Page 101

Appendix A

Standard Models

C200H Standard I/O Units Name Input Units

AC Input Unit

100 to 120 VAC

C200H-IA121

16 pts

100 to 120 VAC

C200H-IA122/IA122V

8 pts

200 to 240 VAC

C200H-IA221

16 pts

200 to 240 VAC

C200H-IA222/IA222V

8 pts

No-voltage contact; NPN

C200H-ID001

8 pts

No-voltage contact; PNP

C200H-ID002

8 pts

12 to 24 VDC

C200H-ID211

16 pts

24 VDC

C200H-ID212

8 pts

12 to 24 VAC/DC

C200H-IM211

16 pts

24 VAC/DC

C200H-IM212

Interrupt Input Unit1

8 pts

12 to 24 VDC

C200HS-INT01

Contact Output Unit

8 pts

2 A, 250 VAC/24 VDC (For resistive loads)

C200H-OC221

12 pts

2 A, 250 VAC/24 VDC (For resistive loads)

C200H-OC222

16 pts

2 A, 250 VAC/24 VAC (For resistive loads)

C200H-OC2252, 3

5 pts

C200H-OC223

12 pts

2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 2 A, 250 VAC/24 VDC (For resistive loads)

16 pts

2 A, 250 VAC/24 VDC (For resistive loads)

C200H-OC226

8 pts

C200H-OC224V

8 pts

2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 1 A, 120 VAC

8 pts

1.2 A, 120 VAC

C200H-OA122-E

8 pts

1.2 A 250 VAC

C200H-OA223

12 pts

0.3 A, 250 VAC

C200H-OA222V

12 pts

0.5 A, 250 VAC

C200H-OA224

8 pts 12 pts 16 pts

1 A, 12 to 48 VDC 0.3 A, 24 VDC 0.3 A, 24 VDC

C200H-OD411 C200H-OD211 C200H-OD2122

8 pts

2.1 A, 24 VDC

C200H-OD213

8 pts

C200H-OD214

8 pts

0.8 A, 24 VDC; source type (PNP); with load short protection 5 to 24 VDC; source type (PNP)

12 pts

5 to 24 VDC; source type (PNP)

C200H-OD217

1.0 A, 24 VDC; source type (PNP); with load short protection 4 timers 0.1 to 1 s/1 to 10 s/10 to 60 s/1 min to 10 min (switchable) Connector w/lead wire (2 m) for 1 external resistor

C200H-OD21A

16 input Connects to B7A Link Terminals. pts 16 output pts

C200H-B7AI1

AC/DC Input Unit

8 pts

Triac Output Unit

Transistor Output Unit

16 pts Analog Timer Unit Variable Resistor Connector Standard B7A Interface Units

94

Model number

8 pts

DC Input Unit

Output Units

Specifications

C200H-OC224 C200H-OC222V

C200H-OA121-E

C200H-OD216

C200H-TM001 C4K-CN223

C200H-B7AO1

Page 102

Appendix A

Standard Models

Note 1. If the Interrupt Input Unit is mounted on an Expansion I/O Rack, the interrupt function cannot be used and the Interrupt Input Unit will be treated as an ordinary 8-point Input Unit. Moreover, Interrupt Input Units cannot be used on Slave Racks. In addition, Interrupt Input Units require that a version 2 (i.e., model numbers with a “-V2” suffix) Backplane be used at the CPU Rack. If an earlier version Backplane is mounted, the interrupt function cannot be used. 2. Transistor Output Unit C200H-OD212/OD21A and Contact Output Unit C200H-OC225 must be mounted to either a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2, or C200HBC101-V1/V2 Backplane. 3. The C200H-OC225 might overheat if more than 8 outputs are turned ON simultaneously.

C200H Group-2 High-density I/O Units Name DC Input Unit

Transistor Output Unit

Specifications 64 pts 32 pts

12 VDC 24 VDC

64 pts

24 VDC

32 pts

16 mA 4.5 VDC to 100 mA 26.4 VDC 0.5 A (5 A/Unit) 24 VDC 16 mA 4.5 VDC to 100 mA 26.4 VDC

64 pts

Model number C200H-ID111 C200H-ID216 C200H-ID218 C200H-ID217 C200H-ID219 C200H-OD218 C200H-OD21B C200H-OD219

C200H Group-2 B7A Interface Units Name Group-2 B7A Interface Units

Specifications Connects to B7A Link Terminals.

