The text of a manual · part 11 of 23
SYSMAC C200HS Programmable Controllers Installation Guide, pages 101 to 110
Pages 101 to 110 of 221
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OC225 and Omron C200HW-SLK23
Page 101
Appendix A
Standard Models
C200H Standard I/O Units Name Input Units
AC Input Unit
100 to 120 VAC
C200H-IA121
16 pts
100 to 120 VAC
C200H-IA122/IA122V
8 pts
200 to 240 VAC
C200H-IA221
16 pts
200 to 240 VAC
C200H-IA222/IA222V
8 pts
No-voltage contact; NPN
C200H-ID001
8 pts
No-voltage contact; PNP
C200H-ID002
8 pts
12 to 24 VDC
C200H-ID211
16 pts
24 VDC
C200H-ID212
8 pts
12 to 24 VAC/DC
C200H-IM211
16 pts
24 VAC/DC
C200H-IM212
Interrupt Input Unit1
8 pts
12 to 24 VDC
C200HS-INT01
Contact Output Unit
8 pts
2 A, 250 VAC/24 VDC (For resistive loads)
C200H-OC221
12 pts
2 A, 250 VAC/24 VDC (For resistive loads)
C200H-OC222
16 pts
2 A, 250 VAC/24 VAC (For resistive loads)
C200H-OC2252, 3
5 pts
C200H-OC223
12 pts
2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 2 A, 250 VAC/24 VDC (For resistive loads)
16 pts
2 A, 250 VAC/24 VDC (For resistive loads)
C200H-OC226
8 pts
C200H-OC224V
8 pts
2 A, 250 VAC/24 VDC (For resistive loads) Independent commons 1 A, 120 VAC
8 pts
1.2 A, 120 VAC
C200H-OA122-E
8 pts
1.2 A 250 VAC
C200H-OA223
12 pts
0.3 A, 250 VAC
C200H-OA222V
12 pts
0.5 A, 250 VAC
C200H-OA224
8 pts 12 pts 16 pts
1 A, 12 to 48 VDC 0.3 A, 24 VDC 0.3 A, 24 VDC
C200H-OD411 C200H-OD211 C200H-OD2122
8 pts
2.1 A, 24 VDC
C200H-OD213
8 pts
C200H-OD214
8 pts
0.8 A, 24 VDC; source type (PNP); with load short protection 5 to 24 VDC; source type (PNP)
12 pts
5 to 24 VDC; source type (PNP)
C200H-OD217
1.0 A, 24 VDC; source type (PNP); with load short protection 4 timers 0.1 to 1 s/1 to 10 s/10 to 60 s/1 min to 10 min (switchable) Connector w/lead wire (2 m) for 1 external resistor
C200H-OD21A
16 input Connects to B7A Link Terminals. pts 16 output pts
C200H-B7AI1
AC/DC Input Unit
8 pts
Triac Output Unit
Transistor Output Unit
16 pts Analog Timer Unit Variable Resistor Connector Standard B7A Interface Units
94
Model number
8 pts
DC Input Unit
Output Units
Specifications
C200H-OC224 C200H-OC222V
C200H-OA121-E
C200H-OD216
C200H-TM001 C4K-CN223
C200H-B7AO1
Page 102
Appendix A
Standard Models
Note 1. If the Interrupt Input Unit is mounted on an Expansion I/O Rack, the interrupt function cannot be used and the Interrupt Input Unit will be treated as an ordinary 8-point Input Unit. Moreover, Interrupt Input Units cannot be used on Slave Racks. In addition, Interrupt Input Units require that a version 2 (i.e., model numbers with a “-V2” suffix) Backplane be used at the CPU Rack. If an earlier version Backplane is mounted, the interrupt function cannot be used. 2. Transistor Output Unit C200H-OD212/OD21A and Contact Output Unit C200H-OC225 must be mounted to either a C200H-BC031-V1/V2, C200H-BC051-V1/V2, C200H-BC081-V1/V2, or C200HBC101-V1/V2 Backplane. 3. The C200H-OC225 might overheat if more than 8 outputs are turned ON simultaneously.
