nominal torque. • The active power consumed is displayed in kW. The line voltage value must be configured. The accuracy of this setting will depend on the error between the voltage configured and the actual voltage. • Energy in kWh displayed with POWERSUITE® • The following starter states are shown in the display of the current state:
Monitoring the parameters with POWERSUITE® on PPC, Starter without run command and power not supplied, Starter without run command and power supplied, Acceleration/deceleration in progress
09/02
© 2002 Schneider Electric All Rights Reserved
31
Page 32
ALTISTART® 48 Soft Start Functions Functions, Steady state operation, Braking in progress, Starter in current limiting mode, Starting time delay not elapsed • Last fault. Displays the last fault which occurred. • Phase rotation direction. Displays the direction of rotation (direct or indirect). • Keypad display locking code, An access code can be used to protect access to the adjustment and configuration parameters of the starter. Only the monitoring parameters will then be visible. Logic input application functions The starter has 4 logic inputs: • 2 logic inputs (RUN and STOP) are reserved for run/stop commands which can be sent in the form of stay-put contacts or as pulsed contacts., 2-wire control: Starting and stopping are controlled by a single logic input. State 1 of the logic input controls starting and state 0 controls stopping., 3-wire control: Starting and stopping are controlled by 2 separate logic inputs. A stop is obtained on opening (state 0) the STOP input. The pulse on the RUN input is stored until the stop input opens. • 2 logic inputs (LI3 and LI4) can be configured with the following functions:, Freewheel stop: When combined with a braked stop or decelerated stop command, activating the logic input will stop the motor in freewheel mode. Assigning the logic inputs with POWERSUITE® on PPC, External fault: Enables the starter to detect an external user fault (level, pressure, etc.). When the contact is open, the starter changes to fault mode., Force to local control mode: If a serial link is used, this function can be used to change from line mode (control via serial link) to local mode (control via the keypad display)., Reset motor thermal fault: Enables the fault to be reset remotely., Activation of the cascade function: In this case, the motor thermal protection is disabled and relay R1 is configured as the fault isolation relay. Can be used to start and decelerate several motors one after the other with a single starter., Reset all faults: Enables all faults to be reset remotely., Second set of motor parameters: Enables a second set of parameters to be selected to start and decelerate two different motors with a single starter.
32
© 2002 Schneider Electric All Rights Reserved
09/02
Page 33
ALTISTART® 48 Soft Start Functions Functions
Logic output application functions The starter has 2 logic outputs (LO1 and LO2) which, depending on their configuration, can be used for remote indication of the following states or events: • Motor thermal alarm: The motor thermal state • has exceeded the alarm threshold and can be used for example to avoid starting a motor if the • thermal reserve is insufficient. • Motor powered: Indicates that there may be current in the motor.
Motor underload alarm: The motor torque is lower than the threshold set. Motor PTC probe alarm: The thermal state monitored by the PTC motor probe has been exceeded.
• Second set of motor parameters activated
• Motor overcurrent alarm: The motor current is higher than the threshold set. Relay and analog output application functions The starter has 3 relays, 2 of which are configurable. • End of starting relay R2: Cannot be configured. The end of starting relay controls the bypass contactor on the starter. It is activated when the motor has completed the starting phase. It is deactivated when a stop command is sent and in the event of a fault. The starter regains control when a braking or deceleration command is sent. • Relay R1 application functions Relay R1 can be configured as follows:, Fault relay: Relay R1 is activated when the starter is powered and there are no faults. It is deactivated when a fault occurs and the motor switches to freewheel mode., Isolating relay: The contact of relay R1 closes when a run command is sent and re-opens when a stop command is sent, at the end of deceleration on a decelerated stop or in the event of a fault. The line contactor is deactivated and the motor is isolated from the line supply. • Relay R3 application functions Relay R3 is configured to indicate the same states or events as logic outputs LO1 or LO2 (see above). • Analog current output AO application functions, The analog output AO provides an image of the following values: motor current, motor torque, motor thermal state, power factor, active power., The following settings are associated with the analog output: - the type of signal supplied: 0-20 mA or 4-20 mA - the scale setting of the signal. The function associates the maximum amplitude of the analog output (20 mA) with a percentage of the nominal value of the parameter, which can be set between 50% and 500%. Function Compatibility table Functions
Decelerating stop
INTELE™ braking stop
Forced freewheel stop
Thermal protection
Motor phase loss detection Tests on low power motor Cascaded motors
Decelerating stop
N/A
N
Y
Y
Y
Y
INTELE™ braking stop
N
N/A
Y
Y
Y
Y
Y
Forced freewheel stop
Y
Y
N/A
Y
Y
Y
N
Thermal protection
Y
Y
Y
Y
N/A
N/A
Y
N
Motor phase loss detection Y
Y
Y
N/A
N/A
Y
N/A
Tests on low power motor
Y
Y
Y
Y
Y
N/A
N
Cascaded motors
Y
Y
N
N
N/A
N
N/A
Y - Compatible functions
09/02
N - Incompatible functions
© 2002 Schneider Electric All Rights Reserved
N/A - Not applicable
33
Page 34
ALTISTART® 48 Soft Start Conventional Starting of Three-Phase Asynchronous Motors Conventional Starting of Three-Phase Asynchronous Motors
Direct starting
• Starting current: 4 to 8 times the nominal current
I/In
