Page 37
Warranty Index Warranty The Watlow Series 965 is warranted to be free of defects in material and workmanship for 36 months after delivery to the first purchaser for use, providing that the units have not been misapplied. Since Watlow has no control over their use, and sometimes misuse, we cannot guarantee against failure. Watlow's obligations hereunder, at Watlow's option, are limited to replacement, repair or refund of purchase price, and parts which upon examination prove to be defective within the warranty period specified. This warranty does not apply to damage resulting from transportation, alteration, misuse, or abuse.
Returns 1. Call Watlow Customer Service, (507)454-5300, for a Return Material Authorization (RMA) number before returning any item for repair. We need this information: • Ship to address • Bill to address • Contact name • Phone number • Ship via • Your P.O. number • Symptoms and/or special instructions • Name and phone number of person returning the material. 2. Prior approval and an RMA number, from the Customer Service Department, is needed when returning any unused product for credit. Make sure the RMA number is on the outside of the carton, and on all paperwork returned. Ship on a Freight Prepaid basis. 3. After we receive your return, we will examine it and determine the cause for your action. 4. In cases of manufacturing defect, we will enter a repair order, replacement order, or issue credit for material. A 20 percent restocking charge is applied for all returned stock controls and accessories. 5. If the unit is unrepairable, it will be returned to you with a letter of explanation. Repair costs will not exceed 50 percent of the original cost.
Watlow Controls Watlow Controls is a division of Watlow Electric Mfg. Co., St. Louis, MO, a manufacturer of industrial electric heating products, since 1922. Watlow begins with a full set of specifications and completes an industrial product that is manufactured totally in-house, in the U.S.A. Watlow products include electric heaters, sensors, controls and switching devices. The Winona operation has been designing solid state electronic control devices since 1962, and has earned the reputation as an excellent supplier to original equipment manufacturers. These OEMs depend upon Watlow Controls to provide compatibly engineered controls which they can incorporate into their products with confidence. Watlow Controls resides in a 100,000 square foot marketing, engineering and manufacturing facility in Winona, Minnesota.
Index
WATLOW Series 965 User's Manual
37
Page 38
Specifications Specifications - (1460) Control Mode • Microprocessor-based, user selectable control modes • Single input, dual output • 2.5Hz Input Sampling Rate • 1Hz Display Update Rate • Ramp to set point: 0 to 9999 degrees or units per hour • Heat and cool auto-tune Agency Approvals • UL and C-UL recognized, File #E43684, UL873 • CE approved 89/336/EEC Electromagnetic Compatibility Directive EN 50081-2: 1994 Emissions EN 50082-2: 1995 Immunity 73/23/EEC Low -Voltage Directive EN 61010-1: 1993 Safety • NEMA 4X2, I.P. 65 rating Operator Interface • Sealed membrane front panel • Dual, four-digit red or green displays • MODE, Up-arrow, Down-arrow, and AUTO/ MANUAL keys • User selectable screen display Accuracy • Calibration accuracy and sensor conformity: ±0.1% of span, ±1 LSD @ 77°F ± 5°F (25°C ± 3°C) ambient and rated line voltage • Accuracy span: 1000°F (540°C) minimum • Temperature stability: ±0.2°F/°F (±0.2°C/°C) rise in ambient maximum • Voltage stability: ±0.01% of span per percent of rated line voltage Sensors/Inputs • Thermocouple, grounded or ungrounded sensors • RTD 2- or 3-wire, platinum, 100Ω @ 0°C calibration to DIN curve (0.00385Ω/Ω/°C) or JIS curve (0.003916Ω/Ω/°C); user selectable • Process, 4-20mA @ 5Ω, or 0-5VÎ (dc) @ 10kΩ input impedance • Sensor break protection de-energizes control output to protect system or selectable bumpless transfer to manual operation • °F or °C or process units display, user selectable Input Range Specified temperature ranges represent the controller’s operational span. • Thermocouple Type J 32 to 1382°F (0 to 750°C) Type K -328 to 2282°F (-200 to 1250°C) Type N 32 to 2282°F (0 to 1250°C) Type S 32 to 2642°F (0 to 1450°C) Type T -328 to 662°F (-200 to 350°C) • RTD Resolution (DIN or JIS) 1° -328 to 1292°F (-200 to 700°C) 0.1° -199.9 to 999.9°F (-128.8 to 537.7°C) • Process 4-20mA @ 5Ω, or -999 to 9999 units 0-5VÎ (dc) @ 10kΩ, or -999 to 9999 units Output 1 (Heating or Cooling) • Electromechanical relay 1, Form C, 5A @ 120/240V~ (ac) maximum, without contact suppression, rated resistive load, 5A @ 30VÎ (dc)3 . • Switched dc signal provides a non-isolated minimum turn on voltage of 3VÎ (dc) into a minimum 500Ω load; maximum on voltage not greater than 12VÎ (dc) into an infinite load. • 4-20mA reverse or direct acting, non-isolated 0 to 800Ω load. • Solid-state relay3, Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac) max., opto-isolated burst fire switched, without contact suppression. Off-state output impedance is 31MΩ.
