For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 111

Appendix B

Specifications are not isolated from each other. If a dielectric strength test is conducted at 50 VDC or higher, internal components such as capacitors will be damaged. If a short-circuit test must be conducted, use a device such as a tester. 3. Acceleration (G)

1

Amplitude 0.075 mm

10

57

150 Frequency (Hz)

C200HS Dimensions M4

130 118

(135)

6.5

A

7.5

D

W

Backplane

A

W

C200H-BC031-V2

246

260

C200H-BC051-V2

316

330

C200H-BC081-V2

421

435

C200H-BC101-V2

491

505

D CPU01-E/CPU01-EC/ CPU03-E

CPU21-E/CPU21-EC/ CPU23-E/CPU31-E/ CPU33-E

118

143

Note 1. All units are in millimeters. 2. For dimensions of individual units and Backplane, refer to page 193 onward.

104

Page 112

Appendix B

Specifications

CPU Specifications Control Method

Stored program

I/O Control Method Programming Method Instruction Length

Cyclic scan and immediate processing are both possible.

Number of Instructions Execution Time

CPU01-E/01-EC/03-E/21-E/23-E: 225 (14 basic instructions + 211 special instructions) CPU31-E/33-E: 229 (14 basic instructions + 215 special instructions) Basic instructions: 0.375 to 1.313 µs Special instructions: Approx. 10 µs

Program Capacity

15.2K words max.

IR Area: I/O bits

480 bits (00000 through 02915)

IR Area: Work bits

6,688 bits (03000 through 23515, 30000 through 51115)

SR bits

1,016 (23600 through 25507 and 25600 through 29915)

TR bits

8 (TR 0 through 7)

HR bits

1,600 (HR 0000 through 9915)

AR bits

448 (AR 0000 through 2715)

LR bits

1,024 (LR 0000 through 6315)

Timers/Counters

512 (TIM/CNT 000 through 511) TIMs: 0 through 999.9 s TIMHs: 0 through 99.99 s CNT: 0 through 9999 counts Read/write: 6,144 (DM 0000 through 6143) Read only: 512 (DM 6144 through 6655) 3,000 words max. (DM 7000 through 9999)

DM words

RUN Output

Power Failure Backup Function Clock Function Memory Backup Time

Self-diagnostic Function Program Check Function

Ladder diagram 1 address/instruction, 1 to 4 words/instruction

I/O bits for Group-2 High-density Units and Group-2 B7A Interface Units: 320 bits (03000 through 04915)

I/O bits for I/O Units mounted to Slave Racks: 800 bits (05000 through 09915)

I/O bits for Special I/O Units: 1,600 bits (10000 through 19915)

I/O bits for Optical I/O Units: 512 bits (20000 through 23115)

Contacts are closed while PC is in RUN mode and operating. Max. switching capacity: 2A 250 VAC (resistive load) 0.5 A 250 VAC (inductive load, cosφ = 0.4) 2 A 24 VDC Holds HR, AR, CNT, and DM, and clock (RTC) contents. Standard The battery service life is five years at 25°C. The service life will be shortened if the battery is used at higher temperatures. Replace the battery within one week after the battery alarm indicator starts blinking. When replacing the battery, install the new battery within five minutes after removing the old one. CPU errors (watchdog timer), I/O verification errors, host link errors, memory errors, battery errors, I/O bus errors, remote I/O errors, etc. Carries out program checks at the beginning of operation for items such as no END instruction, instruction errors, and so on.

105

Page 113

Appendix B

Specifications

Standard I/O Units AC Input Unit C200H-IA121 Rated Input Voltage

100 to 120 VAC 50/60 Hz

Operating Input Voltage

85 to 132 VAC 50/60 Hz

Input Impedance

9.7 kW (50 Hz), 8 kW (60 Hz)

Input Current

10 mA typical (at 100 VAC)

ON Voltage

60 VAC min.

OFF Voltage

20 VAC max.

ON Response Time

35 ms max. (at 100 VAC, 25°C)

OFF Response Time

55 ms max. (at 100 VAC, 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

250 g max.

Dimensions

A-shape

Circuit Configuration IN

100 to 120 VAC

IN

0.33 mF 470 W

330 kW COM

Internal Circuit

910 W

Input indicator

Terminal Connections 0 A0 1 2 100 to 120 VAC

3 4 5 6 7 COM

NC

106

A1 A2 A3 A4 A5 A6 A7 A8 A9

Page 114

Appendix B

Specifications

AC Input Unit C200H-IA122/IA122V Rated Input Voltage

100 to 120 VAC 50/60 Hz

Operating Input Voltage

85 to 132 VAC 50/60 Hz

Input Impedance

9.7 kW (50 Hz), 8 kW (60 Hz)

Input Current

10 mA typical (at 100 VAC)

ON Voltage

60 VAC min.

OFF Voltage

20 VAC max.

ON Response Time

35 ms max. (at 100 VAC, 25°C)

OFF Response Time

55 ms max. (at 100 VAC, 25°C)

No. of Circuits

1 (16 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

300 g max./400 g max. (IA122V)

Dimensions

B-shape

Circuit Configuration IN

100 to 120 VAC

IN

0.33 mF 470 W

330 kW COM

Internal Circuit

910 W

Input indicator

Terminal Connections

1 3 5 100 to 120 VAC

7 9 11 13 15 COM

B0 A0 A1 A2 A3

0

B1

2

B2

4

B3

6

B4

8

A4

B5 10

A5

B6 12 B7 14

A6 A7 A8

B8

NC

B9

NC

107

Page 115

Appendix B

Specifications

AC Input Unit C200H-IA221 Rated Input Voltage

200 to 240 VAC 50/60 Hz

Operating Input Voltage

170 to 264 VAC 50/60 Hz

Input Impedance

21 kW (50 Hz), 18 kW (60 Hz)

Input Current

10 mA typical (at 200 VAC)

ON Voltage

120 VAC min.

OFF Voltage

40 VAC max.

ON Response Time

35 ms max. (at 200 VAC, 25°C)

OFF Response Time

55 ms max. (at 200 VAC, 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

250 g max.

