The text of a manual · part 3 of 5

Series 965 User's Manual, pages 19 to 27

Pages 19 to 27 of 43

The original document is the PDF (401 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Watlow 965-3CA0-00RG

Page 19

Operation = Prompt appears or not according to control configuration. M

75

The upper display will always return to the process value after 1 minute without key strokes.

Control Set Point rE2/It2 ( )

Reset 1/Integral 1

Proportional band 1 rA2/dE2 ( )

Rate 2/Deviative 2 rE1/It1 ( )

Reset 1/Integral

Ct2

( )

Cycle time 2 rA1/dE1 ( )

Rate 1/Deviative 1

ALO

( )

Alarm low

AHI

( )

Alarm high

CAL

( )

Calibration offset

AUt

( )

Auto-tune

Pb1

NOTE:

( )

Ct1

( )

Cycle time 1

Pb2

( )

Proportional band 2

Figure 24 The Operation Menu.

Operation Parameters Set Point: Sets the operating set point for Output 1. Represents the process value the system tries to achieve for Output 1. "SP" does not appear, the control set point value will. The lower display may be blank if dSP = Pro. If in a ramping mode, the lower display alternately flashes the desired end set point and rP. Proportional Band 1 & 2 : A proportional band expressed in degrees or % of span, within which a proportioning function is active for Output 1 or 2. When Pb1 = 0, the unit functions as an on/off control on Output 1 and 2. Pb2 will not appear if Pb1 = 0 or Ot2 ≠ Con. The switching differential is determined by the HSC parameter. If dFL = US: Range Pb1: 0 to 999°F/0 to 555°C/0 to 999 Units; 0.0 to 9.9°F/ 0.0 to 5.5°C/0.0 to 9.9 units, Pb2: The same as Pb1 except lower limit is 1. Defaults: Pb1 = 25°F/2.5°F Pb2 = 25 If dFL = SI: Range: 0 to 999.9% of span Defaults: Pb1 = 3.0% Pb2 = 3.0% Reset /Integral 1 & 2: An integral control action for Output 1 or 2 that automatically eliminates offset, or "droop," between set point and actual process temperature. rE1/It1: Will not appear if Pb1 = 0. rE2/It2: Appears if Pb1 ≠ 0 and Ot2 = Con. Either reset (rE) or integral (It) will appear depending on how the dFL parameter is set in the Calibration menu. See Appendix II. If dFL = US: Range: 0 to 9.99 repeats/minute Default: 0.00 If dFL = SI: Range: 00.1 to 9.99 minutes per repeat Default: 0.00 Rate /Derivative 1 & 2 : The rate (derivative) function for Output 1 or Output 2. Eliminate over shoot on start up, or after the set point changes. rA1/dE1: Will not appear if Pb1 = 0. rA2/dE2: Appears if Pb1 ≠ 0 and Ot2 = Con. Either rate (rA) or derivative (dE) appears depending on how dFL is set in the Calibration menu. If dFL = US or SI: Range: 0 to 9.99 minutes Default: 0.00 Cycle Time 1 & 2: Time for a controller to complete one time proportioned cycle for Output 1 or Output 2; expressed in seconds. Ct1: Will not appear if Pb1 = 0, or Output 1 is 4-20mA. Ct2: Will not appear if Pb1 = 0 or Ot2 ≠ Con. If a mechanical relay or contactor is switching power to the load, a longer cycle time may be desirable to minimize wear on the mechanical components. Typical life of a mechanical relay is 100,000 cycles. Range: 0.1 to 999.9 Default: 5.0 Setup, Chapter 4

[SP ]

Pb1 Pb2 rE1/It1 rE2/It2 rA1/dE1 rA2/dE2

Ct1 Ct2

WATLOW Series 965 User's Manual

19

Page 20

Operation ALO

Alarm Low: Represents the low process alarm or low deviation alarm. This parameter will not appear if Ot 2 = no or Con. If Ot2 = dEA or dE: Range: -999 to 0 Default: -999 If Ot2 = PrA or Pr: Range: rL to AHI Default: rL

AHI

Alarm High: Represents the high process alarm or high deviation alarm. This parameter will not appear if Ot2 = no or Con. If Ot2 = dEA or dE: Range: 0 to 999 Default: 999 If Ot2 = PrA or Pr: Range: ALO to rH Default: rH

CAL

Calibration Offset: Adds or subtracts degrees from the input signal. Range: -180°F to 180°F/-100°C to 100°C/-180 units to 180 units; or -18.0°F to 18.0°F/-10.0°C to 10.0°C Default: 0

AUt

Auto-Tune: Initiates auto-tune. Range: 0 = off, 1 = slow, 2 = medium, 3 = fast

Table 3 Operation Menu Prompts and Descriptions.