38
WATLOW Series 965 User's Manual
Output 2 (Heat, Cool or Alarm) • Electromechanical relay1 , Form C, 5A @ 120/240V~ (ac) maximum, without contact suppression, rated resistive load, 5A @ 30VÎ (dc)3. • Switched dc signal provides a non-isolated minimum turn on voltage of 3VÎ (dc) into a minimum 500Ω load; maximum on voltage not greater than 12VÎ (dc) into an infinite load. • Solid-state relay3 , Form A, 0.5A @ 24V~ (ac) min., 264V~ (ac) max., opto-isolated burst fire switched, without contact suppression. Off-state output impedance is 31MΩ. • Alarm output can be latching or non-latching, and process or deviation with separate high and low values. Alarm silencing (inhibit) on power up. Output Configurations • Output 1 User selectable as: on/off: P, PI, PD, PID, heat or cool action • Adjustable switching differential: 1 to 99°F (1 to 55°C) • Proportional band: 0 (off) or 1 to 999°F (0 to 555°C) or 0.0 to 999.9 units Integral: 0 (off) or 0.1 to 99.9 minutes per repeat Reset: 0 (off) or 0.01 to 9.99 repeats per minute Rate/derivative: 0 (off) or 0.01 to 9.99 minutes Cycle time: 0.1 to 999.9 seconds • Output 2 User selectable as: Control with action opposite that of Output 1 (heating or cooling) • Process or deviation alarm with flashing alarm message • Process or deviation alarm without alarm message • Alarm with separate high and low set points • Hysteresis: 1 to 9999° or units switching differential Line Voltage/Power • 100-240V~ (ac), +10%, -15%; (85-264V~ [ac]) 50/60Hz, ±5% •12-24Vı (ac/dc), +10%, -15%; (10-26Vı [ac/dc]) 50/60Hz, ±5% • Fused internally (factory replaceable only) Slo-Blo® type (time-lag): 1A, 250V for high voltage versions 2A, 250V for low voltage versions • Power consumption 5VA maximum • Data retention upon power failure via non-volatile memory Operating Environment • 32 to 149°F (0 to 65°C) • 0 to 90% RH, non-condensing Storage Temperature • -40° to 185°F (-40° to 85°C) Terminals • #6 compression universal head screw terminals, accepts 2014 gauge wire Controller Weight • 0.4 lb (0.2 kg) Shipping Weight • 0.75 lb (0.34 kg) Dimensions • Compact 1⁄16 DIN size and NEMA 4X 2, (I.P. 65) front panel make the Series 965 easy to apply and maintain in a wide variety of applications. Unique mounting bezel, gasket and collar make installation a snap. Overall Height: 2.1 inches (55 mm) Width: 2.1 inches (55 mm) Depth: 4.7 inches (120 mm) Bezel Height: 2.1 inches (55 mm) Width: 2.1 inches (55 mm) Depth: 0.6 inches (15 mm) Chassis Height: 1.8 inches (45 mm) Width: 1.8 inches (45 mm) Depth: 4.1 inches (105 mm) 1
Electromechanical relays warranted for 100,000 closures only. Solid-state switching devices recommended for applications requiring fast cycle times or extended service life. 2 To effect NEMA 4X (I.P. 65) rating requires a minimum mounting panel thickness of 0.06inch (1.5 mm) and surface finish not rougher than 0.000032 inch (0.000812 mm). 3 Switching inductive loads (relay coils, etc.) requires using an RC suppressor. Appendix
Page 39
Model No. Series 965 Model Number Information Ordering Information - W965-XMNN Rev A00
965A-3___-00__