C200H Group-2 High-density I/O Units Name DC Input Unit
Transistor Output Unit
Specifications 64 pts 32 pts
12 VDC 24 VDC
64 pts
24 VDC
32 pts
16 mA 4.5 VDC to 100 mA 26.4 VDC 0.5 A (5 A/Unit) 24 VDC 16 mA 4.5 VDC to 100 mA 26.4 VDC
64 pts
Model number C200H-ID111 C200H-ID216 C200H-ID218 C200H-ID217 C200H-ID219 C200H-OD218 C200H-OD21B C200H-OD219
C200H Group-2 B7A Interface Units Name Group-2 B7A Interface Units
Specifications Connects to B7A Link Terminals.
32 input pts 32 output pts 16 input pts and 16 output points 32 input pts and 32 output points
Model number C200H-B7A12 C200H-B7A02 C200H-B7A21 C200H-B7A22
C200H Special I/O Units All of the following are classified as Special I/O Units except for the ASCII Unit, which is an Intelligent I/O Unit. Name High-density I/O Units
DC Input Unit
Transistor Output Unit
Specifications
Model number
32 pts
5 VDC (TTL inputs); with high-speed input function
C200H-ID501
32 pts 32 pts
24 VDC; with high-speed inputs C200H-ID215 0.1 A, 24 VDC (usable as 128-point dynamic output unit) C200H-OD215
32 pts DC Input/ Transistor Output Unit
35 mA, 5 VDC (TTL outputs) (usable as 128-point dy- C200H-OD501 namic output unit) 16 input/ 12-VDC inputs; with high-speed input function C200H-MD115 16 output pts 0.1 A , 12-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 24-VDC inputs; with high-speed input function C200H-MD215 16 output pts 0.1 A , 24-VDC outputs (usable as 128-point dynamic input unit) 16 input/ 5 VDC (TTL inputs); with high speed input function 35 C200H-MD501 16 output pts mA, 5 VDC Output (TTL outputs) (usable as 128-point dynamic input unit)
95
Page 103
Appendix A
Standard Models Name Analog I/O Analog Input Units Unit Analog Output Unit Temperature Sensor Unit
Temperature Control Unit
Heat/Cool Temperature Control Unit
Specifications 4 to 20 mA, 1 to 5/0 to 10 V (switchable); 4 inputs
Model number C200H-AD001
4 to 20 mA, 1 to 5/0 to 10/–10 to 10 V (switchable); 8 inputs 4 to 20 mA, 1 to 5/0 to 10 V (switchable); 2 outputs
C200H-AD002 C200H-DA001
4 to 20 mA, –10 to 10 V; 4 outputs Thermocouple (K(CA) or J(IC)) (switchable); 4 inputs Thermocouple (K(CA) or L(Fe-CuNi)) (switchable); 4 inputs Platinum resistance thermometer (JPt) (switchable), DIN standards; 4 inputs Platinum resistance thermometer (Pt) (switchable); 4 inputs Thermocou- Transistor output ple Voltage output Current output Pt resisTransistor output tance therVoltage output mometer
C200H-DA002 C200H-TS001 C200H-TS002 C200H-TS101
Thermocouple
Pt resistance thermometer PID Control Unit
Position Control Unit
Cam Positioner Unit
High-speed Counter Unit
Voice Unit
96
Current output Transistor output
C200H-TC103 C200H-TV001
Voltage output Current output Transistor output
C200H-TV002 C200H-TV003 C200H-TV101
Voltage output
C200H-TV102 C200H-TV103 C200H-PID01 C200H-PID02 C200H-PID03 C200H-NC111 C200H-NC112
1 axis
C200H-CT001-V1
Pulse input; counting speed: 50 kcps; 5 VDC/12 VDC/24 VDC Pulse input; counting speed: 75 kcps; RS-422 line driver
EEPROM For connecting the ASCII Unit to the FIT10 (9P/25P) Cable length: 2 m Local application, electromagnetic coupling Remote application, microwave transmissions Read/Write Electromagnetic type Head Microwave type Data Carrier SRAM type for V600-H series. (see note) EEPROM type for V600-H series. 60 messages max.; message length: 32, 48, or 64 s (switchable) Connecting RS-232C Cable
Connecting Cable I/D Sensor Unit
C200H-TC102
Current output Transistor output Voltage output Current output 1 axis Pulse output; speeds: 1 to 99,990 pps 1 axis Directly connectable to servomotor driver; compatible with line driver; speeds: 1 to 250,000 pps 2 axis 1 to 250000. pps. 53 pts per axis Detects angles of rotation by means of a resolver and provides ON and OFF outputs at specified angles. A maximum of 48 cam outputs (16 external outputs and 32 internal outputs) maximum are available.