Operation Parameters Pb1 rE1

It1 rA1 dE1 Ct1 Pb2 rE2 It2 rA2 dE2 Ct2 ALO - Deviation dE Process Pr AHI -

CAL AUt

20

Deviation dE Process Pr

Default: 0

Operation Menu Use this page as a master copy for your Series 965 Operation Parameters. Do not enter any values here; make photocopies instead. Value

Range If dFL = US: 0 - 999°F/0 - 555°C/0 - 999 Units 0 - 99.9°F/0 - 55.5°C/0 - 99.9 Units 0=ON/OFF control. HSC =switch diff. If dFL = SI: 0.0 to 999.9% of span 0.00 to 9.99 repeats/minute 0.00 = No Reset. Won't appear if Pb1 = 0 or dFL = SI. 0.0 - 99.9 minutes/rpt. 0.00 = No Integral. Won't appear if Pb1 = 0 or dFL = US. 0.00 to 9.99 minutes 0.00 = No Rate. Will not appear if Pb1 = 0 or dFL = SI. 0.00 - 9.99 minutes. 0.00 = No Derivative. Won't appear if Pb 1 = 0 or dFL = US. 0.1 to 999.9 Won't appear if Pb1 = 0, or 4-20mA. Same as Pb1. Pb2 lower limit = 1, 0.1, 0.01 Same range as rE1. Same range as It1. Same range as rA1. Same range as dE1. Same range as Ct1. -999 to 0 rL to AHI Will not appear if Ot2 = no or Con. 0 to 999 ALO to rH Will not appear if Ot2 = no or Con. ±18°F/±10°C/±18 Units 0-3

WATLOW Series 965 User's Manual

Factory Default 25°F 2.5°F

3% 0.00 repeats/minute

00.0 minutes/repeat 0.00 minutes

0.00 minutes 5.0 seconds

-999 rL 999 rH 0 0 Setup, Chapter 4

Page 21

Tuning

Chapter 5 NOTE: Set the HSC parameter under the Setup Menu to 3°F/2°C before auto-tuning your control.

How to Tune and Operate Auto-tuning (Heat and/or Cool) The Series 965 can automatically tune the PID parameters to fit the characteristics of your particular thermal system. The auto-tuning procedure operates on a thermal response value, slow, medium, or fast. Use the slow thermal response when your process does not need to reach set point too rapidly, or if it usually does not often exceed set point. A fast thermal response produces a rapid temperature change over a short period of time. Once the auto-tune sequence has begun, the Output 1 heat proportional band is set to 0 and the control goes into an on/off mode of control at 90% of the established set point. The displayed set point remains unchanged. Once the control finishes "learning" the system, it returns to a standard PID control with the PID values automatically set as a result of auto-tuning. See Manual Tuning on the next page to set the cool PID parameters. Any change of the set point, while in auto-tune, re-initiates the auto-tune procedure.

Auto-tuning at a Set Point of 200°F

Auto-tune Begins

Auto-tune Complete Set Point

200

Figure 25 Auto-tuning at a Set Point of 200°F.

°Temp

180 Process 100

90% of Set Point

°Time

In order for the 965 to successfully complete auto-tune, the process must cross 90% of set point four times within 80 minutes after auto-tune has started. If this does not happen within the 80 minute time limit, the Pb remains at 0 and the control functions in an on/off mode.

Tuning and Operating, Chapter 5

WATLOW Series 965 User's Manual

21

Page 22

Tuning To start auto-tuning: 1. Press the MODE key until the AUt prompt appears in the data display. 2.