• Starting torque: 0.5 to 1.5 times the nominal torque
C/Cn
6
3
5
2.5
4
2
3
1.5
2
1
• Characteristics:, Motor with 3 terminals, low and medium power, On-load starting, High current peak and voltage drop, Simple device Cr 1
0.5, Sudden starting for the mechanism • No parameter adjustment
0
0
0.25 0.5
0.75
0
N/Ns
1
Starting current
0
0.25 0.5
0.75
N/N
1
Starting torque
Wye Delta starting
• Starting current: 1.8 to 2.6 times the nominal current
5
2.5
4
2
3
1.5
2
1
1
0.5
0
• Starting torque: 0.5 times the nominal torque
C/Cn 3
I/In 6
• Characteristics:, Motor with 6 terminals, No-load or low resistive torque starting, High current peaks and torque when changing to “star-delta” mode, A device requiring maintenance
0
N/Ns 0
0.25 0.5
0.75
1
Starting current
Cr, Subject to mechanical stress when starting • No parameter adjustment
0
0.25
0.5 0.75
1
N/Ns
Starting torque
Primary resistor starting
• Starting current: 4.5 times the nominal current • Starting torque: 0.5 to 0.75 times the nominal torque
C/Cn 3
I/In 6
• Characteristics: 5
2.5
4
2
3
1.5
2
1
1
0.5, Motor with 3 terminals, high power, Starting with increasing resistive torque, High current peak Cr, A large, bulky device requiring maintenance, Subject to mechanical stress when starting • No parameter adjustment
0
0
0.25 0.5
0.75
1
0
N/Ns
Starting current
0
0.25
0.5
0.75
1
N/Ns
Starting torque
Autotransformer starting 6
• Starting current: 1.7 to 4 times the nominal current • Starting torque: 0.4 to 0.85 times the nominal torque
C/Cn
I/In 3
5
2.5
4
2
3
1.5
2
1
1
0.5
• Characteristics:, Motor with 3 terminals, high power, Large voltage drop and current peak when connected at full voltage, A complex, bulky device requiring maintenance, Subject to mechanical stress when starting Cr
• No parameter adjustment
0 0
0.25 0.5 0.75
Starting current
34
1
N/Ns
0 0
0.25 0.5
0.75
1
N/Ns
Starting torque
© 2002 Schneider Electric All Rights Reserved
09/02
Page 35
ALTISTART® 48 Soft Start Conventional Starting of Three-Phase Asynchronous Motors
Conventional electronic starting with voltage ramp and current limit • A controller with 6 thyristors connected head-to-tail in each line phase is used to power the three-phase asynchronous motor by gradually increasing the voltage on start-up. M, Depending on the firing time and angle of the thyristors, it can be used to supply a voltage which will gradually increase at a fixed frequency.
3, The gradual increase in the output voltage can either be controlled by the acceleration ramp, or by the value of the limiting current, or linked to both parameters.
Schematic diagram α
α
Firing angle Id
• Figure 1 shows the behavior of the torque in relation to the starting current. Limiting the starting current Is to a preset value Is1 will reduce the starting torque Ts1 to a value which is almost equal to the ratio of the square of currents Is and Is1.
C
Example Id1 Cd
On a motor with the following characteristics: Ts = 2 Tn for Is = 6In, current limiting at Is1= 3 In or 0.5 Is results in a starting torque: Ts1 = Ts x (0.5)2 = 2 Tn x 0.25 = 0.5 Tn.
U
Cr
0.85 U Cr
• Figure 2 shows the torque/speed characteristic of a squirrel cage motor in relation to the supply voltage. The torque varies like the square of the voltage at a fixed frequency. The gradual increase in the voltage prevents the instantaneous current peak on power-up.
0.6 U
Cd1 0
N/Ns 0
0.25
Figure 1
0.5
0.75
1
0
N/Ns 0
0.25
0.5
0.75
1
Figure 2
Advantages of starting with the ATS48 Soft Start • Conventional electronic starting To rectify problems caused by: - mechanical stress when starting - hydraulic transients during acceleration and deceleration in pump applications Conventional electronic starting requires the use of several current limits or the switching of several voltage ramps. The settings become complicated and must be modified every time the load changes. • Starting with the ATS48 Soft Start The ATS48 controller’s torque control enables starting without mechanical stress and the smooth control of hydraulic transients with a single acceleration ramp. The settings are simple and effective, whatever the load.
09/02
© 2002 Schneider Electric All Rights Reserved
35
Page 36
A comprehensive range of Motor Starters Schneider’s regional focus Schneider is committed to supporting its customers at every stage of a project. Our dedicated sales engineers in the Canadian electrical industry operate from 27 regional sales and service centres. Our sales engineers are skilled at assessing individual requirements and combined with expert support of our product specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account.
Increase your performance with the associated TeSys components Circuit-breakers, Contactors, and Fuses up to the highest powers.
To access the expertise of the Schneider Electric locally, please contact the nearest regional customer centre. Each centre includes a product showroom for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing excellent meeting facilities.
Schneider Electric expertise in electrical distribution, industrial control and automation
With its brands, Federal Pioneer, Merlin Gerin, Modicon, Square D and Telemecanique, Schneider Electric offers a full range of products and services for end users, system integrators, OEMs, contractors, consulting engineers and the electrical supply industry for commercial and industrial applications. Contact Schneider Electric at www.schneider-electric.ca.
Schneider Electric Head Office 19 Waterman Avenue Toronto, Ontario M4B 1Y2 www.schneider-electric.ca Tel.: (416) 752-8020 Fax: (416) 752-6230 T8636CT0201EP R0
September, 2002
© 2002 Schneider Canada, All Rights Reserved
We provide electrical distribution, power quality, energy management, control and automation equipment for OEM's machinery, industrial and commercial facilities in Canada and around the world. Our products, systems and services help a wide range of companies improve quality, safety, and productivity. Our objective is to deliver comprehensive solutions wherever you do business.