The text of a manual · part 1 of 5
Series 965 User's Manual, pages 1 to 9
Pages 1 to 9 of 43
The original document is the PDF (401 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Watlow 965-3CA0-00RG
Page 1
Series 965 User's Manual
96 TOTAL
1/16 DIN Microprocessor-Based Auto-tuning Control
CUSTOMER SATISFACTION 3 Year Warranty
ISO 9001 Registered Company Winona, Minnesota USA
WatlowControls Watlow Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona, MN 55987-5580, Phone: 507/454-5300, Fax: 507/452-4507
0600-0003-0000 Rev. C July 1998 Supersedes: 0600-0003-0000 Rev. B
$10.00 Made in the U.S.A. Printed on Recycled Paper
Page 2
About This Manual Starting Out
How to Use this Manual We have designed this user's manual to be a helpful guide to your new Series 965. The headlines in the upper right and left corners indicate which tasks are explained on that page.
Notes and Safety Information NOTE: Details of a "Note" appear here, in the narrow box on the outside of each page.
We use notes, cautions and warnings throughout this book to draw your attention to important information. Notes are printed in bold in the margin to alert you to an important detail.
ç ç CAUTION: Details of a "Caution" appear here, in the narrow box on the outside of each page.
Ó
A Caution symbol (an exclamation point in a triangle) appears with information that is important to protect equipment and performance. Read and follow all cautions that apply to your application.
Ó A Warning symbol (a lightning bolt in a diamond) appears with information that is important to protect people and equipment from damage. Pay very close attention to all warnings that apply to your application.
Technical Assistance
WARNING: Details of a "Warning" appear here, in the narrow box on the outside of each page.
If you encounter a problem with your Watlow controller, review all of your configuration information for each step of the setup, to verify that your selections are consistent with your applications. If the problem persists after checking all the steps, call for technical assistance: Watlow Controls at (507) 454-5300, between 7:00 a.m. and 5:30 p.m. Central Standard Time. Ask for an applications engineer. When you call, have the following information ready: • the controller's model number ( the 12-digit number is printed on the top of the stickers on each side of the controller's case and on the top or right side of the circuit board); • this user's manual; • all configuration information; • the Diagnostics Menu readings.
Warranty and Returns For information about the warranty covering the Series 965, see page 37.
Comments and Suggestions We welcome your comments and opinions about this user's manual and the Series 965. Send them to the Technical Editor, Watlow Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona,MN 55987-5580.Orcall(507)454-5300.Orfaxthemto(507)452-4507. (1459).
2
WATLOW Series 965 User's Manual
How to Use the Manual
Page 3
Contents Starting Out Page
Item
Chapter 1 4 Starting Out With The Watlow Series 965 4 General Description Chapter 2 5 Install And Wire The Series 965 5 Panel Cutout 5 Dimensions 5 Installation Procedure 7 Wiring the Series 965 8 Sensor Installation Guidelines 8 Input Wiring 10 Output 1 Wiring 11 Alarm Wiring 12 System Wiring Example Chapter 3 13 How To Use The Keys And Displays 13 Keys, Displays & LEDs Chapter 4 14 How To Set Up The Series 965 14 Setting the Input Type DIP Switch 15 Entering Setup Menu 16 Setup Parameters 18 Setup Menu Table 19 Operation Parameters 20 Operation Menu Table Chapter 5 21 How To Tune And Operate 21 Auto-tuning 22 Manual Tuning 23 Manual and Automatic Operation 24 Using Alarms 25 Error Code Messages Appendix 1 27 Noise Sources 27 Decreasing Noise Sensitivity 28 Eliminating Noise Appendix 2 29 Entering the Calibration Menu 30 Restoring Factory Calibration 30 Calibration Menu
How to Use the Manual
31 34 36 37 38 39 40 41
Calibration Procedures Glossary Index Warranty and Returns Specifications Model Number Information Declaration of Conformity Quick Reference
Figures & Tables Page Figure 4 5 5 6 6 7 7 8 8 9 9 10 10 10 10 11 11 11 12 13 14 15 15 19 21 24 29 30
Item
