Page 28

Wiring Guide • Use twisted pair wire any time control circuit signals must travel over two feet, or when you bundle them parallel with other wires. • Select the size or gauge of wire by calculating the maximum circuit current and choosing the gauge meeting that requirement. Using greatly larger wire sizes than required generally increases the likelihood of electrostatic (capacitance) coupling of noise. • Eliminate ground loops in the entire control system. You can spot the obvious loops by studying the "as-built" wiring diagram. There are also notso-obvious ground loops resulting from connecting internal circuit commons in the manufacturer's equipment. • Do not daisy chain ac power (or return) lines, or output signal (or return) lines to multiple control circuits. Use a direct line from the power source to each input requiring ac power. Avoid paralleling L1 (power lead) and L2 (return lead) to load power solenoids, contactors, and control circuits. If an application uses L1 (power lead) to switch a load, L2 (return lead) has the same switched signal and could couple unwanted noise into a control circuit. • Tie all ground terminals together with one lead (usually green wire) tied to ground at one point. Don't connect ground to the control case if the control is in a grounded enclosure (preventing ground loops). • Do not confuse chassis grounds (safety ground) with control circuit commons or with ac supply L2 (return or neutral line). Each return system wiring must be separate. Absolutely never use chassis ground (safety) as a conductor to return circuit current.

Eliminating Noise • Use "snubbers" (QUENCHARC™ P/N: 0804-0147-0000) to filter out noise generated by relays, relay contacts, solenoids, motors, etc. A snubber is a simple filter device using a 0.1µf, 600 volt, non-polarized capacitor in series with a 100Ω, 1/2 watt resistor. The device can be used on ac or dc circuits to effectively dampen noise at its source. • The ultimate protection is an "uninterruptable" power supply. This "senses" the ac power line; when the line fluctuates, a battery powered 60Hz inverted circuit takes over, supplying power within one-half to one cycle of the ac line; very expensive.

28

WATLOW Series 965 User's Manual

Appendix

Page 29

Appendix 2

Calibration

Calibration Before attempting to calibrate, make sure you read through the procedures carefully and have the proper equipment called for in each procedure. Make sure the DIP switches are in the proper position per input type. See Figure 21, Page 14.

Entering the Calibration Menu In the Calibration Menu, various input signals must be supplied for the control to go through its auto calibration. The calibration menu can only be entered from the LOC parameter in the Setup Menu. Press the Up-arrow/Down-arrow keys simultaneously for 3 seconds (± 1 second). The CAL parameter appears in the lower display with "no" in the upper display.

Figure 27 Entering the Calibration Menu.

NOTE: Calibration values will not be retained unless you are in the MANUAL mode. Do not enter the MANUAL mode until you are at the correct input parameters.

Any inadvertent change in the displayed data, when pressing the Up-arrow/ Down-arrow keys, is ignored. Calibration values won't be retained unless you are in the manual mode. Press the Up-arrow/Down-arrow key to change the upper display to “YES.” Press MODE to enter the calibration sequence. NOTE: Upon entering the calibration menu, the upper display window indicates CAL. It continues to indicate CAL (with the exception of calibration of the 4-20mA output) while the operator walks through the entire calibration parameter list. While calibrating the 4-20mA output, the upper display contains a numeric value to be slewed up or down until the output value is correct. The control uses the lower display to prompt the user as to what the input should be.

While in the Calibration Menu, the control output(s) go off and the alarm output (if present) is on.

With the dFL parameter, select either U.S. parameters which include displaying °F, rate, reset, and proportional band in degrees or units. Or select SI (System International) and the displayed parameters are °C, integral, derivative, and proportional band in % of span. Once the information has been properly established and maintained for at least 5 to 10 seconds, the MODE key may then be used to display the next prompt. After the final input is established, press the MODE key twice to return the unit to the configuration menu at the top of the parameter list. Appendix

WATLOW Series 965 User's Manual

29

Page 30

Calibration

Restoring Factory Calibration The rSt parameter restores the factory calibration values to the Series 965. If you calibrate your control incorrectly, you have the option to default to the original values. Once you leave the CAL menu, the values are entered. 1. Press the Up-arrow/Down-arrow keys simultaneously for three seconds. The LOC parameter appears in the lower display. Continue holding the Uparrow/Down-arrow keys until the lower display reads CAL. 2. Press the Up-arrow key until YES appears in the upper display. 3. MODE through the calibration menu until rSt appears in the lower display. 4. Press the Up-arrow key until YES appears in the upper display. 5. Press the MODE key and the 965 advances to test the displays. This procedure is used only to restore calibration, it is not meant to clear values.