32 input pts 32 output pts 16 input pts and 16 output points 32 input pts and 32 output points

Model number C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22

C200H Special I/O Units All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit. Name High-density I/O Units

DC Input Unit

Transistor Output Unit

Specifications

Model number

32 pts

5 VDC (TTL inputs); with high-speed input function

C200H-ID501

32 pts 32 pts

24 VDC; with high-speed inputs C200H-ID215 0.1 A, 24 VDC (usable as 128-point dynamic output unit) C200H-OD215

32 pts DC Input/ Transistor Output Unit

35 mA, 5 VDC (TTL outputs) (usable as 128-point dy- C200H-OD501 namic output unit) 16 input/ 12-VDC inputs; with high-speed input function C200H-MD115 16 output pts 0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 24-VDC inputs; with high-speed input function C200H-MD215 16 output pts 0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 5 VDC (TTL inputs); with high speed input function 35 C200H-MD501 16 output pts mA, 5 VDC Output (TTL outputs) (usable as 128-point dynamic input unit)

95

Page 103

Appendix A

Standard Models Name Analog I/O Analog Input Units Unit Analog Output Unit Temperature Sensor Unit

Temperature Control Unit

Heat/Cool Temperature Control Unit

Specifications 4 to 20 mA, 1 to 5/0 to 10 V (switchable); 4 inputs

Model number C200H-AD001

4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V (switchable); 8 inputs 4 to 20 mA, 1 to 5/0 to 10 V (switchable); 2 outputs

C200H-AD002 C200H-DA001

4 to 20 mA, –10 to 10 V; 4 outputs Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs Thermocouple (K(CA) or L(Fe-CuNi)) (switchable); 4 inputs Platinum resistance thermometer (JPt) (switchable), DIN standards; 4 inputs Platinum resistance thermometer (Pt) (switchable); 4 inputs Thermocou- Transistor output ple Voltage output Current output Pt resisTransistor output tance therVoltage output mometer

C200H-DA002 C200H-TS001 C200H-TS002 C200H-TS101

Thermocouple

Pt resistance thermometer PID Control Unit

Position Control Unit

Cam Positioner Unit

High-speed Counter Unit

Voice Unit

96

Current output Transistor output

C200H-TC103 C200H-TV001

Voltage output Current output Transistor output

C200H-TV002 C200H-TV003 C200H-TV101

Voltage output

C200H-TV102 C200H-TV103 C200H-PID01 C200H-PID02 C200H-PID03 C200H-NC111 C200H-NC112

1 axis

C200H-CT001-V1

Pulse input; counting speed: 50 kcps; 5 VDC/12 VDC/24 VDC Pulse input; counting speed: 75 kcps; RS-422 line driver

EEPROM For connecting the ASCII Unit to the FIT10 (9P/25P) Cable length: 2 m Local application, electromagnetic coupling Remote application, microwave transmissions Read/Write Electromagnetic type Head Microwave type Data Carrier SRAM type for V600-H series. (see note) EEPROM type for V600-H series. 60 messages max.; message length: 32, 48, or 64 s (switchable) Connecting RS-232C Cable

Connecting Cable I/D Sensor Unit

C200H-TC102

Current output Transistor output Voltage output Current output 1 axis Pulse output; speeds: 1 to 99,990 pps 1 axis Directly connectable to servomotor driver; compatible with line driver; speeds: 1 to 250,000 pps 2 axis 1 to 250000. pps. 53 pts per axis Detects angles of rotation by means of a resolver and provides ON and OFF outputs at specified angles. A maximum of 48 cam outputs (16 external outputs and 32 internal outputs) maximum are available.

1 axis ASCII Unit

C200H-TS102 C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101

C200H-NC211 C200H-CP114

C200H-CT002 C200H-ASC02 CV500-CN228 C200H-IDS01-V1 C200H-IDS21 V600-H series V620-H series V600-DjjRjj V600-DjjPjj C200H-OV001 C200H-CN224

Page 104

Appendix A

Standard Models Name Fuzzy Logic Unit Fuzzy Support Software

Specifications Model number Up to 8 inputs and 4 outputs. (I/O to and from specified data area words) C200H-FZ001 C500-SU981-E Available on either 3.5” or 5.25” floppy disks.

Note For Read/Write Head and Data Carrier combinations, refer to the V600 FA ID System R/W Heads and EEPROM Data Carriers Operation Manual and Supplement or V600 FA ID System R/W Heads and SRAM Data Carriers Operation Manual and Supplement.