1 axis ASCII Unit
C200H-TS102 C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101
C200H-NC211 C200H-CP114
C200H-CT002 C200H-ASC02 CV500-CN228 C200H-IDS01-V1 C200H-IDS21 V600-H series V620-H series V600-DjjRjj V600-DjjPjj C200H-OV001 C200H-CN224
Page 104
Appendix A
Standard Models Name Fuzzy Logic Unit Fuzzy Support Software
Specifications Model number Up to 8 inputs and 4 outputs. (I/O to and from specified data area words) C200H-FZ001 C500-SU981-E Available on either 3.5” or 5.25” floppy disks.
Note For Read/Write Head and Data Carrier combinations, refer to the V600 FA ID System R/W Heads and EEPROM Data Carriers Operation Manual and Supplement or V600 FA ID System R/W Heads and SRAM Data Carriers Operation Manual and Supplement.
C200H Link Units Name Host Link Unit
Specifications Rack-mounting
C200H only
Model number APF/PCF
C200H-LK101-PV1
RS-422
C200H-LK202-V1
RS-232C
C200H-LK201-V1
PC Link Unit
Multilevel
RS-485
C200H-LK401
Remote I/O Master Unit
Up to two per PC; connectable to up to 5 Slaves per PC total
APF/PCF
C200H-RM001-PV1
Wired
C200H-RM201
SYSMAC LINK Unit/SYSMAC NET Link Units The SYSMAC LINK Units and SYSMAC NET Link Unit can only be used with the C200HS-CPU31-E and C200HSCPU33-E CPUs. Name SYSMAC LINK Unit
Specifications Wired via coaxial cable. Bus Connection Unit required separately. One C1000H-CE001 F Adapter included.
Wired via optical fiber cable. Bus Connection Unit required separately. An Optical Fiber Cable Bracket must be used to support an optical cable connected to the SYSMAC LINK Unit.