Calibration Menu (

)

YES to calibrate, No skips to display test.

0.00

(

)

50.0

(

)

Input 0.00mV for low input. Input 50.00mV for high input.

CAL No

Yes

Figure 28 Calibration Parameters tC

(

)

Connect a Type "J" ambient compensator with inputs shorted.

440

(

)

Set the low resistance to 44.01Ω.

255

(

)

Set the high resistance to 255.42Ω.

0.00

(

)

Set the voltage source to 0.000 volts.

5.00

(

)

Set the voltage source to 5.000 volts.

4.00

(

)

Set the current source to 4.00mA.

20.0

(

)

Set the current source to 20.00mA.

4A0

(

)

Enter 4-20mA output calibration value for 4mA.

2A0

(

)

Enter 4-20mA output calibration value for 20mA.

rSt

(

)

(

)

Restores factory calibration values. Factory use only. Select US (rate, reset, proportional band in degrees or units, °F) or SI (integral, derivative, proportional band in % of span, °C) Factory use only.

dSP dFL MEM

ç Before attempting to calibrate, make sure you have the proper equipment called for in each procedure. The Series 965 is calibrated and tested before leaving the factory. 30

WATLOW Series 965 User's Manual

Appendix

Page 31

T/C Calibration

Thermocouple Field Calibration Procedure Equipment Required • •

Type "J" Reference Compensator with reference junction at 32°F/0°C, or Type "J" Thermocouple Calibrator set at 32°F/0°C. Precision millivolt source, 0-50mV min. range, 0.01mV resolution

Setup And Calibration 1. Connect the AC line voltage L1 and L2 to the proper terminals. 2. Connect the millivolt source to Terminal 5 Negative and Terminal 3 Positive on the Series 965 terminal strip. Use regular 20 - 24 gauge wire. Make sure the DIP switch is set for thermocouple input, see Chapter 4. 3. Apply power to the unit and allow it to warm up for 15 minutes. After warm-up put the unit in the CAL menu. See Figure 27 on Page 29. Select YEs. 4. Press the A/M key twice to enter the MANUAL mode. The unit is calibrating when MN LED is on. Make sure the unit is in MANUAL mode only when you are in the correct parameters. 5. At the 0.00 prompt, enter 0.00mV from the millivolt source to the control. Allow at least 10 seconds to stabilize. Press the MODE key. 6. At the 50.0 prompt, enter 50.00mV from the millivolt source to the Series 965. Allow at least 10 seconds to stabilize. Press the MODE key. 7. At the tC prompt, disconnect the millivolt source, and connect the reference compensator or T/C calibrator to Terminal 5 Negative, and Terminal 3 Positive on the Series 965 terminal strip. If using a compensator, turn on and short the input wires. If using "J" calibrator, set to simulate 32°F/0°C. Allow 10 seconds for the control to stabilize. The unit will leave the CAL mode if 1 minute passes between key activations. To conclude the T/C calibration, advance the MODE key to the next prompt or exit the CAL menu. Press the A/M key twice to exit the MANUAL mode.

RTD Field Calibration Procedure Equipment Required •

1KΩ precision decade resistance box with 0.01Ω resolution.

Setup And Calibration 1.

Connect the ac line voltage L1 and L2 to the proper terminals.

2.

Connect the decade resistance box to Terminal 2, 3 and 5 on the terminal strip. Use regular 20 - 24 gauge wire of the same length and type. Make sure the DIP switch is set for RTD input, see Chapter 4.

3.

Apply power to the unit and allow it to warm up for 15 minutes. After warm-up put the unit in the CAL menu. See Figure 27 on Page 29. Select YEs. Press the MODE key until the 440 prompt is displayed.

4.

Press the A/M key twice to enter the MANUAL mode. The unit is calibrating when the MN LED is on. Make sure the unit is in MANUAL mode only when you are in the correct parameters.