Dimensions

A-shape

Circuit Configuration IN

IN

0.15 mF 820 Ω

200 to 240 VAC 680 kW COM

Internal Circuit

910 Ω

Input indicator

Terminal Connections 0 A0 1 2 200 to 240 VAC

3 4 5 6 7 COM

NC

108

A1 A2 A3 A4 A5 A6 A7 A8 A9

Page 116

Appendix B

Specifications

AC Input Unit C200H-IA222/IA222V Rated Input Voltage

200 to 240 VAC 50/60 Hz

Operating Input Voltage

170 to 264 VAC 50/60 Hz

Input Impedance

21 kW (50 Hz), 18 kW (60 Hz)

Input Current

10 mA typical (at 200 VAC)

ON Voltage

120 VAC min.

OFF Voltage

40 VAC max.

ON Response Time

35 ms max. (at 200 VAC, 25°C)

OFF Response Time

55 ms max. (at 200 VAC, 25°C)

No. of Circuits

1 (16 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

300 g max./400 g max. (IA222V)

Dimensions

B-shape

Circuit Configuration IN

IN

0.15 mF 680 Ω

200 to 240 VAC 680 kW COM

Internal Circuit

910 Ω

Input indicator

Terminal Connections

1 3 5 200 to 240 VAC

7 9 11 13 15 COM

B0 A0 A1 A2 A3

0

B1

2

B2

4

B3

6

B4

8

A4

B5 10

A5

B6 12 B7 14

A6 A7 A8

B8

NC

B9

NC

109

Page 117

Appendix B

Specifications

No-Voltage Contact Input Unit C200H-ID001 Input Voltage Input Impedance

No-voltage contact/NPN output type (negative common) 3 kW

Input Current

7 mA typical

ON Voltage

(14.4 VDC min.)

OFF Voltage

(5.0 VDC max.)

ON Response Time

1.5 ms max. (no-voltage contact, at 25°C)

OFF Response Time

1.5 ms max. (no-voltage contact, at 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration Current

IN

IN

COM

3 kW 0.01 mF

Internal Circuit

1.8 kW

Input indicator

0.3 A 24 VDC Power supply

+ Internal 24-VDC – power supply CPU, Expansion I/O Power Supply, Remote I/O Slave Unit

Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals. Terminal Connections 0 1 2 3 Current (NPN output)

4 5 6 7 COM NC

110

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

Page 118

Appendix B

Specifications

No-Voltage Contact Input Unit C200H-ID002 Input Voltage Input Impedance

No-voltage contact/PNP output type (positive common) 3 kW

Input Current

7 mA typical

ON Voltage

(14.4 VDC min.)

OFF Voltage

(5.0 VDC max.)

ON Response Time

1.5 ms max. (no-voltage contact, at 25°C)

OFF Response Time

1.5 ms max. (no-voltage contact, at 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration IN

IN

COM

3 kW 0.01 mF

Internal Circuit

1.8 kW

Current

Input indicator

0.3 A 24 VDC

+ Internal 24-VDC – power supply

Power supply

CPU, Expansion I/O Power Supply, Remote I/O Slave Unit

Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals. Terminal Connections 0 1 2 3 Current (PNP output)

4 5 6 7 COM NC

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

111

Page 119

Appendix B

Specifications

DC Input Unit C200H-ID211 Rated Input Voltage

12 to 24 VDC

Operating Input Voltage

10.2 to 26.4 VDC

Input Impedance

2 kW

Input Current

10 mA (at 24 VDC)

ON Voltage

10.2 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time

1.5 ms max. (at 24 VDC, 25°C)

OFF Response Time

1.5 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (8 point/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration IN

IN

2 kW

COM

0.01 mF

Internal Circuit

1.8 kW

12 to 24 VDC

Input indicator

Terminal Connections 0 1 2 3 12 to 24 VDC

4 5 6 7 COM

NC

112

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

Page 120

Appendix B

Specifications

DC Input Unit C200H-ID212 Rated Input Voltage

24 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Input Impedance

3 kW

Input Current

7 mA (at 24 VDC)

ON Voltage

14.4 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

1.5 ms max. (at 24 VDC, 25°C)

OFF Response Time

1.5 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (16 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

300 g max.

Dimensions

B-shape

Circuit Configuration IN

IN

3 kW

COM

0.01 mF

Internal Circuit

1.8 kW

24 VDC

Input indicator

Terminal Connections

1 3 5 7 24 VDC

9 11 13 15 COM

A0 A1 A2 A3 A4 A5 A6 A7 A8

B0

0

B1

2

B2

4

B3

6

B4

8

B5 10 B6 12 B7 14 B8

NC

B9

NC

113