Page 10

DC Output Output 1 Wiring Switched Model # 965A - 3 C

- 00

.

V+ unregulated

9

Figure 12 Switched dc Output Wiring

V - 10

Internal Circuitry

NOTE: When an external device with a nonisolated circuit common is connected to the 4-20mA or Switched dc output, you must use an isolated or ungrounded thermocouple.

+

10

-

External Load

Mechanical Relay Without Contact Suppression, Form C, 5 Amp Model # 965A - 3 D

- 00

.

Figure 13 5 Amp Mechanical Relay Wiring

NOTE: Switching inductive loads (relay coils, solenoids, etc.) with the mechanical relay, switched dc or solid-state relay output options requires using an R.C. suppressor. Watlow carries the R.C suppressor Quencharc brand name, which is a trademark of ITW Pakron. Watlow Part No. 0804-0147-0000.

9

8

NC

9

COM

Fuse L1

1 0 NO External Load

Customer Supplied Quencharc

L2

Process, 4-20mA Model # 965A - 3 F

- 00

.

Maximum load resistance: 800Ω

Figure 14 4-20mA Process Wiring

9

+

10

-

External Load

Solid-state Relay Without Contact Suppression, 0.5 Amp Model # 965A - 3 K Figure 15 0.5 Amp Solid-state Relay Without Contact Suppression Wiring

- 00

. Custommer Supplied Quencharc

L2

External Load 8

SS1 Fuse

1 0 SS1

10

WATLOW Series 965 User's Manual

L1

Install and Wire, Chapter 2

Page 11

Output 2 Wiring Switched DC Output Model # 965A - 3

C

- 00

NOTE: For more information on alarms see page 24.

. 6

+

7

-

External Load

Figure 16 Switched dc Output Wiring

V+ unregulated

6 V - 7

Internal Circuitry

Mechanical Relay Without Contact Suppression, Form C, 5 Amp Model # 965A - 3

D

- 00

Figure 17 5 Amp Mechanical Relay Wiring

. Fuse

1 NC

6

COM

7

NO

L1

External Load L2

Customer Supplied Quencharc

Solid-state Relay Without Contact Suppression, 0.5 Amp Model # 965A - 3

K

- 00

.

1 SS2

L1 Fuse

7

NOTE: Switching inductive loads (relay coils, solenoids, etc.) with the mechanical relay, switched dc or solid-state relay output options requires using an RC suppressor. Watlow carries the RC suppressor Quencharc brand name, which is a trademark of ITW Pakron. Watlow Part No. 0804-0147-0000.

NOTE: Output is in open State in Alarm Condition.

SS2 External Load L2

Customer Supplied Custommer Supplied Quencharc Quencharc

Install and Wire, Chapter 2

Figure 18 0.5 Amp Solid-state Relay Without Contact Suppression Wiring

WATLOW Series 965 User's Manual

11

Page 12

Wiring Example

Ó

WARNING:

All wiring and fusing must conform to the National Electric Code NFPA70. Contact your local board for additional information. Failure to observe NEC safety guidelines could result in injury to personnel or damage to property.

Figure 19 System Wiring Example

ç

CAUTION:

Watlow mercury relay loads must have a unity power factor. For RESISTIVE LOADS ONLY.

L1 120VÅ (VAC) L2 Earth Ground

High Temperature Light Coil

High Limit Mechanical Controller

Fuse 11

12

SSR-240-10A-DC1 dc Input SSR

2

1

3

4

3 (+)

92A3-1DJ1-0000 Limit Control

Out

In 9 +

Heater

10 -

5 (-)

13

Red 965A-3CA0-0000 Rear View

10

11

+

-

Optional Normally Open Momentary Switch

Limit Sensor

Process Sensor

14

120VÅ (VAC) L1

1

L2

11 1

1 Not Used 2 S1, I3 S2, TC+, V+ 4 Not Used 5 S3, TC-, V-, I+ 6 Not Used 7 Not Used 8 Not Used 9 DC +1 10 DC -1 11 L1 12 L2

5

3

5

9 6

10 7

(+)

3-32VÎ (dc) In

(-)

SSR-240-10A-DC1 DC Input Solid-state Relay

1 CR-1 5

6 7

1

8

1

11

Out 24-240VÅ (ac)

9

1

8

12 13

13

(+)

14

10

10

(-)

15

11

13

10

17

2

2 Series 92 92A3-1DJ1-0000 Limit Control

3

4 1

Heater

2

14

9

12

WATLOW Series 965 User's Manual

(-)

Series 965 965A-3CA0-0000 Temperature control

3

4

11

12

2 4 (+)

2

965A-3CA0-0000

12

3

5

16 1CR 18 R High Temperature Light

2 2

Install and Wire, Chapter 2

Page 13

Keys/Displays

Chapter 3 How to Use the Keys and Displays After one minute with no key activations, the control reverts to the process value in the upper display and the set point in the lower display.