Select a thermal response value, 1=slow, 2=medium, and 3=fast, using the Up-arrow/Down-arrow keys. A thermal response value of 2 satisfactorily tunes most thermal systems.

3.

Press the MODE key. While the control is in the tuning mode, the lower display alternately displays the normal information and the prompt At. The time between alternations is 1 second.

4.

When tuning is complete, the displays return to their previous state and AUt reverts to 0. The 965 installs appropriate PID tuning parameters and saves them in the non-volatile memory. If a mechanical relay or contactor is switching power to the load, a longer cycle time may be desirable to minimize wear on the mechanical components. Typical life of a mechanical relay is 100,000 cycles.

To abort auto-tuning either reset the AUt parameter to 0, press the A/M key twice, or cycle power off and on. In all cases, aborting auto-tune restores all values to those previous to auto-tuning.

Manual Tuning For optimum control performance, tune the Series 965 to your thermal system. The tuning settings here are for a broad spectrum of applications; your system may have somewhat different requirements. NOTE: This is a slow procedure, taking from minutes to hours to obtain optimum value. NOTE: Tune heating outputs at a set point above ambient temperature. Tune cooling outputs at a set point below ambient temperature.

1. Apply power to the Series 965 and enter a set point. Begin with these Operation parameters: Pb = 1, rE/It = 0.00, rA/dE = 0.00, Ct = 5.0, CAL = 0, AUt= 0. 2. Proportional Band Adjustment: Gradually increase Pb until the upper display temperature stabilizes to a constant value. The process temperature will not be right on set point because the initial reset value is 0.00 repeats per minute. (When Pb = 0; rE/It and rA/dE1 are inoperative, and the 965 functions as a simple ON/OFF control.) The HSC parameter determines the switching differential value. 3. Reset/Integral Adjustment: Gradually increase rE, or decrease It until the upper display temperature begins to oscillate or "hunt." Then slowly decrease rE or increase It until the upper display stabilizes again near set point. 4. Cycle Time Adjustment: Set Ct as required. Faster cycle times sometimes achieve the best system control. However, if a mechanical contactor or solenoid is switching power to the load, a longer cycle time may be desirable

22 WATLOW Series 965 User's Manual

Tuning and Operating, Chapter 5

Page 23

Tuning/Operation to minimize wear on the mechanical components. Experiment until the cycle time is consistent with the quality of control you want. Ct will not appear on units with a process output. 5. Rate/Derivative Adjustment: Increase rA/dE to 1.00 minute. Then raise set point by 20° to 30°F, or 11° to 17°C. Observe the system's approach to set point. If the load temperature overshoots set point, increase rA/dE to 2.00 minutes. Raise set point by 20 to 30°F, or 11 to 17°C and watch the approach to the new set point. If you increase rA/dE1 too much, approach to set point is very sluggish. Repeat as necessary until the system rises to the new set point without overshooting or approaching the set point too slowly. 6. Calibration Offset Adjustment: You may want your system to control to a temperature other than the value coming from the input sensor. If so, measure the difference between that temperature (perhaps at another point in the system) and the process value showing in the upper display. Then enter the CAL offset value you want. Calibration offset adds or subtracts degrees from the value of the input signal.

Manual and Automatic Operation To change from auto to manual operation, press the A/M key twice. Manual operation provides open loop control of the outputs from a range of -100% (full cooling) to 100% (full heating) power. The 965 allows a negative output value only with a Cl (Cool) selection on either Ot1 or Ot2 = Con. Automatic operation provides closed loop on/off or PID control. When the operator transfers from a closed loop to an open loop, the 965 retains the power level from the closed loop control, referred to as bumpless transfer. When the 965 returns to closed loop control, it restores the previous set point temperature.

NOTE: Process input does not have sensor break protection or bumpless transfer. Outputs selected as Ht (reverse acting) will be full on if sensor break occurs.

