Page 1 of SYSMAC C200HS Programmable Controllers Installation Guide

Manual · Omron

SYSMAC C200HS Programmable Controllers Installation Guide

Manual221 pagesPDF 2.5 MB

Installation guide for OMRON SYSMAC C200HS programmable controllers, including racks, I/O Units such as the C200H-OC225, wiring and upkeep.

Download the PDF2.5 MB

Covers · 2 models

The models it covers

Summary

What is in it

OMRON's installation guide for the SYSMAC C200HS Programmable Controllers. It introduces PCs and compares the C200HS with the C200H, describes the CPUs, Expansion I/O Racks, power supplies and I/O Units, and explains installation, wiring, peripheral devices and system expansion (Programming Console, LSS, SSS). Troubleshooting charts, maintenance of fuses, relays and batteries, standard models and specifications follow. Units it lists include the C200H-OC225 Contact Output Unit and C200HW-SLK23 SYSMAC LINK Unit.

Its parts

  1. Precautions
  2. Introduction
  3. System Configuration and Unit Description
  4. Installation
  5. Wiring
  6. Peripheral Devices and System Expansion
  7. Troubleshooting
  8. Inspection and Maintenance

From the manual

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

This is the OMRON installation manual for C200HS Programmable Controllers: mounting, wiring, system expansion, troubleshooting and maintenance, with lists of standard models and their specifications. The site files it under the C200H-OC225 Contact Output Unit and the C200HW-SLK23 SYSMAC LINK Unit, which it covers among many other C200H and C200HS Units. It lets the reader check ratings, compatible backplanes and CPUs, accessories and replacement relays.

Read for this summary: pages 4, 7 to 8, 22, 24, 48, 74, 92, 95 to 97, 101 to 102, 104 to 105, 131 to 132 and 199 to 200 of 221.

C200H-OC225 type
C200H-OC225: 16-point Contact Output Unit, one common (16 points/common), 8 points max. ON at once p. 101, 132
C200HW-SLK23 type
C200HW-SLK23: SYSMAC LINK Unit wired via coaxial cable, data link capacity 918 words p. 22, 104
Contact rating
C200H-OC225: max. 2 A 250 VAC or 2 A 24 VDC (8 A/Unit); min. 10 mA 5 VDC p. 132
SYSMAC LINK CPUs
C200HW-SLK23: used only with the C200HS-CPU31-E and C200HS-CPU33-E CPUs p. 104
Backplane
C200H-OC225: must be mounted on a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2 or C200HBC101-V1/V2 Backplane p. 102
Bus connection
C200HW-SLK23: needs a C200H-CE001 or C200H-CE002 Bus Connection Unit, bought separately p. 74, 104, 105
Relay
C200H-OC225: G6B-1174P-FD-US (24 VDC) relays in sockets p. 132
Response time
C200H-OC225: ON and OFF response 10 ms max. p. 132
Relay life
C200H-OC225: electrical 500,000 operations (resistive load) or 100,000 (inductive load); mechanical 50,000,000 p. 132
Internal current
C200H-OC225: 50 mA 5 VDC max., 75 mA 26 VDC with 8 points ON p. 132
Weight, size
C200H-OC225: 400 g max., B-shape p. 132
Coax accessories
C200HW-SLK23: one C1000H-CE001 F Adapter included; a C1000H-TER01 Terminator is needed at each end node p. 104
Coaxial cables
ECXF5C-2V and 5C-2V coaxial cables for SYSMAC LINK p. 104
Rack expansion
Up to two Expansion I/O Racks and five Remote I/O Slave Racks per CPU Rack; cable up to 10 m between Racks, 12 m in total p. 48

What this manual walks you through

  • Mounting Units to the Backplane and adding Expansion I/O Racks p. 48
  • Connecting a SYSMAC LINK System to the C200HS p. 74
  • Troubleshooting Output Units by symptom p. 92
  • Replacing an Output Unit fuse p. 95
  • Replacing Output Unit relays p. 95, 96, 97
  • Choosing standard I/O, link and optional Units p. 101, 102, 104, 105
  • Differences between the C200HS and the C200H p. 24
  • Current drawn by Units and rack dimensions p. 199, 200

Good to know

  • The C200H-OC225 might overheat if more than 8 outputs are ON at the same time. p. 102
  • On any other model of Backplane, the 16-point Output Units (C200H-OC225/OD212/OD21A) will not operate properly. p. 48
  • Unused I/O connecting cable connectors are covered with the caps provided. p. 48
  • Fuses in High-density I/O Units cannot be replaced by the user. p. 95
  • Use UL or CSA approved fuses where the UL or CSA standards must be met. p. 95

Questions this manual answers

How many outputs can be on at once on a C200H-OC225?

Up to 8 of its 16 points can be ON at the same time; the manual warns the Unit might overheat with more. p. 102, 132

Which backplane does the C200H-OC225 need?

A C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2 or C200HBC101-V1/V2 Backplane. p. 102

What relay does the C200H-OC225 use?

G6B-1174P-FD-US (24 VDC) relays, mounted in sockets. p. 132

Which CPUs work with the C200HW-SLK23?

Only the C200HS-CPU31-E and C200HS-CPU33-E. p. 104

What is the data link capacity of the C200HW-SLK23?

918 words; it is the SYSMAC LINK Unit wired via coaxial cable. p. 104

The whole text · 23 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 3021-30
  4. Pages 31 to 4031-40
  5. Pages 41 to 5041-50
  6. Pages 51 to 6051-60
  7. Pages 61 to 7061-70
  8. Pages 71 to 8071-80
  9. Pages 81 to 9081-90
  10. Pages 91 to 10091-100
  11. Pages 101 to 110101-110
  12. Pages 111 to 120111-120
  13. Pages 121 to 130121-130
  14. Pages 131 to 140131-140
  15. Pages 141 to 150141-150
  16. Pages 151 to 160151-160
  17. Pages 161 to 170161-170
  18. Pages 171 to 180171-180
  19. Pages 181 to 190181-190
  20. Pages 191 to 200191-200
  21. Pages 201 to 210201-210
  22. Pages 211 to 220211-220
  23. Page 221221

The file

Revision and size

RevisionCat. No. W236-E1-07, Revised March 2003
PublisherOMRON
Pages221
PDF2.5 MB
TextText from the PDF itself; page 221 is a scan, read by OCR, which may hold reading errors.

The first pages · 3 of 221

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 221
Page 2
Page 2of 221
Page 3
Page 3of 221

More documents · 1

For the same models