Model number Data link capacity: 918 words
C200HW-SLK23
Data link capacity: 2,966 words
C200HW-SLK24
Data link capacity: 918 words
C200HW-SLK13
Data link capacity: 2,966 words
C200HW-SLK14
Terminator
One required for each node at ends of System
C1000H-TER01
Attachment Stirrup
Provided with SYSMAC LINK Unit
C200H-TL001
F Adapter
---
C1000H-CE001
F Adapter Cover Communications Cable
---
C1000H-COV01
Coaxial cables
ECXF5C-2V 5C-2V C200H-APS03
Auxiliary Power Supply Unit SYSMAC NET Link Unit
Power Supply Adapter Power Cable
Manufactured by Hitachi Manufactured by Fujigura Supplies backup power to either one or two SYSMAC LINK Units. One C200H-CN111 Power Connecting Cable included. Bus Connection Unit required separately. An Optical Fiber Cable Bracket must be used to support an optical cable connected to the SYSMAC NET Link Unit. Required when supplying power from Central For 1 Unit Power Supply For 2 Units Connects Power Supply Adapter and SYSMAC NET Link Unit
For 1 Unit For 2 Units
C200HS-SNT32
C200H-APS01 C200H-APS02 C200H-CN111 C200H-CN211
97
Page 105
Appendix A
Standard Models Name Bus Connection Unit
Specifications Connects SYSMAC LINK Unit or SYSMAC NET Link Unit to C200HS-CPU31-E/CPU33-E
Model number For 1 Unit For 2 Units
C200H-CE001 C200H-CE002
CompoBus Units Name
Specifications
Model number
CompoBus/S Master Unit
---
C200HW-SRM21
CompoBus/D (DeviceNet) Master Unit
---
C200HW-DRM21
Optional Products Name
Specifications
Model number
I/O Unit Cover
Cover for 10-pin terminal block
C200H-COV11
Terminal Block Cover
Short protection for 10-pin terminal block
C200H-COV02
Short protection for 19-pin terminal block
C200H-COV03
Connector Cover
Protective cover for unused Backplane connectors
C500-COV01
Space Unit
Used for vacant slots
C200H-SP001
Battery Set
For C200H RAM Memory Unit only
C200H-BAT09
Relay
24 VDC
G6B-1174P-FD-US DC24
Backplane Insulation Plate
For 10-slot Backplane
C200H-ATTA1
For 8-slot Backplane
C200H-ATT81
For 5-slot Backplane
C200H-ATT51
For 3-slot Backplane
C200H-ATT31
For 10-slot Backplane
C200H-ATTA3
For 8-slot Backplane
C200H-ATT83
For 5-slot Backplane
C200H-ATT53
For 3-slot Backplane
C200H-ATT33
G6R-1
I/O Bracket
Note 1. When ordering, specify the model name (any component of which is not sold separately). 2. Order the press-fit tool from the manufacturer.
Mounting Rails and Accessories Name
Specifications
Model number
DIN Track Mounting Bracket
1 set (2 included)
C200H-DIN01
DIN Track
Length: 50 cm; height: 7.3 mm
PFP-50N
Length: 1 m; height: 7.3 mm
PFP-100N
Length: 1 m; height: 16 mm
PFP-100N2
End Plate
---
PFP-M
Spacer
---
PFP-S
98
Page 106
Appendix A
Standard Models
Link Adapters Name
Specifications
Link Adapter
Model number
3 RS-422 connectors
3G2A9-AL001
3 optical connectors (APF/PCF)
3G2A9-AL002-PE
3 optical connectors (PCF)
3G2A9-AL002-E
1 connector each for APF/PCF, RS-422, and RS-232C
3G2A9-AL004-PE
1 connector each for PCF, RS-422, and RS-232C
3G2A9-AL004-E
1 connector each for APF/PCF and APF
3G2A9-AL005-PE
1 connector each for PCF and AGF
3G2A9-AL005-E
1 connector for APF/PCF; 2 for AGF
3G2A9-AL006-PE
O/E converter; 1 connector for RS-485, 1 connector each for APF/PCF
B500-AL007-PE
Used for on-line removal of SYSMAC NET Link Units from the SYSMAC NET Link System, SYSMAC NET Optical Link Adapter 3 connectors for APF/PCF.
B700-AL001
SYSMAC BUS/SYSMAC WAY Optical Fiber Products Plastic Clad Optical Fiber Cable/All Plastic Optical Fiber Cable Name Plastic Clad Optical Fiber Cable (indoor)
Specifications 0.1 m, w/connectors 1 m, w/connectors
Model number Ambient temp: –10° to 70°C
3G5A2-OF011 3G5A2-OF101
2 m, w/connectors
3G5A2-OF201
3 m, w/connectors
3G5A2-OF301
5 m, w/connectors
3G5A2-OF501
10 m, w/connectors
3G5A2-OF111
20 m, w/connectors
3G5A2-OF211
30 m, w/connectors
3G5A2-OF311
40 m, w/connectors
3G5A2-OF411
50 m, w/connectors
3G5A2-OF511
Cable only; order desired length between 1 and 200 m in increments of 1 m.