The MN LED indicates auto or manual operation. When the LED is on, the control is in manual operation. When the LED is off, it is in automatic operation. When the LED flashes, press the key again within five seconds to complete the change in operation. When a sensor opens, the 965 switches from automatic to manual operation if LOC = 0, 1 or 2. • If LOC = 0, 1 or 2 and the bumpless transfer conditions are met, process has stabilized at a ± 5% power level for a 2 minute period prior to sensor break provided the power level is less than 75%. The 965 switches to manual operation at the last automatic power level. • If LOC = 3 or 4, the 965 switches into manual operation at 0% power (outputs disabled). When transferring from auto to manual operation, the control output(s) remains stable ("bumpless," smooth transition). When transferring from manual to automatic operation, the control output(s) may change significantly. In manual operation, the output value appears in the lower display; in automatic operation, the set point appears. Tuning and Operating, Chapter 5

WATLOW Series 965 User's Manual

23

Page 24

Auto/Man-Alarms Using Alarms

NOTE: When the alarm output is deenergized, the NO contact is open in the alarm condition.

The Series 965 has two alarm types, Process or Deviation. A process alarm sets an absolute temperature. When the process exceeds that absolute temperature limit an alarm occurs. The process alarm set points may be independently set high and low. Under the Setup Menu, select the type of alarm output with the Ot2 parameter. PrA = Process Alarm Pr = Process alarm with no alarm message displayed A Deviation alarm alerts the operator when the process strays too far from set point. The operator can enter independent high and low alarm settings. The reference for the deviation alarm is the set point. Any change in set point causes a corresponding shift in the deviation alarm. dEA = Deviation Alarm dE = Deviation alarm with no alarm message displayed Example: If your set point is 100°F/38°C, and a deviation alarm is set at +7°F/ 4°C as the high limit, and -5°F/3°C as the low limit, the high alarm trips at 107°F/ 41.6°C, and the low alarm at 95°F/35°C. If you change the set point to 130°F/ 54.4°C, the alarms follow the set point and trip at 137°F/59°C and 125°F/51.6°C. Under the Setup Menu, select the type of alarm output with the Ot2 parameter. dEA = Deviation Alarm dE = Deviation alarm with no alarm message displayed Both process and deviation alarms can be latching or non-latching. When the alarm condition is removed a non-latching alarm automatically clears the alarm output. You must manually clear a latching alarm before it will disappear. Flashing "LO" or "HI" in the lower display indicates an alarm when Ot2 = PrA or dEA. The lower display alternately shows information from the current parameter and the "LO" or "HI" alarm message at one second intervals. The alarm output is de-energized and the L2 LED is lit. To clear an alarm… • First correct the alarm condition, then… • If the alarm is latching… Clear it manually; press the A/M key once as soon as the process temperature is inside the HSA parameter alarm limit. • If the alarm is non-latching… The alarm clears itself automatically as soon as the process temperature is inside the HSA parameter alarm limit.

Figure 26 Alarm Display Examples

24 WATLOW Series 965 User's Manual

Press once Clear a latched and corrected alarm.

Tuning and Operating, Chapter 5

Page 25

Error Codes Alarm Silencing is available with the deviation alarm. When SIL is selected as "on," the operator must manually disable the alarm by pressing the A/M key once on initial power up (in either the latching or non-latching mode). Alarm silencing disables the alarm output relay. However, the L2 LED (also the lower display when Ot2 = dEA) shows an alarm condition until the process value is within the "safe" region of the deviation alarm band. Once the process value crosses into the "safe" region, both a latching or a non-latching alarm is ready. Any future deviation outside this safe band triggers an alarm.

Error Code Messages ç Four dashes, "- - - -", in the upper display indicate a Series 965 error. The error code is visible in the lower display.

NOTE: An alarm display will be masked by an error condition or when the control is in the Calibration or Setup Menus.

Er 2 - Sensor underrange error (only applies to RTD units) The sensor input generated a value lower than the allowable signal range, or the A/D circuitry malfunctioned. Enter a valid input. Make sure the In parameter (selected in the Setup menu) and the DIP switch settings both match your sensor. Refer to the table below for the appropriate input type and range.

Er 4 - Configuration error The unit's microprocessor is faulty; call the factory.

Er 5 - Non volatile checksum error The nonvolatile memory checksum discovered a checksum error. Unless a momentary power interruption occurred while the unit was storing data, the nonvolatile memory is bad. Call the factory.

Er 6 - A/D underflow error

ç CAUTION: Electrical noise or a noise event, vibration or excess environmental moisture or temperature may cause Series 965 errors to occur. If the cause of an error is not otherwise apparent, check for these.