5.

At the 440 prompt, set the decade resistance box to 44.01. Allow at least 10 seconds to stabilize. Press the MODE key to enter the calibration data. Press the A/M key twice to exit the MANUAL mode. The unit will leave the CAL mode if 1 minute passes between key activations. To conclude the RTD calibration, advance the MODE key to the next prompt or exit the CAL menu.

6.

At the 255 prompt, set the decade resistance box to 255.42. Allow at least 10 seconds to stabilize. Press the MODE key.

Appendix

NOTE: Before calibration on an installed control, make sure all data and parameters are documented. See Setup and Operation Tables, Pages 18 and 20.

NOTE: When the MN LED is on, the unit is automatically calibrating. Your sequence is VERY important. Always move to the next parameter before changing the calibration equipment.

WATLOW Series 965 User's Manual

31

Page 32

Process Input 0-5 Volt Input Field Calibration Procedure Equipment Required: NOTE:

•

Before calibration on an installed control, make sure all data and parameters are documented. See Setup and Operation Charts, Pages 18 and 20.

Precision DC voltage source 0-5 volt minimum range with 0.001 volt resolution.

Setup and Calibration 1. Connect the AC line voltage L1 and L2 to the proper terminals on the 965. 2. Connect the voltage/current source to Terminal 3 (+) and 5 (-) on the Series 965 terminal strip. Use regular 20 - 24 gauge wire. Make sure the DIP switch is set for process input, see Chapter 4. 3. Apply power to the unit and allow it to warm up for 15 minutes. After warm-up put the unit in the CAL menu. See Figure 27 on Page 29. Select YEs. Press the MODE key until 0.00 is displayed. 4. Press A/M twice to enter the MANUAL mode. The unit is calibrating when the MN LED is on. Make sure the unit is in the MANUAL mode only when you are in the correct parameters. See Figure 28 on Page 30. 5. At the 0.00 parameter, set the voltage source to 0.000 volts. Allow at least 10 seconds to stabilize. Press the MODE key. 6. At the 5.00 parameter, set the voltage source to 5.000VÎ (VDC). Allow at least 10 seconds to stabilize. The unit leaves the CAL mode if 1 minute passes between key activations. Press A/M twice to exit the MANUAL mode. To conclude the 0-5 Volt calibration, advance the MODE key to the next prompt or exit the CAL menu.

NOTE: When the MN LED is on, the unit is automatically calibrating. Your sequence is VERY important. Always move to the next parameter before changing the calibration equipment.

4-20mA Input Field Calibration Procedure Equipment Required: •

Precision current source 0-20mA minimum range with 0.01mA resolution.

Setup and Calibration 1. Connect the AC line voltage L1 and L2 to the proper terminals on the 965. 2. Connect the current source to Terminal 2 (-) and 5 (+) on the Series 965 terminal strip. Use regular 20 - 24 gauge wire. Make sure the DIP switch is set for process input, see Chapter 4. 3. Apply power to the unit and allow it to warm up for 15 minutes. After warm-up put the unit in the CAL menu. See Figure 27 on Page 29. Select YEs. Press the MODE key until 4 is displayed. 4. Press A/M twice to enter the MANUAL mode. The unit is calibrating when the MN LED is on. Make sure the unit is in the MANUAL mode only when you are in the correct parameters. See Figure 28 on Page 30. 5. At the 4.00 parameter, set the current source to 4.00mA. Allow at least 10 seconds to stabilize. Press the MODE key. 6. At the 20.0 parameter, set the current source to 20.00mA. Allow at least 10 seconds to stabilize. The unit leaves the CAL mode if 1 minute passes between key activations. Press A/M twice to exit the MANUAL mode. To conclude, advance the MODE key to the next prompt or exit the CAL menu.

32

WATLOW Series 965 User's Manual

Appendix

Page 33

4-20mA Output 4-20mA Output Field Calibration Procedure Equipment Required: • •

300Ω, 1/2 watt 10% resistor. 4 - 1/2 digit Digital Multimeter.

NOTE:

Setup And Calibration 1.

Connect the ac line voltage L1 and L2 to the proper terminals of the 965. See Chapter 2. Set the multimeter to measure current.

2.