B500-OF002
All Plastic Optical Fiber Cable
Cable only; order desired length in 5 m increments between 5 and 100 m, or in increments of 200 m or 500 m.
B500-PF002
Optical Connectors A
Two optical connectors (brown) for APF (10 m max.)
3G5A2-CO001
Optical Connectors B
Two optical connectors (black) for APF (8 to 20 m)
3G5A2-CO002
All Plastic Optical Fiber Cable Set 1-m cable with an Optical Connector A connected to each end
3G5A2-PF101
Optical Fiber Processing Kit
3G2A9-TL101
Accessory: 125-mm nipper (Muromoto Tekko’s 550M) for APF
99
Page 107
Appendix A
Standard Models H-PCF Name Optical Fiber Cable SYSMAC BUS, SYSMAC WAY
Specifications 10 m, black
S3200-HCCB101
50 m, black
S3200-HCCB501
100 m, black
S3200-HCCB102
500 m, black
S3200-HCCB502
1000 m, black
S3200-HCCB103
10 m, orange
S3200-HCCO101
50 m, orange
S3200-HCCO501
100 m, orange
S3200-HCCO102
500 m, orange
S3200-HCCO502
1000 m, orange
S3200-HCCO103
10 m, black
Optical Fiber Cable Connector
Model number Two-core cable
Two-core cable
S3200-HBCB101
50 m, black
S3200-HBCB501
100 m, black
S3200-HBCB102
500 m, black
S3200-HBCB502
1000 m, black
S3200-HBCB103
SYSMAC BUS: C200H-RM001-PV1 C200H-RT001/RT002-P C500-RM001-(P)V1 C500-RT001/RT002-(P)V1 B500-jjj(-P)
Half-lock connector S3200-COCH82 for Remote I/O Master, Remote I/O Slave, Host Link Unit, and Link Adapter
Note 1. Optical fiber cables must be prepared and connected by specialists. 2. If the user prepares and connects optical fiber cables, the user must take a seminar held under the auspices of Sumitomo Electric Industries, Ltd. and obtain a proper certificate. 3. The Optical Power Tester, Head Unit, Master Fiber Set, and Optical Fiber Assembling Tool are required to connect optical fiber cables. Optical Fiber Assembling Tool Name Optical Fiber Assembling Tool
Specifications
Model number
Used to connect H-PCF and crimp-cut connectors for optical transmission systems such as the SYSMAC C- and CV-series SYSMAC BUS, SYSMAC LINK and SYSMAC NET.
S3200-CAK1062
Note 1. Optical fiber cables must be prepared and connected by specialists. 2. The Optical Power Tester, Head Unit, Master Fiber set, and Optical Fiber Assembling Tool are required to connect optical fiber cables. Optical Power Tester Name
Specifications
Head Unit
Optical Power Tester (see note) (provided with a connector adapter, light source unit, small single-head plug, hard case, and AC adapter)
SYSMAC BUS: C200H-RM001-PV1 C200H-RT001/RT002-P C500-RM001-(P)V1 C500-RT001/RT002-(P)V1
S3200-CAT2822 (provided with the Tester)
Model number S3200-CAT2820
Note: There is no difference between the light source unit and connector adapter for the Head Unit and those for the Optical Power Tester.