Upper Display Red or green, 0.3" (8 mm) high, seven segment, four digit LED display, indicating either process, actual temperature, the operating parameter values or an open sensor. When powering up, the Process display will be blank for five seconds. This display can be blank by setting [`dSP] to [`SEt]. See page 18.

L1 When lit, this LED tells you when Output 1 is energized.

Lower Display Red or green, 0.3" (8 mm) high, seven-segment, fourdigit LED display, indicating the set point, output value, parameters for data in the upper display, or error and alarm codes. This display can be blank by setting [`dSP] to [`Pro]. See page 18.

Mode Key Steps the control through the Operating Menu; also, in the Auto mode, new data is self entering in five seconds.

L2 When lit, this LED tells you when Output 2 is active. This output can be configured as a control or alarm output.

MN Lit when the control is in Manual operation. Press the A/M key twice to enter Automatic operation. When blinking, this indicates that pressing the A/M key toggles between Auto and Manual. After five seconds without pressing the A/M key, the LED stops blinking, and returns to its previous state.

Up-arrow Key Increases the value of the displayed parameter. A light touch increases the value by one. Holding the key down increases the value at a rapid rate. New data is self entering in five seconds.

Down-arrow Key Decreases the value of the displayed parameter. A light touch decreases the value by one. Holding the key down decreases the displayed value at a rapid rate. New data is self entering in five seconds.

Up-arrow/Down-arrow Keys When pressed simultaneously for three seconds, the Setup Menu appears displaying the [`LOC] parameter. Continue to press the Up-arrow/Down-arrow keys, and the Calibration Menu appears. Keys & Displays, Chapter 3

Figure 20 Series 965 Keys and Displays

A/M Key Pressed once, it clears any latched alarms and toggles between Auto and Manual mode. If pressed again within five seconds it will change from Auto to Manual or vice versa. While in Manual mode, percent power is in the lower display.

WATLOW Series 965 User's Manual

13

Page 14

Setup

Chapter 4 How To Set Up The Series 965 Setting up the Series 965 is a simple process. First set the DIP switches to match your input type. Refer to the orientation below and Page 16 for the In parameter. Next, configure the 965's features to your application in the Setup Menu, then enter values in the Operating Menu. Both tasks use the MODE key to move through the menus and the Up-arrow/Down-arrow keys to select data. Before entering information in the Setup menu, set the dFL parameter. If selected as US: °F, proportion band in degrees, reset rate are the defaults. If selected as SI: °C, proportional band in % of span, derivative and integral are the defaults. Changing the dFL prompt will set parameters to their factory default. Document all current parameter settings first. See Appendix 2 in the calibration section to change this parameter.

How to Set the Input Type DIP Switch

Ó WARNING: Remove power from the control before removing the chassis from the case or changing the DIP switches.

The Series 965 input type can be user selectable at any time via a Dual In-line Package (DIP) switch inside the control, located on the left (viewed from the bottom). To set the DIP switch, remove the control chassis from the case. Holding each side of the bezel, press in firmly on the side grips until the tabs release. You may need to rock the bezel back and forth several times to release the chassis. The locations of the board and switches appear in Figure 21. Refer to the input types below for DIP switch orientation. DIP switch selection must match the sensor selected under the In parameter in the Setup Menu. Set the software selection for the input type to match. See Page 16.

Figure 21 DIP Switch Location and Orientation

Control Chassis Bottom View

Input Types Thermocouple

14

WATLOW Series 965 User's Manual

RTD

Process

Setup, Chapter 4

Page 15

Setup Entering the Setup Menu The Setup Menu displays the parameters that configure the Series 965's features to your application. Enter the Setup Menu by pressing the Up-arrow and Down-arrow keys simultaneously for 3 seconds. The lower display shows the LOC parameter, and the upper display shows its current level. All keys are inactive until you release both keys. You can reach the LOC parameter from anywhere.

Figure 22 Entering the Setup Menu

You will not see all parameters in this menu, depending on the unit's configuration and model number. After stepping through the menu it returns to the control set point parameter under the Operation Menu.

M

= Parameter may or may not appear depending on your control configuration.

Mode Key

LOC

(

)

User lock out

HSA

(

)

Output hysteresis Output 22 alarm hysteresis

In

(

)

Input type

LAt

(

)

Latching for alarm dEC

(

)

Decimal place

SIL

(

)

Silence alarm

C_F

(

)

Celcius__Fahrenheit rtd

(

)

RTD calibration curve rL

(

)

Range low rP

(

)

Ramp function rH

(

)

Range high rt

(

)

Ramp rate

Ot 1

(

)

Output 1

PL

(

)

% Power limiting

HSC

(

)

Control hysteresis dSP

(

)

Display

Ot2

(

)

Output 2 75

Setup, Chapter 4

NOTE: While in the Setup Menu, all outputs are off.

