A total of eight I/O Units mounted to the Backplane. When using 16-point Output Units (models C200H-OC225/OD212/OD21A) mount them to a C200H-BC 1-V1/V2 Backplane. Transistor Output Unit C200H-OD212/OD21A and Contact Output Unit C200H-OC225 must be mounted to either a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2, or C200HBC101-V1/V2 Backplane.
The C200H-OC225 might overheat if more than 8 outputs are turned ON simultaneously. Relay: G6B-1174P-FD-US, 24 VDC. 16 pts 2 A, 250 VAC/24 VAC (For resistive loads)
Min. Switching Capacity 10 mA 5 VDC
Relay G6B-1174P-FD-US (24 VDC) w/socket
Service Life of Relay Electrical: 500,000 operations (resistive load)/100,000 operations (inductive load) Mechanical: 50,000,000 operations
Max. Switching Capacity 2 A 250 VAC (co sign zero = 1), 2 A 250 VAC (co sign zero = 0.4), 2 A 24 VDC (8 A/Unit)
ON Response Time 10 ms max.
OFF Response Time 10 ms max.
No. of Circuits 1 (16 points/common) 8 points max. can be ON simultaneously.