The A/D circuit is underrange. An open or reversed polarity sensor is the most likely cause. Check the sensor; if the connection is good and functions properly, call the factory. The A/D underrange voltage is too low to convert an A/D signal. Make sure the In parameter matches your sensor and DIP switches are set accordingly.

Er 7 - A/D overflow error The A/D circuit is overrange. An open or reversed polarity sensor is the most likely cause. Check the sensor; if the connection is good, and the sensor functions properly, call the factory. The A/D overrange voltage is too high to convert an A/D signal. Make sure the In parameter matches your sensor and DIP switches are set accordingly. Tuning and Operating, Chapter 5

WATLOW Series 965 User's Manual

25

Page 26

Error Codes Error Code Actions • Er 2, Er 6, Er 7 result in these conditions: • If operator access is LOC 0, 1 or 2 ... …and the control was in AUTO operation when the error occurred, it goes into manual (% power) operation. If the output power is less than 75% power, and a <5% change in power occurred within the last two minutes, the 965 switches into manual operation at the last automatic power level (bumpless transfer). If the control was in manual operation, it remains there. Press A/M twice to see the error code. The alarm output (if present) is in its alarm state (LED lit). The upper display reads "- - -". The lower display indicates the error code. If the control was operating with stable output values when the error occurred, it continues to operate at those levels on a % power basis. If output values were not stable, the control outputs go to 0% power (OFF). • If operator access is LOC 3 or 4… The control remains in auto operation and the outputs go off. The A/M and MODE keys are inactive. The Up-arrow/Down-arrow keys may be used simultaneously to enter the Setup Menu. The alarm output (if present) is in its alarm state (LED lit). The upper display reads "- - - -". The lower display indicates the error code. • To clear a corrected error… • Press M (Mode key).

• Er 4 and Er 5 result in these conditons: • The control is in auto operation with both outputs off. • The alarm output, if present, are in their alarm state (de-energized with the LED lit). • The upper display indicates the process value. • The lower display indicates the error code. • All keys are inactive. • All Setup Menu parameters return to default values. • The above conditions occur regardless of the value of LOC, or the presence of the Setup or Calibration Menus. • To clear a corrected error… • Cycle power to the control.

26 WATLOW Series 965 User's Manual

Tuning and Operating, Chapter 5

Page 27

Noise Guidelines

Appendix 1 Noise and Installation Guidelines For wiring guidelines, refer to the IEEE Standard No. 518-1982, available from IEEE, Inc. 345 East 47th Street, New York, NY 10017.

Noise Sources • Switches and relay contacts operating inductive loads such as motors, coils, solenoids, and relays, etc. • Thyristors or other semiconductor devices which are not zero crossover-fired (randomly-fired or phase angle-fired devices). • All welding machinery and heavy current carrying conductors. • Fluorescent and neon lights.

Decreasing Noise Sensitivity • Physical separation and wire routing must be given careful consideration in planning the system layout. For example, ac power supply lines should be bundled together and physically kept separate from input signal lines (sensor lines). A 12" (305 mm) minimum separation is usually effective. Keep all switched output signal lines (high power level) separate from input signal lines (sensor lines). Cross other wiring at 90° angles whenever crossing lines is unavoidable. • Look at the system layout; identify and locate electrical noise sources such as solenoids, relay contacts, motors, etc. Route the wire bundles and cables as far away as possible from these noise sources. Don't mount relays or switching devices close to a microprocessor control. Don't have phase angle-fired devices in the same electrical enclosure or on the same power line with the control. • Shielded cables should be used for all low power signal lines to protect from magnetic and electrostatic coupling of noise. Some simple pointers are: ◊ Whenever possible, run low level signal lines unbroken from signal source to the control circuit. ◊ Connect the shield to the control circuit common at the control end only. Never leave the shield unconnected at both ends. Never connect both shield ends to a common or ground. ◊ Maintain shield continuity at daisy chain connection points by reconnecting the broken shield. ◊ Assume no electrostatic shielding when using the shield as a signal return. If you must do this, use triaxial cable (electrostatically shielded coaxial cable).

Appendix

WATLOW Series 965 User's Manual

27