100
Page 108
Appendix A
Standard Models Head Unit Name
Specifications
Head Unit (a set consisting of light source unit and connector adapter) (see note)
Model number
SYSMAC BUS: C200H-RM001-PV1 C200H-RT001/RT002-P
S3200-CAT2822
SYSMAC NET: S3200-LSU03-V1/LSU03-01E C500-SNT31-V4 3G8FX-TM111 3G8SX-TM111
S3200-CAT3202
Note: Use a proper Head Unit model for the optical module to be used. If two types of optical modules (unit type and board type) are used, order an Optical Power Tester plus a proper Head Unit model. Master Fiber Set Name Master Fiber Set (1 m)
Specifications
Model number
S3200-CAT3202 (SYSMAC NET, NSB, NSU, Bridge)
S3200-CAT3201
S3200-CAT2002/CAT2702 (SYSMAC NET, SYSMAC LINK)
S3200-CAT2001H
S3200-CAT2822 (SYSMAC BUS)
S3200-CAT2821
Note 1. The Master Fiber Set is used in combination with the Optical Power Tester to check the optical levels of optical fiber cables connected to optical fiber cable connectors. 2. Optical fiber cables must be prepared and connected by specialists. 3. The Optical Power Tester, Head Unit, Master Fiber set, and Optical Fiber Assembling Tool are required to connect optical fiber cables.
SYSMAC LINK/SYSMAC NET Link Optical Fiber Products Optical Fiber Cables for SYSMAC LINK and SYSMAC NET Link Systems Use hard-plastic-clad quartz optical fiber (H-PCF) cables for SYSMAC LINK and SYSMAC NET Link Systems. H-PCF cables are available with connectors already attached, or cables and connectors can be purchased separately and assembled by the user. Refer to the System Manual for the SYSMAC LINK or SYSMAC NET Link Systems for assembly procedures. Models numbers for H-PCF cables with connecters attached are provided in the following illustration. Model Numbers for H-PCF Cables with Connectors
S3200-CNjjj-jj-jj
Cable length 201: 501: 102: 152: 202: Blank:
2m 5m 10 m 15 m 20 m Over 20 m (Specify.)
Connectors 20-25:
Full-lock connector on one end, half-lock connector on other end.
25-25:
Half-lock connectors on both ends.
An Optical Fiber Cable Bracket must be used to support an optical fiber cable connected to the C200HS-SNT32 SYSMAC NET Link Unit or C200HW-SLK13/SLK14 SYSMAC LINK Unit. User optical fiber cables with both tension members and power supply lines. The following half-lock connector is used and connects to the C200HS SYSMAC LINK and SYSMAC NET Link Units: S3200-COCF2511. The following full-lock connector is used and connects to the CV500 SYSMAC LINK and SYSMAC NET Link Units and the C1000H SYSMAC LINK Unit: S3200-COCF2011. This full-lock connector cannot be connected to the C200HS SYSMAC LINK and SYSMAC NET Link Units. The above connectors cannot be used for the C500 SYSMAC NET Link Unit, cable relays, and the SYSMAC NET Link Network Service Board. Refer to the SYSMAC NET Link System Manual for further information.
101
Page 109
Appendix A
Standard Models
Programming Devices Name Programming Console
Specifications
Model number
Hand-held, w/backlight; requires the C200H-CN222 or C200H-CN422, see below
C200H-PR027-E
2-m Connecting Cable attached.
CQM1-PRO01-E
Programming Console Mounting Bracket
Used to attach Hand-held Programming Console to a panel.
C200H-ATT01
Programming Console Connecting Cables
For Hand-held Programming Console
2m
C200H-CN222
4m
C200H-CN422
2m
C200HS-CN222
4m
C200HS-CN422
Provided with an anti-static cover and conforms to EC directives. Data Setting Console
Used for data input and process value display for the C200H-TCjjj, C200H-TVjjj, C200H-CP114, and C200H-PID0j.
C200H-DSC01
Data Setting Console Connecting Cables
For C200H-DSC01
2m
C200H-CN225
4m
C200H-CN425
Connecting Cable
Used to connect an IBM PC/AT or compatible to the C200HS.
3.3 m
CQM1-CIF02
Ladder Support Software (LSS) Name Ladder Support Software (for C20, CjjP, CjjK, C120, CjjH, C200H, C200HS, C500, C1000H, C2000H, and CQM1)
Specifications
Model number
5.25”, 2D for IBM PC/AT compatible
C500-SF711-EV3
3.5”, 2HD for IBM PC/AT compatible
C500-SF312-EV3
SYSMAC Support Software (SSS) Product SYSMAC Support Software
Description 3.5”, 2HD for IBM PC/AT compatible
Model no. C500-ZL3AT1-E
Training Materials Name
Specifications
Model number
SYSMAC Training System
Includes text book, cassette tape, and input switch board.