C200H Link Units Name Host Link Unit

Specifications Rack-mounting

C200H only

Model number APF/PCF

C200H-LK101-PV1

RS-422

C200H-LK202-V1

RS-232C

C200H-LK201-V1

PC Link Unit

Multilevel

RS-485

C200H-LK401

Remote I/O Master Unit

Up to two per PC; connectable to up to 5 Slaves per PC total

APF/PCF

C200H-RM001-PV1

Wired

C200H-RM201

SYSMAC LINK Unit/SYSMAC NET Link Units The SYSMAC LINK Units and SYSMAC NET Link Unit can only be used with the C200HS-CPU31-E and C200HSCPU33-E CPUs. Name SYSMAC LINK Unit

Specifications Wired via coaxial cable. Bus Connection Unit required separately. One C1000H-CE001 F Adapter included.

Wired via optical fiber cable. Bus Connection Unit required separately. An Optical Fiber Cable Bracket must be used to support an optical cable connected to the SYSMAC LINK Unit.

Model number Data link capacity: 918 words

C200HW-SLK23

Data link capacity: 2,966 words

C200HW-SLK24

Data link capacity: 918 words

C200HW-SLK13

Data link capacity: 2,966 words

C200HW-SLK14

Terminator

One required for each node at ends of System

C1000H-TER01

Attachment Stirrup

Provided with SYSMAC LINK Unit

C200H-TL001

F Adapter

---

C1000H-CE001

F Adapter Cover Communications Cable

---

C1000H-COV01

Coaxial cables

ECXF5C-2V 5C-2V C200H-APS03

Auxiliary Power Supply Unit SYSMAC NET Link Unit

Power Supply Adapter Power Cable

Manufactured by Hitachi Manufactured by Fujigura Supplies backup power to either one or two SYSMAC LINK Units. One C200H-CN111 Power Connecting Cable included. Bus Connection Unit required separately. An Optical Fiber Cable Bracket must be used to support an optical cable connected to the SYSMAC NET Link Unit. Required when supplying power from Central For 1 Unit Power Supply For 2 Units Connects Power Supply Adapter and SYSMAC NET Link Unit

For 1 Unit For 2 Units

C200HS-SNT32

C200H-APS01 C200H-APS02 C200H-CN111 C200H-CN211

97

Page 105

Appendix A

Standard Models Name Bus Connection Unit

Specifications Connects SYSMAC LINK Unit or SYSMAC NET Link Unit to C200HS-CPU31-E/CPU33-E

Model number For 1 Unit For 2 Units

C200H-CE001 C200H-CE002

CompoBus Units Name

Specifications

Model number

CompoBus/S Master Unit

---

C200HW-SRM21

CompoBus/D (DeviceNet) Master Unit

---

C200HW-DRM21

Optional Products Name

Specifications

Model number

I/O Unit Cover

Cover for 10-pin terminal block

C200H-COV11

Terminal Block Cover

Short protection for 10-pin terminal block

C200H-COV02

Short protection for 19-pin terminal block

C200H-COV03

Connector Cover

Protective cover for unused Backplane connectors

C500-COV01

Space Unit

Used for vacant slots

C200H-SP001

Battery Set

For C200H RAM Memory Unit only

C200H-BAT09

Relay

24 VDC

G6B-1174P-FD-US DC24

Backplane Insulation Plate

For 10-slot Backplane

C200H-ATTA1

For 8-slot Backplane

C200H-ATT81

For 5-slot Backplane

C200H-ATT51

For 3-slot Backplane

C200H-ATT31

For 10-slot Backplane

C200H-ATTA3

For 8-slot Backplane

C200H-ATT83

For 5-slot Backplane

C200H-ATT53

For 3-slot Backplane

C200H-ATT33

G6R-1

I/O Bracket

Note 1. When ordering, specify the model name (any component of which is not sold separately). 2. Order the press-fit tool from the manufacturer.