Figure 23 The Setup Menu

Control Set Point

WATLOW Series 965 User's Manual

15

Page 16

Setup Setup Parameters When you are at the top of the menu, the Series 965 displays the user level of operation in the upper display, and the LOC parameter in the lower display. Press the MODE key and the value of the next parameter appears in the upper display, and the parameter appears in the lower display. LOC

NOTE: Set the LOC parameter value as the final step in programming the Series 965 controller to prevent locking yourself out of the Operations and Setup Menu during initial programming.

NOTE: Process input does not have sensor break protection or bumpless transfer.

Lock: Selects the level of operator lock-out as defined below. Range: 0 - 4 Default: 0 LOC 0: All operating parameters may be viewed or changed. Manual operation is permitted. When in manual operation, percent power is adjustable. Bumpless transfer to manual mode can occur on sensor break. LOC 1: The set point, actual, and alarm settings are the only visible parameters, set point is adjustable in this level. Manual operation and auto-tune are permitted. When in manual operation, percent power is adjustable. Bumpless transfer to manual mode can occur on sensor break. LOC 2: The set point, actual, and alarm settings are the only visible parameters, set point is adjustable in this level. Manual operation is permitted. When in manual operation, percent power is adjustable. Bumpless transfer to manual mode can occur on sensor break. LOC 3: The set point and actual are the only visible parameters, set point is adjustable in this level. Manual operation is not permitted. Bumpless transfer is defeated and outputs are disabled on sensor break. LOC 4: The set point and actual are the only visible parameters, set point is not adjustable in this level of lock-out. Manual operation is not permitted. Bumpless transfer is defeated and outputs are disabled on sensor break.

16

In

Input: Selects the sensor input type. The internal DIP switch must also match the In parameter. See Figure 21 on Page 14 for DIP switch orientation, and see Table 1 on Page 18 for input type temperature ranges. Range: J, K (appears as H), t, n, S, rtd, rt.d, 0-5, 420 Default: J dEC

Decimal: Selects the location of the decimal point for all process related data. This parameter only appears if the In parameter is 0-5 or 420. Make sure the internal DIP switch matches the In parameter. Range: 0, 0.0, 0.00 Default: 0

C_F

Celsius _ Fahrenheit: Selects the units of temperature measurement for the control. This parameter only appears if the In parameter is a thermocouple or RTD input. The default is dependent on the dFL parameter located in the Calibration menu. Refer to the Appendix. Range: C or F If dFL = US: Default: F If dFL = SI: Default: C rL

Range Low: Selects the low limit of the set point. Also used to set the low end of the process input. 0.0VÎ (VDC) and 4mA represent Range Low (rL) for process input. The process input is linearly scaled between rL and rH. See the model number and specification in the Appendix for range values, or refer to Table 1 on Page 18. Range: Sensor range low to rH Default: Low limit of sensor type/-500 for process input