Series 965 Input & Output Overview 1 Multiple Panel Cutout Dimensions 2 Series 965 Dimensions 3 Mounting, Case Side View & Collar 4 Case, Rear View & NEMA 4X Seal Example 5 High Voltage Power Wiring 6 Low Voltage Power Wiring 7 Thermocouple Sensor Input Wiring 8 0-5VÎ (dc) Process Sensor Input Wiring 9 2- or 3-wire RTD Sensor Input Wiring 10 4-20mA Process Sensor Input Wiring 11 Switched DC Output Wiring 12 5A Mechanical Relay Wiring 13 4-20mA Process Wiring 14 0.5A Solid-state Relay w/o Suppression Wiring 15 Switched DC Output Wiring 16 5A Mechanical Relay Wiring 17 0.5A Solid-state Relay w/o Suppression Wiring 18 System Wiring Example 19 Series 965 Keys and Displays 20 DIP Switch Location & Orientation 21 Entering the Setup Menu 22 The Setup Menu 23 The Operation Menu 24 Auto-tuning at a 200°F Set Point 25 Alarm Display Examples 26 Entering the Calibration Menu 27 Calibration Menu 28 Tables
18 Input Ranges 1 18 Setup Menu Prompts/Description 20 Operation Menu Prompts/Description
2 3
41 Quick Reference Sheet (Perforated)
WATLOW Series 965 User's Manual
3
Page 4
Starting Out Starting Out
Chapter 1 Starting Out With The Watlow Series 965, A Microprocessor-Based Control
Dual Control OutputPID or on/off, User Selectable
Single Input Type J, K, T, N or S Thermocouple, RTD or Process
Output 1 Heat or Cool Output 2 Heat, Cool, Alarm or None
Figure 1 Series 965 Input and Output Overview Output 1 or 2 Percent Power
Auto-tuning for Heat & Cool PID Settings
General Description Welcome to the Watlow Series 965, a 1/16 DIN microprocessor-based temperature control. The 965 has a single input which accepts type J, K, T, N or S thermocouple, RTD or process input. With dual output, the primary can be heating or cooling while the secondary can be a control output opposite the primary output (heat or cool), alarm or none. Both outputs can be selected as either PID or on/off. PID settings include proportional band, reset/integral, and rate/derivative. Setting the proportional band to zero makes the Series 965 a simple on/off control with switching differential selectable under the HSC parameter. Special 965 features include the NEMA 4X rating, dual four digit displays in either red or green, optional low volt power supply, auto-tuning for both heat and cool outputs, ramp to set point for gradual warm-up of your thermal system, and automatic/manual capability with bumpless transfer. Operator-friendly features include automatic LED indicators to aid in monitoring and setup, as well as a calibration offset at the front panel. The Watlow Series 965 automatically stores all information in a non-volatile memory.
4
WATLOW Series 965 User's Manual
Getting Started, Chapter 1
Page 5
Chapter 2
Installation
Install and Wire the Series 965 1.77" to 1.79" (44.96mm to 45.47mm)
Panel Cutout Your Panel Thickness
NOTE: Measurements between panel cutouts are the minimum recommended.
0.06" to 0.38" (1.5 to 9.7 mm)
1.77" to 1.79" (44.96mm to 45.47mm)
Figure 2 Series 965 Multiple Panel Cutout Dimensions
0.38" (9.65mm) Minimum 0.85" (20mm)
Figure 3 Series 965 Dimensions
4.7" (119mm)
2.1" (53 mm)
4.1" (104mm)
1.76" (45mm)
0.40" (10mm) 1.21" (31mm)
NOTE: For rapid mounting, use Greenlee punch #60020 and die #60021, or hand hydraulic unit, Kit #7306. All available from Grainger.
Installation Procedure Follow this procedure to mount the Watlow Series 965 temperature control: 1. Make a panel cutout per the dimensions in Figure 2. 2. Remove the 965 chassis from its case. Holding each side of the bezel, press in firmly on the side grips until the tabs release. Pull the chassis out of the case and set aside for later installation. 3. Make sure the rounded side of the external case gasket is facing the panel surface. Check to see that the gasket is not twisted, and is seated within the case bezel flush with the panel. Place the case in the cutout you just made. Make sure the gasket is between the panel cutout and the case bezel. See Figure 4A. Install and Wire, Chapter 2
WATLOW Series 965 User's Manual
5
Page 6
0 to 0.019 space (0 to 0.483 mm)
Installation
Panel
Ridges
Figure 4 Mounting, Case Side View & Collar Cross Section
4A
Bezel Tabs
Mounting Collar External Gasket
4B
Teeth
Mounting Collar Cross Section (notice the offset teeth on each tab)
4. While pressing the front of the case firmly against the panel, slide the mounting collar over the back of the control. The tabs on the collar must line up with the mounting ridges on the case for secure installation. See Figure 4A again. Slide the collar firmly against the back of the panel getting it as tight as possible. Make sure you cannot move the case within the cutout; if you can you do not have a NEMA 4X seal. NOTE: To guarantee a proper NEMA 4X seal, make sure the gasket between the panel and the rim of the case is not twisted and is seated properly. PRESS FIRMLY.