Mounting Rails and Accessories Name

Specifications

Model number

DIN Track Mounting Bracket

1 set (2 included)

C200H-DIN01

DIN Track

Length: 50 cm; height: 7.3 mm

PFP-50N

Length: 1 m; height: 7.3 mm

PFP-100N

Length: 1 m; height: 16 mm

PFP-100N2

End Plate

---

PFP-M

Spacer

---

PFP-S

98

Page 106

Appendix A

Standard Models

Link Adapters Name

Specifications

Link Adapter

Model number

3 RS-422 connectors

3G2A9-AL001

3 optical connectors (APF/PCF)

3G2A9-AL002-PE

3 optical connectors (PCF)

3G2A9-AL002-E

1 connector each for APF/PCF, RS-422, and RS-232C

3G2A9-AL004-PE

1 connector each for PCF, RS-422, and RS-232C

3G2A9-AL004-E

1 connector each for APF/PCF and APF

3G2A9-AL005-PE

1 connector each for PCF and AGF

3G2A9-AL005-E

1 connector for APF/PCF; 2 for AGF

3G2A9-AL006-PE

O/E converter; 1 connector for RS-485, 1 connector each for APF/PCF

B500-AL007-PE

Used for on-line removal of SYSMAC NET Link Units from the SYSMAC NET Link System, SYSMAC NET Optical Link Adapter 3 connectors for APF/PCF.

B700-AL001

SYSMAC BUS/SYSMAC WAY Optical Fiber Products Plastic Clad Optical Fiber Cable/All Plastic Optical Fiber Cable Name Plastic Clad Optical Fiber Cable (indoor)

Specifications 0.1 m, w/connectors 1 m, w/connectors

Model number Ambient temp: –10° to 70°C

3G5A2-OF011 3G5A2-OF101

2 m, w/connectors

3G5A2-OF201

3 m, w/connectors

3G5A2-OF301

5 m, w/connectors

3G5A2-OF501

10 m, w/connectors

3G5A2-OF111

20 m, w/connectors

3G5A2-OF211

30 m, w/connectors

3G5A2-OF311

40 m, w/connectors

3G5A2-OF411

50 m, w/connectors

3G5A2-OF511

Cable only; order desired length between 1 and 200 m in increments of 1 m.

B500-OF002

All Plastic Optical Fiber Cable

Cable only; order desired length in 5 m increments between 5 and 100 m, or in increments of 200 m or 500 m.

B500-PF002

Optical Connectors A

Two optical connectors (brown) for APF (10 m max.)

3G5A2-CO001

Optical Connectors B

Two optical connectors (black) for APF (8 to 20 m)

3G5A2-CO002

All Plastic Optical Fiber Cable Set 1-m cable with an Optical Connector A connected to each end

3G5A2-PF101

Optical Fiber Processing Kit

3G2A9-TL101

Accessory: 125-mm nipper (Muromoto Tekko’s 550M) for APF

99

Page 107

Appendix A

Standard Models H-PCF Name Optical Fiber Cable SYSMAC BUS, SYSMAC WAY

Specifications 10 m, black

S3200-HCCB101

50 m, black

S3200-HCCB501

100 m, black

S3200-HCCB102

500 m, black

S3200-HCCB502

1000 m, black

S3200-HCCB103

10 m, orange

S3200-HCCO101

50 m, orange

S3200-HCCO501

100 m, orange

S3200-HCCO102

500 m, orange

S3200-HCCO502

1000 m, orange

S3200-HCCO103

10 m, black

Optical Fiber Cable Connector

Model number Two-core cable

Two-core cable

S3200-HBCB101

50 m, black

S3200-HBCB501

100 m, black

S3200-HBCB102

500 m, black

S3200-HBCB502

1000 m, black

S3200-HBCB103

SYSMAC BUS: C200H-RM001-PV1 C200H-RT001/RT002-P C500-RM001-(P)V1 C500-RT001/RT002-(P)V1 B500-jjj(-P)

Half-lock connector S3200-COCH82 for Remote I/O Master, Remote I/O Slave, Host Link Unit, and Link Adapter

Note 1. Optical fiber cables must be prepared and connected by specialists. 2. If the user prepares and connects optical fiber cables, the user must take a seminar held under the auspices of Sumitomo Electric Industries, Ltd. and obtain a proper certificate. 3. The Optical Power Tester, Head Unit, Master Fiber Set, and Optical Fiber Assembling Tool are required to connect optical fiber cables. Optical Fiber Assembling Tool Name Optical Fiber Assembling Tool

Specifications

Model number

Used to connect H-PCF and crimp-cut connectors for optical transmission systems such as the SYSMAC C- and CV-series SYSMAC BUS, SYSMAC LINK and SYSMAC NET.