Connect the multimeter in series with the 300Ω resistor to Terminal 9 Positive and 10 Negative on the Series 965 terminal strip. Use regular 20 - 24 gauge wire.

3.

Apply power to the unit and allow it to warm up for 15 minutes. After warm-up put the unit in the CAL menu. Press the MODE key until the 4A0 prompt is displayed.

4.

Press the A/M key twice to enter the MANUAL mode. The unit is calibrating when the MANUAL LED is on.

5.

At the 4A0 prompt, the multimeter should read approximately 4mA. Allow at least 10 seconds to stabilize.

6.

Use the Up-arrow/Down-arrow keys (reverse acting) to adjust the reading on the multimeter for 3.85mA ± 0.10mA. Press the MODE key.

7.

At the 2A0 prompt, the multimeter should read approximately 20mA. Allow at least 10 seconds to stabilize. The unit will leave the CAL mode if 1 minute passes between key activations except for 4-20mA units.

8.

Use the UP/DOWN keys (reverse acting) to adjust the reading on the multimeter for 20.15mA ±0.10mA.

9.

To conclude the 4-20mA output calibration, advance the MODE key to the next prompt or exit the CAL menu.

Appendix

Before calibration on an installed control, make sure all data and parameters are documented. See Setup and Operation Charts, Pages 18 and 20.

NOTE: When the MN LED is on, the unit is automatically calibrating. Your sequence is VERY important. Always move to the next parameter before changing the calibration equipment.

WATLOW Series 965 User's Manual

33

Page 34

Glossary, A-P

This glossary includes general thermal system control terms.

Alarm: A condition, generated by a controller, indicating that the process has exceeded or fallen below the set or limit point.

Droop: Difference in temperature between set point and stabilized process temperature.

Alarm Silence: Disables the alarm relay output.

Duty cycle: Percentage of "load on time" relative to total cycle time.

Anti-reset: Control feature that inhibits automatic reset action outside the proportional band. Automatic prompts: Data entry points where a microprocessor-based control "prompts" or asks the operator/programmer for information input. Auto-tune: Automatically tunes the Series 965 PID parameters to fit the characteristics of your particular thermal system. Bumpless transfer: When transferring from auto to manual operation, the control output(s) will not change ("bumpless," smooth transition). Closed loop: Control system that has a sensing device for process variable feedback. Cold junction: Point of connection between thermocouple metals and the electronic instrument. Cold junction compensation: Electronic means to compensate for the effective temperature at the cold junction. Cycle time: The time necessary to complete a full on-through-off period in a time proportioning control system.

Hysteresis: In on/off control, the temperature change necessary to change the output from full on to full off. Hunting: Oscillation or fluctuation of process temperature between set point and process variable. Input: Process variable information being supplied to the instrument. Integral: Control action that automatically eliminates offset, or “droop,” between set point and actual process temperature. Also "reset." Isolation: Electrical separation of sensor from high voltage circuitry. Allows for application of grounded or ungrounded sensing element. JIS: Joint Industrial Standards. Also Japanese Industrial Standards Committee (JISC). Establishes standards on equipment and components. Offset: Adjustment to actual input temperature and to the temperature values the Series 965 uses for display and control. On/off control: Control of temperature about a set point by turning the output full on below set point and full off above set point in the heat mode.

Derivative: Anticipatory action that senses the rate of change of the process, and compensates to minimize overshoot and undershoot. Also "rate."

Open loop: Control system with no sensory feedback.

Deviation alarm: An alarm referenced at a fixed number of degrees, plus or minus, from set point.

Output: Action in response to difference between set point and process variable.

Default parameters: The parameters, or programmed instructions, permanently stored in microprocessor software to provide a data base.

Overshoot: Condition where temperature exceeds set point due to initial power up or process changes.

DIN: Deutsche Industrial Norms, a widely-recognized German standard for engineering units.

P control: Proportioning control.

Display capability: In a digital indicating instrument, the entire possible span of a particular parameter or value.

34

WATLOW Series 965 User's Manual

Parameter: A physical property whose value determines the response of an electronic control to given inputs.