C200H-ETL01-E
Fuzzy Training System
Includes a Fuzzy Training System Manual, a Main Unit, a C200H-MR831 Memory Unit, a C200H-PRO27-E Programming Console, a C200H-CN222 Cable for the Programming Console, C500-SU381-E Fuzzy Training Software, an RS-232C Cable, and a carrying belt.
C200H-ETL13-E
102
Page 110
Appendix B Specifications The following figures and tables provide specifications for each Unit of the C200HS. I/O Units may take on one of three different shapes and are sometimes referred to as A-shape Units, B-shape Units, or E-shape Units. Group-2 High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape Units or D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these five shapes of I/O Unit.
CPUs and Power Supplies General Specifications Item
Supply Voltage
C200HS-CPU01-E/CPU01-EC/CPU21-E/ CPU21-EC/CPU31-E, C200H-PS221/PS221-C
C200HS-CPU03-E/CPU23-E/ CPU33-E, C200H-PS211 24 VDC
Operating Voltage Range
100 to 120/200 to 240 VAC selectable 50/60 Hz 85 to 132/170 to 264 VAC
Power Consumption
120 VA max.
40 W max.
Surge Current
30 A max.
30 A max.
Output Capacity
Fuse
CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E: 4.6 A, 5 VDC (3.9 A supplied to I/O Units) CPU03-E/CPU23-E/CPU33-E: 3 A, 5 VDC (2.3 A supplied to I/O Units) Expansion I/O Rack: 3 A, 5 VDC (2.7 A supplied to I/O Units) 2 A 250 V 5.2 dia. x 20 (MF51NR) 2 A 125 V 5.2 dia. x 20 (MF51NR)
24 VDC Output
0.3 A, 24 VDC +10%/–20%
None
Insulation Resistance
20 MΩ between AC terminals and the GR terminal at 500 VDC (See note 1.) 2,300 VAC at 50/60 Hz for 1 minute between AC terminals and housing; 1,000 VAC at 50/60 Hz for 1 minute between DC terminals and housing. Leakage current: 10 mA max. (See note 1.)
(See note 2.)
Dielectric Strength
20.4 to 26.4 VDC
(See note 2.)
Noise Immunity
1,500 Vp-p, pulse width: 100 ns to 1 µs, rise time: 1 ns pulse (by noise simulator)
Vibration
Shock
JIS C0911 conforming,10 to 57 Hz; 0.075 mm amplitude, 57 to 150 Hz; acceleration: 9.8 m/s2 (see note 3), in X, Y, and Z directions, for 80 minutes each (sweep time 8 min x 10 sweeps = 80 min); (When mounted on DIN track, 2 to 55 Hz, 2.94 m/s2, in X, Y, and Z directions, for 20 minutes each) JIS C0912 conforming, 147 m/s2 in X, Y, and Z directions, 3 times each
Ambient Temperature
Operating: 0° to 55°C; storage: –20° to 75°C (without battery)
Humidity
10% to 90% (without condensation)
Atmosphere
Must be free of the following: • Corrosive gases • Abrupt temperature changes • Direct sunlight • Dust, salt, or metal filings • Water, oil, or chemicals
Grounding
Connect to a ground of 100 Ω or less
Enclosure Rating
Mounted in a panel
Weight
6 kg max.
Note 1. Internal components might be damaged if insulation resistance or dielectric strength tests are conducted with the LG and GR terminals connected. 2. Do not conduct a dielectric strength test on the C200HS-CPU03-E/CPU23-E/CPU33-E, PS211, RT002-P, or RT202 Units. The power supply input line and internal circuit of the 24 VDC Power Supply
103