S3200-CAK1062

Note 1. Optical fiber cables must be prepared and connected by specialists. 2. The Optical Power Tester, Head Unit, Master Fiber set, and Optical Fiber Assembling Tool are required to connect optical fiber cables. Optical Power Tester Name

Specifications

Head Unit

Optical Power Tester (see note) (provided with a connector adapter, light source unit, small single-head plug, hard case, and AC adapter)

SYSMAC BUS: C200H-RM001-PV1 C200H-RT001/RT002-P C500-RM001-(P)V1 C500-RT001/RT002-(P)V1

S3200-CAT2822 (provided with the Tester)

Model number S3200-CAT2820

Note: There is no difference between the light source unit and connector adapter for the Head Unit and those for the Optical Power Tester.

100

Page 108

Appendix A

Standard Models Head Unit Name

Specifications

Head Unit (a set consisting of light source unit and connector adapter) (see note)

Model number

SYSMAC BUS: C200H-RM001-PV1 C200H-RT001/RT002-P

S3200-CAT2822

SYSMAC NET: S3200-LSU03-V1/LSU03-01E C500-SNT31-V4 3G8FX-TM111 3G8SX-TM111

S3200-CAT3202

Note: Use a proper Head Unit model for the optical module to be used. If two types of optical modules (unit type and board type) are used, order an Optical Power Tester plus a proper Head Unit model. Master Fiber Set Name Master Fiber Set (1 m)

Specifications

Model number

S3200-CAT3202 (SYSMAC NET, NSB, NSU, Bridge)

S3200-CAT3201

S3200-CAT2002/CAT2702 (SYSMAC NET, SYSMAC LINK)

S3200-CAT2001H

S3200-CAT2822 (SYSMAC BUS)

S3200-CAT2821

Note 1. The Master Fiber Set is used in combination with the Optical Power Tester to check the optical levels of optical fiber cables connected to optical fiber cable connectors. 2. Optical fiber cables must be prepared and connected by specialists. 3. The Optical Power Tester, Head Unit, Master Fiber set, and Optical Fiber Assembling Tool are required to connect optical fiber cables.

SYSMAC LINK/SYSMAC NET Link Optical Fiber Products Optical Fiber Cables for SYSMAC LINK and SYSMAC NET Link Systems Use hard-plastic-clad quartz optical fiber (H-PCF) cables for SYSMAC LINK and SYSMAC NET Link Systems. H-PCF cables are available with connectors already attached, or cables and connectors can be purchased separately and assembled by the user. Refer to the System Manual for the SYSMAC LINK or SYSMAC NET Link Systems for assembly procedures. Models numbers for H-PCF cables with connecters attached are provided in the following illustration. Model Numbers for H-PCF Cables with Connectors

S3200-CNjjj-jj-jj

Cable length 201: 501: 102: 152: 202: Blank:

2m 5m 10 m 15 m 20 m Over 20 m (Specify.)

Connectors 20-25:

Full-lock connector on one end, half-lock connector on other end.

25-25:

Half-lock connectors on both ends.

An Optical Fiber Cable Bracket must be used to support an optical fiber cable connected to the C200HS-SNT32 SYSMAC NET Link Unit or C200HW-SLK13/SLK14 SYSMAC LINK Unit. User optical fiber cables with both tension members and power supply lines. The following half-lock connector is used and connects to the C200HS SYSMAC LINK and SYSMAC NET Link Units: S3200-COCF2511. The following full-lock connector is used and connects to the CV500 SYSMAC LINK and SYSMAC NET Link Units and the C1000H SYSMAC LINK Unit: S3200-COCF2011. This full-lock connector cannot be connected to the C200HS SYSMAC LINK and SYSMAC NET Link Units. The above connectors cannot be used for the C500 SYSMAC NET Link Unit, cable relays, and the SYSMAC NET Link Network Service Board. Refer to the SYSMAC NET Link System Manual for further information.

101

Page 109

Appendix A

Standard Models

Programming Devices Name Programming Console

Specifications

Model number

Hand-held, w/backlight; requires the C200H-CN222 or C200H-CN422, see below

C200H-PR027-E

2-m Connecting Cable attached.

CQM1-PRO01-E

Programming Console Mounting Bracket

Used to attach Hand-held Programming Console to a panel.

C200H-ATT01

Programming Console Connecting Cables

For Hand-held Programming Console

2m

C200H-CN222

4m

C200H-CN422

2m

C200HS-CN222

4m

C200HS-CN422

Provided with an anti-static cover and conforms to EC directives. Data Setting Console

Used for data input and process value display for the C200H-TCjjj, C200H-TVjjj, C200H-CP114, and C200H-PID0j.