Appendix

Page 35

Glossary, D-P Glossary, P-Z PD control: Proportioning control with rate action. PI control: Proportioning control with auto-reset. PID control: Proportioning control with auto-reset and rate. Process variable: Thermal system element to be regulated, such as time, temperature, relative humidity, etc. Programmed display data: Displayed information which gives the operator/programmer the "programmed" or intended process information, i.e., intended set point, intended alarm limit, etc. Proportional band: Span of temperature about the set point where time proportional control action takes place. Proportioning control: See Time Proportioning Control. Rate: Anticipatory action that senses the rate of change of temperature and compensates to minimize overshoot. Also "derivative." Rate band: A thermal control band that defines where the rate (derivative) function begins. A Watlow rate band occurs centered on set point at one or more times the width of the proportional band.

Switching sensitivity: In on/off control, the temperature change necessary to change the output from full on to full off. Thermal system: A regulated environment consisting of a heat source, heat transfer medium, sensing device and a process variable control instrument. Thermocouple: Temperature sensing device that is constructed of two dissimilar metals wherein a measurable, predictable voltage is generated corresponding to temperature. Thermocouple break protection: Fail-safe operation that assures output shutdown upon an open thermocouple condition. Three mode control: Proportioning control with reset and rate. Time proportioning control: Action which varies the amount of on and off time when "close" to the set point, i.e., in the proportional band. This variance is proportional to the difference between the set point and the actual process temperature. In other words, the amount of time the output relay is energized depends on the system temperature. Triac: Solid state switching device.

Reference junction: Synonymous with cold junction. See "Cold junction."

Upper display data: Displayed information which gives the operator/programmer real or "actual" data, i.e., actual process temperature. See "Programmed display data."

Reset: Control action that automatically eliminates offset, or "droop," between set point and actual process temperature. Also "integral."

Warm start: Start-up condition where all program information is remembered by the instrument's memory back-up protection.

Reset windup inhibit: Synonymous with antireset. See "Anti-reset."

Zero switching: Action that provides output switching only at the zero-voltage, crossing points of the ac line.

RTD: Resistance Temperature Detector. Resistive sensing device displaying resistance versus temperature characteristics. Displays positive temperature coefficient. Set point: Intended value of the process variable.

Appendix

WATLOW Series 965 User's Manual

35

Page 36

Index Index A Alarms 24 Wiring 11 Appendix 27 A/M key 13 Automatic Operation 13, 23 Auto-tuning 21 B Bumpless transfer 23 C Calibration 29 Calibration Offset 20 D DC Output 1 10 DC Output 2 11 Declaration of Conformity 40 Default Parameters Operation 20 Setup 18 Dimensions Faceplate 5 Panel Cutout 5 Sideview 5 DIP Switches 14 Displays 13, 17 Down-arrow key 13 E Eliminate Noise 28 Entering the Setup Menu 15 Error Codes 25 F, G General Description 4 Glossary 34 H High Voltage Wiring 7 Hysteresis 17 I Input Wiring 8 DIP Switch 14 Ranges 18 Input Installation 5 J, K Keys 13 L L1 & L2 Keys 13 Ladder Wiring Diagram, System 12 Lock Parameter 16 Low Voltage Wiring 7 Lower Display 13

36

WATLOW Series 965 User's Manual

M M/N Key 13 Manual Operation 13, 23 Manual Tuning 22 Mechanical Relay, 5 Amp Output 1 Wiring 10 Output 2 Wiring 11 MODE key 13 Model Number 39 N Noise Eliminating 28 Sources 27 Decreasing Sensitivity 27 O Operation Parameters 19 Output Wiring 5A Mechanical Relay 10, 11 4-20mA 10 DC (Open Collector) 10, 11 Solid State Relay w/o Supp. 10, 11 Overview of the Series 965 4 P Power Limiting 17 Power Wiring 7 Process Input 8, 9 Process Output 10 Q Quick Reference Sheet 41 R Ramping 17 Rate 17 Restoring Calibration 30 Returns 37 RTD Calibration 31 RTD Sensor Wiring 9 S Sensor Wiring 8 Series 965 Input And Output Overview 4 Setup Menu and Parameters 15 Specifications 38 System Wiring Example 12 T Thermocouple Break Protection 7, 8, 16, 23 Thermocouple Calibration 31 Thermocouple Sensor Wiring 8 Tuning 21 U, V, W Up-arrow key 13 Upper Display 13 Warranty 37

Index