Series 965 User's Manual
Manual43 pagesPDF 401 KB
User's manual for the Watlow Series 965, a 1/16 DIN microprocessor-based auto-tuning temperature control.
Filed with · 1 model
Also filed with these models on the old site
Summary
What is in it
Watlow's user's manual for the Series 965, a 1/16 DIN microprocessor-based temperature control with a single thermocouple, RTD or process input and dual outputs. It explains panel mounting and the NEMA 4X seal, power, input and output wiring for each model option with a system wiring example, the keys and displays, the input type DIP switch and the setup and operation menus, auto-tuning and manual tuning, alarms and error codes, noise guidelines and field calibration, with specifications and model number information.
Its parts
- Starting Out With The Watlow Series 965
- Install and Wire the Series 965
- How to Use the Keys and Displays
- How To Set Up The Series 965
- How to Tune and Operate
From the manual
Key facts from this manual
Each line names its page in the PDF.
This is the Watlow Series 965 User's Manual, revision C of July 1998, for a 1/16 DIN microprocessor-based auto-tuning temperature control with one input and two outputs. It covers the whole Series 965 line by model number option rather than one exact model. It shows how to mount and wire the control, set the input type, set it up and tune it, and read its error codes.
- What it is
- 1/16 DIN microprocessor-based temperature control with a single input and dual outputs, PID or on/off p. 4
- Inputs
- Thermocouple (grounded or ungrounded); 2- or 3-wire 100 ohm platinum RTD, DIN or JIS curve; 4-20mA or 0-5V dc process p. 38
- Thermocouple ranges
- J: 32 to 1382°F (0 to 750°C); K: -328 to 2282°F (-200 to 1250°C); N: 32 to 2282°F (0 to 1250°C); S: 32 to 2642°F (0 to 1450°C); T: -328 to 662°F (-200 to 350°C) p. 38
- Output 1
- Heating or cooling: Form C 5A mechanical relay, switched dc, 4-20mA, or Form A 0.5A solid-state relay p. 38
- Output 2
- Heat, cool or alarm: none, switched dc, Form C 5A mechanical relay, or Form A 0.5A solid-state relay p. 38, 39
- Power
- 100-240V ac (85-264V ac) high voltage version or 12-24V ac/dc low voltage version, 50/60Hz; 5VA maximum p. 38
- Error codes
- Er 2 sensor underrange (RTD units only), Er 4 configuration error, Er 5 non-volatile checksum error, Er 6 A/D underflow, Er 7 A/D overflow p. 25
- Displays
- Two four-digit, seven-segment LED displays, red or green, 0.3 in (8 mm) high p. 13
- Size and weight
- 2.1 in high, 2.1 in wide, 4.7 in deep overall; 0.4 lb (0.2 kg) p. 38
- Panel cutout
- 1.77 to 1.79 in (44.96 to 45.47 mm); panel 0.06 to 0.38 in (1.5 to 9.7 mm) thick p. 5
- Operating environment
- 32 to 149°F (0 to 65°C), 0 to 90% RH non-condensing; storage -40 to 185°F (-40 to 85°C) p. 38
- Internal fuse
- Slo-Blo time-lag, factory replaceable only: 1A 250V on high voltage versions, 2A 250V on low voltage versions p. 38
- RC suppressor
- Quencharc, Watlow part 0804-0147-0000, for switching inductive loads p. 10
- Approvals
- The manual states UL and C-UL recognized (File #E43684, UL873) and CE approved p. 38
What this manual walks you through
- Mounting the control in a panel cutout and checking the NEMA 4X seal p. 5, 6
- Wiring high voltage or low voltage power p. 7
- Wiring thermocouple, RTD and process sensor inputs p. 8, 9
- Wiring each Output 1 and Output 2 option p. 10, 11
- A system wiring example with a Series 92 limit control and a dc-input solid-state relay p. 12
- Using the keys, displays and LEDs, including Auto and Manual mode p. 13
- Setting the input type DIP switch to match the sensor p. 14
- Entering the Setup Menu and its parameters p. 15
- Auto-tuning the PID settings p. 21
- Reading error codes and clearing them p. 25, 26
Good to know
- Applying high voltage to a low voltage unit causes irreversible damage. p. 7
- Process inputs have no sensor break protection, so the outputs can stay full on. p. 8
- When an external device with a non-isolated circuit common is connected to the 4-20mA or dc output, the thermocouple must be isolated or ungrounded. p. 8
- Switching inductive loads such as relay coils requires an RC suppressor. p. 38
- The manual states the NEMA 4X (IP 65) front panel rating needs a mounting panel at least 0.06 in (1.5 mm) thick. p. 38
Questions this manual answers
What sensors does the Watlow 965 accept?
Its single input takes a type J, K, T, N or S thermocouple, an RTD, or a process signal. p. 4
What does Er 7 mean on a Watlow 965?
Er 7 is an A/D overflow error, most likely caused by an open or reverse-polarity sensor. Check the sensor and make sure the In parameter and DIP switches match it. p. 25
How do I enter the setup menu on a Watlow 965?
Press the Up-arrow and Down-arrow keys together for 3 seconds; the lower display then shows the LOC parameter. p. 15
What supply voltage does the Series 965 need?
It comes as a 100-240V ac nominal high voltage version (power digit 0 in the model number) or a 12-24V ac or dc low voltage version (digit 1). High voltage on a low voltage unit causes irreversible damage. p. 7, 39
What RC suppressor part number is used with the Watlow 965 outputs?
The manual says to order a Quencharc, 0804-0147-0000, when an output drives a solenoid, contactor or other inductive device. p. 39
Contents
Chapters and sections
Each line opens the PDF at its page.
- How to Use this Manual2
- Notes and Safety Information2
- Technical Assistance2
- Warranty and Returns2
- Comments and Suggestions2
- Chapter 14
- Chapter 25
- Chapter 313
- Chapter 414
- Chapter 521
- Appendix 127
- Appendix 229
- Glossary, A-P34
- Glossary, P-Z35
- Index36
- Warranty37
- Returns37
- Watlow Controls37
- Specifications38
- Model No.39
- Conformity40
- Series 965 Quick Reference41