C200H-DSC01

Data Setting Console Connecting Cables

For C200H-DSC01

2m

C200H-CN225

4m

C200H-CN425

Connecting Cable

Used to connect an IBM PC/AT or compatible to the C200HS.

3.3 m

CQM1-CIF02

Ladder Support Software (LSS) Name Ladder Support Software (for C20, CjjP, CjjK, C120, CjjH, C200H, C200HS, C500, C1000H, C2000H, and CQM1)

Specifications

Model number

5.25”, 2D for IBM PC/AT compatible

C500-SF711-EV3

3.5”, 2HD for IBM PC/AT compatible

C500-SF312-EV3

SYSMAC Support Software (SSS) Product SYSMAC Support Software

Description 3.5”, 2HD for IBM PC/AT compatible

Model no. C500-ZL3AT1-E

Training Materials Name

Specifications

Model number

SYSMAC Training System

Includes text book, cassette tape, and input switch board.

C200H-ETL01-E

Fuzzy Training System

Includes a Fuzzy Training System Manual, a Main Unit, a C200H-MR831 Memory Unit, a C200H-PRO27-E Programming Console, a C200H-CN222 Cable for the Programming Console, C500-SU381-E Fuzzy Training Software, an RS-232C Cable, and a carrying belt.

C200H-ETL13-E

102

Page 110

Appendix B Specifications The following figures and tables provide specifications for each Unit of the C200HS. I/O Units may take on one of three different shapes and are sometimes referred to as A-shape Units, B-shape Units, or E-shape Units. Group-2 High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape Units or D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these five shapes of I/O Unit.

CPUs and Power Supplies General Specifications Item

Supply Voltage

C200HS-CPU01-E/CPU01-EC/CPU21-E/ CPU21-EC/CPU31-E, C200H-PS221/PS221-C

C200HS-CPU03-E/CPU23-E/ CPU33-E, C200H-PS211 24 VDC

Operating Voltage Range

100 to 120/200 to 240 VAC selectable 50/60 Hz 85 to 132/170 to 264 VAC

Power Consumption

120 VA max.

40 W max.

Surge Current

30 A max.

30 A max.

Output Capacity

Fuse

CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E: 4.6 A, 5 VDC (3.9 A supplied to I/O Units) CPU03-E/CPU23-E/CPU33-E: 3 A, 5 VDC (2.3 A supplied to I/O Units) Expansion I/O Rack: 3 A, 5 VDC (2.7 A supplied to I/O Units) 2 A 250 V 5.2 dia. x 20 (MF51NR) 2 A 125 V 5.2 dia. x 20 (MF51NR)

24 VDC Output

0.3 A, 24 VDC +10%/–20%

None

Insulation Resistance

20 MΩ between AC terminals and the GR terminal at 500 VDC (See note 1.) 2,300 VAC at 50/60 Hz for 1 minute between AC terminals and housing; 1,000 VAC at 50/60 Hz for 1 minute between DC terminals and housing. Leakage current: 10 mA max. (See note 1.)

(See note 2.)

Dielectric Strength

20.4 to 26.4 VDC

(See note 2.)

Noise Immunity

1,500 Vp-p, pulse width: 100 ns to 1 µs, rise time: 1 ns pulse (by noise simulator)

Vibration

Shock

JIS C0911 conforming,10 to 57 Hz; 0.075 mm amplitude, 57 to 150 Hz; acceleration: 9.8 m/s2 (see note 3), in X, Y, and Z directions, for 80 minutes each (sweep time 8 min x 10 sweeps = 80 min); (When mounted on DIN track, 2 to 55 Hz, 2.94 m/s2, in X, Y, and Z directions, for 20 minutes each) JIS C0912 conforming, 147 m/s2 in X, Y, and Z directions, 3 times each

Ambient Temperature

Operating: 0° to 55°C; storage: –20° to 75°C (without battery)

Humidity

10% to 90% (without condensation)

Atmosphere

Must be free of the following: • Corrosive gases • Abrupt temperature changes • Direct sunlight • Dust, salt, or metal filings • Water, oil, or chemicals

Grounding

Connect to a ground of 100 Ω or less

Enclosure Rating

Mounted in a panel

Weight

6 kg max.

Note 1. Internal components might be damaged if insulation resistance or dielectric strength tests are conducted with the LG and GR terminals connected. 2. Do not conduct a dielectric strength test on the C200HS-CPU03-E/CPU23-E/CPU33-E, PS211, RT002-P, or RT202 Units. The power supply input line and internal circuit of the 24 VDC Power Supply

103