Output 1 C = Switched dc output, non-isolated D = Electromechanical relay, Form C, 5A, without contact suppression1 3 F = Process, 4-20mAÎ (dc), non-isolated K = Solid-state relay, Form A, 0.5A, without contact suppression 3 Output 2 A = None C = Switched dc output, non-isolated D = Electromechanical relay, Form C, 5A, without contact suppression1 3 K = Solid-state relay, Form A, 0.5A, without contact suppression 3 Line Voltage/Power 0 = 100-240V~ (ac) nominal (high voltage) 1 = 12-24V~ (ac) nominal or 12-24VÎ (dc) (low voltage) Display Upper Display 00 = Red RG = Red GR = Green GG = Green
Lower Display Red Green Red Green
* Note: If this output will drive a solenoid, MDR, contactor or other inductive device, order a Quencharc™ (0804-0147-0000) for output protection. See Chapter 2 for wiring.
Spare Parts • Mounting collar • Case gasket • Protective terminal cover • Internal bezel gasket • Quencharc™ RC suppressor Appendix
0822-0395-0000 0830-0402-0002 0822-0426-0001 0830-0402-0001 0804-0147-0000
WATLOW Series 965 User's Manual
39
Page 40
Conformity Put Declaration of Conformity on this page.
40
WATLOW Series 965 User's Manual
Appendix
Page 41
Series 965 Quick Reference Use this page as a quick reference for the Series 965. Tear along the perforation.
Keys & Displays Upper Display: Red or green, LED display, indicating either process actual temperature, the operating parameter values, or an open sensor.
L1: When lit it indicates Output 1 is energized.
Lower Display: Red or green, four digit LED display, indicating the set point, output value, parameters for data in the upper display, or error and alarm codes.
MN: Lit when in manual operation. Press A/M twice to enter Automatic. When blinking, press A/M to toggle between Auto and Manual. After 5 seconds without key activations it returns to its previous state.
MODE Key: Steps the control through the operating menu, also, in the Auto mode, new data is self entering in 5 seconds.
L2: When lit it indicates when Output 2 is active. This output can be configured as a control or alarm output.
Down-arrow Key: Decreases the value of the displayed parameter. New data is self entering in 5 seconds.
Up-arrow Key: Increases the value of the displayed parameter. New data is self entering in 5 seconds.
Up-arrow/Down-arrow Keys: When pressed simultaneously for 3 seconds, the Setup Menu appears displaying the LOC parameter. Continue to press the UP/DOWN keys, and the Calibration menu appears.
A/M Key: Press once to clear latched alarms and toggles between Auto and Manual. If pressed within 5 seconds it changes from Auto to Manual or vice versa. While in Manual, percent power is in the lower display.
Alarms Process Alarm sets an absolute temperature. When the process exceeds that absolute temperature limit an alarm occurs. The process alarm set points may be independently set high and low. Under the Setup menu, select the type of alarm output with the Ot2 parameter. PrA = Process alarm Pr = Process alarm with no alarm message displayed the deviation alarm band. Once the process value crosses into the "safe" region, both a latching or a non-latching alarm is ready. Any future deviation outside this safe band triggers an alarm. Both alarms can be latching or non-latching. When the alarm condition is removed a non-latching alarm automatically clears the alarm output. You must manually clear a latching alarm before it will disappear.