Figure 5 Case Rear View and NEMA 4X Seal Example
Now let's make sure we have a tight seal. Use your thumb to lock the tabs into place while pressing the case from side to side. Don't be afraid to apply enough pressure to install the control. The tabs on each side of the collar have teeth which latch into the ridges. See Figure 4B. Each tooth is staggered at a different height, so only one of the tabs on each side are ever locked into the ridges at any time. Looking at Figure 5, you see that the tabs on one side of the collar correspond with those on the opposite side. Make sure that the two corresponding tabs are the only ones locked in the ridges at the same time. If the matching tabs are not holding the case at the same time you will not have a NEMA 4X seal. You can make a visual check, or use your finger nail to pull out on each tab. Only one on each side is engaged, and they must be corresponding as in Figure 5. The space between the bezel and panel must be between 0 and 0.019" (0.48 mm). Make sure that the two corresponding tabs below are locked in the ridges at the same time.
NEMA 4X Seal Example.
When removing the mounting collar, we suggest sliding a thin tool such as a putty knife or screwdriver under all three tabs on each side at once and pulling it back off the case. 5. Insert the control chassis into its case and press the bezel to seat it. Make sure the inside gasket is also seated properly and not twisted. The hardware installation is complete. Proceed to the wiring section from here.
6
WATLOW Series 965 User's Manual
Install and Wire, Chapter 2
Page 7
Power Wiring
How to Wire the Series 965 The Series 965 wiring is illustrated by model number option. Check the unit sticker on the control and compare your model number to those shown here and also the model number breakdown in the Appendix of this manual. All outputs are referenced to a de-energized state. The final wiring figure is a typical system example. When you apply power without sensor inputs on the terminal strip, the Series 965 displays [----] in the upper display, and a [```0] in the lower display, except for 0-5VÎ (dc) or 4-20mA process input units. Press the A/M key twice, and [ER`7] is displayed for one second. This error indicates an open sensor or A/D error. Remove power to the control and connect the sensor properly, see pages 8 and 9. All wiring and fusing must conform to the National Electric Code and to any locally applicable codes as well.
High Voltage Model #
965A - 3
0 - 00
.
100 to 240 VÅ (ac), nominal (85 to 264 actual)
Ó WARNING: To avoid potential electric shock, use National Electric Code (NEC) safety practices when wiring and connecting this unit to a power source and to electrical sensors or peripheral devices.
NOTE: Taking the unit out of the case is not a normal operating condition and should only be done by a qualified maintenance installation technician. Power to the case should be disconnected before removing or installing the controller into its case.
Figure 6 High Voltage Power Wiring
Low Voltage Model #
965A - 3
1 - 00
.
Ó 12-24V‡ (ac/dc)
Figure 7 Low Voltage Power Wiring
Ó WARNING: If high voltage is applied to the low voltage unit, irreversible damage will occur.
Install and Wire, Chapter 2
WATLOW Series 965 User's Manual
7
Page 8
Input Wiring
Sensor Installation Guidelines We suggest you mount the sensor at a location in your process or system where it reads an average temperature. Put the sensor as near as possible to the material or space you want to control. Air flow past this sensor should be moderate. The sensor should be thermally insulated from the sensor mounting. See Chapter 4 for more information on DIP switch location and orientation.
Thermocouple Input NOTE: When an external device with a nonisolated circuit common is connected to the 420mA or dc output, you must use an isolated or ungrounded thermocouple.
Extension wire for thermocouples must be of the same alloy as the thermocouple itself to limit errors.
DIP Switch Orientation
Figure 8 Thermocouple Sensor Input Wiring
+
3
-
5
T/C
ç CAUTION: Process input does not have sensor break protection. Outputs can remain full on.
0-5VÎ (dc) Process Input
ç DIP Switch Orientation
Figure 9 0-5VÎ (dc) Process Sensor Input Wiring
+
3
-
5
Vdc
Input impedance: 10KΩ
8
WATLOW Series 965 User's Manual
Install and Wire, Chapter 2
Page 9
Input Wiring RTD, 2- or 3-wire There could be a + 2°F input error for every 1Ω of lead length resistance when using a 2-wire RTD. That resistance, when added to the RTD element resistance, will result in erroneous input to the instrument. To overcome this problem, use a 3-wire RTD sensor, which compensates for lead length resistance. When extension wire is used for a 3-wire RTD, all wires must have the same electrical resistance (i.e. same gauge, copper stranded, same length).
DIP Switch Orientation
S1
2
S1
2
S2
3
S2
3
S3
5
2-wire RTD Jumper Terminals 3 and 5.
3-wire RTD
S3
Figure 10 2- or 3-wire RTD Sensor Input Wiring
5
4 - 20mA Process Input
ç ç DIP Switch Orientation
-
CAUTION: Process input does not have sensor break protection. Outputs can remain full on.
2
Figure 11 4-20mA Process Sensor Input Wiring
I dc
+
5
Input impedance: 5Ω
Install and Wire, Chapter 2
WATLOW Series 965 User's Manual
9