WATLOW Series 965 User's Manual

Setup, Chapter 4

Page 17

Setup Range High: Selects the high limit of the operating range. Also used to set the high end of the process input. 5.0VÎ (dc) and 20mA represent Range High (rH) for process input. The process input is linearly scaled between rL and rH. See the model number and specification information in the Appendix for your range values, or refer to Table 1 on Page 18. Range: Sensor range high to rL Default: High limit of sensor type/9999 for process input Output 1: Selects the action for the primary output. Action in response to the difference between set point and process variable. Select ht (heat) for reverse acting or select CL (cool) for direct acting. Range: ht, CL Default: ht Hysteresis-Control: Selects the switching hysteresis for Output 1 and 2 when you select 0 (ON/OFF) under the Pb1 parameter and Ot2 = Con. Range: 1 to 99, 0.1 to 9.9, 0.01 to 0.99/1 to 55, 0.1 to 5.5, 0.01 to 0.55 Default: 3, 0.3, 0.03°F/2, 0.2, 0.02 Output 2: Selects the output action for the secondary output. Range: Con Control mode opposite Output 1 (heat or cool) Default: Con PrA Process alarm with alarm message displayed Pr Process alarm with no alarm message displayed dEA Deviation alarm with alarm message displayed dE Deviation alarm with no alarm message displayed no None Hysteresis - Alarm: Selects the switching hysteresis for Output 2 when Ot2 is an alarm. This parameter only appears if Ot2 ≠ Con or no. See Page 19 for the Pb1 parameter. Range: 1 to 9999, 0.1 to 999.9, 0.01 to 99.99/1 to 5555, 0.1 to 555.5, 0.01 to 55.5 Default: 3, 0.3, 0.03/2, 0.2, 0.02 Latching: Selects whether the alarm is latching or non-latching. Latching alarms must be cleared before the alarm output will reset. Non-latching automatically resets the alarm output when the condition clears. This parameter will not appear if Ot2 = Con or no. Range: LAt or nLA Default: nLA Silencing: Selects alarm silencing (inhibit) for the alarm. This parameter appears only when Ot2 = dEA or dE. For more information see Chapter 5, "Using Alarms." Range: On or OFF Default: OFF RTD: Selects the RTD calibration curve for RTD inputs. This parameter will not appear unless In = rtd or rt.d. JIS = 0.003916Ω/Ω°C, DIN = 0.003850Ω/Ω°C. Range: din or JIS Default: din Ramping: Choose Str, and the set point ramps at the selected rate in °/hr from process (actual) temperature to set point, when power is applied to the control (start up). It will not ramp with a set point change. On is the same as Str plus it ramps with a set point change. It ramps from the previous set point to a new one at the selected ramp rate. OFF is for no ramping action. When ramping, the lower display alternately flashes rP. The set point displayed is the desired end set point. The ramping setpoint is not shown. Entering the Setup menu or manual operation disables the outputs and ramp. Once you exit either one, the 965 controls to the last entered set point. Range: Str, On, OFF Default: OFF Rate: Selects the ramping rate in degrees per hour. This parameter will not appear if rP = OFF. Range: 0 to 9999 Default: 100°/hr

Setup, Chapter 4 rH

Ot1

HSC

Ot2

HSA

LAt

SIL rtd rP rt

WATLOW Series 965 User's Manual

17

Page 18

Setup PL dSP

Power Limiting: The power limiting function in % power for heat. Range: Dependent on output type. -100 to100 Default: 100 Display: Selects which displays are active or viewable. Five seconds after selected, the appropriate display goes blank. Press MODE, Up-arrow or Down-arrow to override this feature and cause the current value to be displayed for 5 seconds. Range: nor Normal displays Default: nor SEt Set Point - Lower display only Pro Process - Upper display only

Table 1 Input Ranges.

Table 2 Setup Menu Prompts and Descriptions.

Parameter

Input Type

Sensor Range Low

Sensor Range High

J K (appears as H) t n S rtd (1°) rt.d (0.1°) 4-20mA 0-5VÎ (dc)

32°F/0°C -328°F/-200°C -328°F/-200°C 32°F/0°C 32°F/0°C -328°F/-200°C -199.9/199.9 4mA/-999 units 0VÎ (dc)/-999 units

1382°F/750°C 2282°F/1250°C 662°F/350°C 2282°F/1250°C 2642°F/1450°C 1292°F/700°C 999.9/700.0 20mA/9999 units 5VÎ (dc)/9999 units

Setup Menu Value

Do not enter any values here; make photocopies instead. Range Factory Default Appears If:

LOC

0-4

0

In

J, K (appears as H), t, n, S, rtd, rt.d, 0-5, 420

J

DIP switch selectable.

dEC

0, 0.0, 0.00

0

In = 0-5 or 420

C_F

C or F

Dependent on dFL.

In = J,K,t,n,S,rtd,rt.d rL rL to rH

Input dependent.

rH rH to rL

Input dependent.

Ot1 ht or CL ht

HSC

1 - 99, 0.1 - 9.9, 0.01 - 0.99 1 to 55, 0.1 to 5.5, 0.01 to 0.55

3, 0.3, 0.03 3, 0.3, 0.03/2, 0.2, 0.02

Ot2

Con = Control PrA = Process Alarm Pr = Process with no alarm message dEA = Deviation alarm dE = Deviation with no alarm message no = None

Con

HSA

1 - 9999, 0.1 - 999.9, 0.01 - 99.99 1 - 5555, 0.1 - 555.5, 0.01 - 55.55

3, 0.3, 0.03°F 2, 0.2, 0.02°C

Ot2 ≠ Con or no

LAt

LAt or nLA nLA

Ot2 ≠ Con or no

SIL

On or OFF

OFF

Ot2 = dEA or dE rtd

JIS or din din

In = rtd or rt.d rP

Str = Ramping on power up on = Ramping to set point at all times OFF = None

OFF rt

0 to 9999

100°/hr

PL dSP

0 to 100 nor = normal SEt = Set Point (lower only) Pro = Process (upper only)

100 nor

18

WATLOW Series 965 User's Manual rP ≠ OFF

Setup, Chapter 4