Deviation Alarm: Alerts the operator when the process strays too far from set point. The operator can enter Flashing LO or HI in the lower display independent high and low alarm settings. Press once indicates an alarm when Ot2 = PrA or The reference for a deviation alarm is set to clear dEA. The lower display alternately point. Any change in set point causes a a latched shows information from the current corresponding shift in the deviation alarm. parameter and a LO or HI alarm mesand Under the Setup menu, select the type of sage at one second intervals. The alarm output with the Ot2 parameter. corrected alarm output is de-energized, L2 is lit. dEA = Deviation alarm alarm. dE = Deviation alarm with no alarm To clear an alarm... message displayed • First correct the alarm condition, then... • If the alarm is latching... Alarm Silencing is available with the deviation alarm. When SIL is Clear it manually; press the A/M key once as soon as the selected as "on," the operator must manually disable the alarm by process temperature is inside the HSA parameter alarm limit. pressing the A/M key once on initial power up (in either the latching or • If the alarm is non-latching... non-latching mode). Alarm silencing disables the alarm output relay. The alarm clears itself automatically as soon as the process However, the L2 LED (also the lower display when Ot2 = dEA) shows temperature is inside the HSA parameter alarm limit. an alarm condition until the process value is within the "safe" region of
Error Codes Four dashes, "- - - -" or a negative number, in the upper display indicate a Series 965 error. The error code is visible in the lower display.
Er 2 - Sensor underrange error (For RTD units only) The sensor input generated a value lower than the allowable signal range, or the A/D circuitry malfunctioned. Enter a valid input. Make sure the In parameter matches your sensor and DIP switch setting. Refer to the table below for the appropriate input type and range. Er 4 - Configuration error The unit's microprocessor is faulty; call the factory.
Er 5 - Non volatile checksum error The nonvolatile memory checksum discovered a checksum error. Unless a momentary power interruption occurred while the unit was storing data, the nonvolatile memory is bad. Call the factory. Er 6 - A/D underflow error The A/D circuit is underrange. An open or reversed polarity sensor is the most likely cause. Check the sensor; if the connection is good and functions properly, call the factory. The A/D underrange voltage is too low to convert an A/D signal. Make sure the In parameter matches your sensor and the DIP switches are set accordingly. Er 7 - A/D overflow error The A/D circuit is overrange. An open or reversed polarity sensor is the most likely cause. Check the sensor; if the connection is good and the sensor functions properly, call the factory. The A/D overrange voltage is too high to convert an A/D signal. Make sure the In parameter matches your sensor and the DIP switches are set accordingly.
Page 42
Entering the Setup Menu The Setup Menu displays the parameters that configure the Series 965's features to your applicaton. Enter the Setup menu by pressing the Up-arrow/Down-arrow keys simultaneously for 3 seconds. The lower display shows the LOC parameter, and the upper display shows its current level. All keys are inactive until you release both keys. You can reach the LOC parameter from anywhere. You will not see all parameters in these menus depending on your unit's configuration and model number.
Setup Menu (
)
Do not enter any values here; make photocopies instead. Parameters
LOC (
)
User lock out
In
(
)
Input type dEC
(
)
Decimal place
C_F (
)
Celcius__Fahrenheit rL
(
)
Range low rH
(
)
Range high
Ot 1
(
)
Output 1
HSC (
)
Control hysteresis
(
)
Output 2
HSA (
)
Output 2 hysteresis
LAt
(
)
Latching for alarm
SIL
(
)
Silence alarm rtd
(
)
RTD calibration curve rP
(
)
Ramp func tion rt
(
)
Ramp rate
PL
(
)
Power limiting dSP
(
)
Display
Ot2
75
Value
Range
Factory Default
Appears If:
LOC In dEC C_F
0 through 4 J, K (appears as H), t, n, S, rtd, rt.d, 0-5, 420 0, 0.0, 0.00 C or F
0 J 0 C F
DIP switch selectable In = 0-5 or 420 dFL = SI or In = T/C or RTD dFL = US or In = T/C or RTD rL rH Ot1 HSC Ot2 rL to rH rH to rL ht or CL 1 to 99, 0.1 - 9.9, 0.01 - 0.99 Con = Control PrA = Process alarm Pr = Process with no alarm message dEA = Deviation alarm dE = Deviation with no alarm message no = None 1 to 9999, 0.1 - 999.9, 0.01 - 99.99 LAt or nLA On or OFF JIS or din Str = Ramping on power up on = Ramping to set point at all times OFF = None 0 to 9999 0 to 100 nor = Normal SEt = Set Point (lower display only) Pro = Process (upper display only)
Input dependent Input dependent ht 3, 0.3, 0.03°F Con
HSA LAt SIL rtd rP rt PL dSP
3, 0.3, 0.03°F nLA OFF din OFF
Ot2 ≠ Con or no Ot2 ≠ Con or no Ot2 = dEA or dE In = rtd or rt.d
100°/hr 100 nor rP ≠ OFF
Operation Menu (
)
Do not enter any values here; make photocopies instead. Parameters Pb1 75 Pb1
Control Set Point ( )
Proportional band 1 rE1/It1 ( )
Reset 1/Integral 1 rA1/dE1 ( )
Rate Rate1/Derivative 1/Deviation1 1
Ct1
( )
Cycle time 1
Pb2
( )
Proportional band 2 rE2/It2 ( )
Reset 2/Integral 2 rA2/dE2 ( )
Rate Rate2/Derivative 2/Deviation2 2
Ct2
( )
Cycle time 2
ALO
( )
Alarm low
AHI
( )
Alarm high
CAL
( )
Calibration offset
AUt
( )
Auto-tune rE1 It1 rA1 dE1 Ct1 Pb2 rE2 It2 rA2 dE2 Ct2 ALO AHI CAL AUt
Value
Range
Factory Default
Appears If:
0 to 999°F/0 to 555°C/0 to 999 Units 0 to 99.9°F/ 0 to 55.5°C/0 TO 99.9 UNITS 0.0 to 999.9% of span 0 = ON/OFF control, HSC = Switching diff. 0.00 to 9.99 repeats/minute / 0.00 = No reset 00.0 to 99.9 minutes/repeat / 0.00 = No integral 0.00 to 9.99 minutes / 0.00 = No rate 0.00 to 9.99 minutes / 0.00 = No derivativew 0.1 to 999.9 seconds 1 to 999°F/0 to 555°C/0 to 999 Units 1 to 99.9°F/ 0 to 55.5°C/0 to 99.9 Units 0.1 to 999.9% of span 0.00 to 9.99 repeats/minute / 0.00 = No reset 00.0 to 99.9 minutes/repeat / 0.00 = No integral 0.00 to 9.99 minutes / 0.00 = No rate 0.00 to 9.99 minutes / 0.00 = No derivative 0.1 to 999.9 seconds -999° to 0 rL to AHI 0 to 999° ALO to rH ± 18°F/±10°C/±18 Units 0 = off, 1 = slow, 2 = medium, 3 = fast
25°F 2.5°F 3% / .3% dFL = US
0.00 repeats/minute 00.0 minutes/repeat 0.00 minutes 0.00 minutes 5.0 seconds 25°F 2.5°F 3% / .3% 0.00 repeats/minute 00.0 minutes/repeat 0.00 minutes 0.00 minutes 5.0 seconds -999° rL 999° rH 0 0
Pb1 ≠ 0 or dFL = US Pb1 ≠ 0 or dFL = SI Pb1 ≠ 0 or dFL = US Pb1 ≠ 0 or dFL is SI Pb1 ≠ 0 or Output 1 ≠ 420 dFL = US dFL = SI dFL = SI, Ot2 = Con, Pb1 ≠ 0 dFL = US, Ot2 = Con, Pb1 ≠ 0 dFL = SI, Ot2 = Con, Pb1 ≠ 0 dFL = US, Ot2 = Con, Pb1 ≠ 0 dFL = SI, Ot2 = Con, Pb1 ≠ 0 Ot2 = Con, Pb1 ≠ 0 Ot2 = dE or dEA Ot2 = Pr or PrA Ot2 = dE or dEA Ot2 = Pr or PrA
Page 43
Watlow Series 965 User's Manual Watlow Controls, 1241 Bundy Blvd., P.O. Box 5580, Winona, MN 55987-5580, Phone: 507/454-5300, Fax: 507/452-4507
2
WATLOW Series 985 User's Manual
Appendix