Page 111
Appendix B
Specifications are not isolated from each other. If a dielectric strength test is conducted at 50 VDC or higher, internal components such as capacitors will be damaged. If a short-circuit test must be conducted, use a device such as a tester. 3. Acceleration (G)
1
Amplitude 0.075 mm
10
57
150 Frequency (Hz)
C200HS Dimensions M4
130 118
(135)
6.5
A
7.5
D
W
Backplane
A
W
C200H-BC031-V2
246
260
C200H-BC051-V2
316
330
C200H-BC081-V2
421
435
C200H-BC101-V2
491
505
D CPU01-E/CPU01-EC/ CPU03-E
CPU21-E/CPU21-EC/ CPU23-E/CPU31-E/ CPU33-E
118
143
Note 1. All units are in millimeters. 2. For dimensions of individual units and Backplane, refer to page 193 onward.
104
Page 112
Appendix B
Specifications
CPU Specifications Control Method
Stored program
I/O Control Method Programming Method Instruction Length
Cyclic scan and immediate processing are both possible.
Number of Instructions Execution Time
CPU01-E/01-EC/03-E/21-E/23-E: 225 (14 basic instructions + 211 special instructions) CPU31-E/33-E: 229 (14 basic instructions + 215 special instructions) Basic instructions: 0.375 to 1.313 µs Special instructions: Approx. 10 µs
Program Capacity
15.2K words max.
IR Area: I/O bits
480 bits (00000 through 02915)
IR Area: Work bits
6,688 bits (03000 through 23515, 30000 through 51115)
SR bits
1,016 (23600 through 25507 and 25600 through 29915)
TR bits
8 (TR 0 through 7)
HR bits
1,600 (HR 0000 through 9915)
AR bits
448 (AR 0000 through 2715)
LR bits
1,024 (LR 0000 through 6315)
Timers/Counters
512 (TIM/CNT 000 through 511) TIMs: 0 through 999.9 s TIMHs: 0 through 99.99 s CNT: 0 through 9999 counts Read/write: 6,144 (DM 0000 through 6143) Read only: 512 (DM 6144 through 6655) 3,000 words max. (DM 7000 through 9999)
DM words
RUN Output
Power Failure Backup Function Clock Function Memory Backup Time
Self-diagnostic Function Program Check Function
Ladder diagram 1 address/instruction, 1 to 4 words/instruction
I/O bits for Group-2 High-density Units and Group-2 B7A Interface Units: 320 bits (03000 through 04915)
I/O bits for I/O Units mounted to Slave Racks: 800 bits (05000 through 09915)
I/O bits for Special I/O Units: 1,600 bits (10000 through 19915)
I/O bits for Optical I/O Units: 512 bits (20000 through 23115)
Contacts are closed while PC is in RUN mode and operating. Max. switching capacity: 2A 250 VAC (resistive load) 0.5 A 250 VAC (inductive load, cosφ = 0.4) 2 A 24 VDC Holds HR, AR, CNT, and DM, and clock (RTC) contents. Standard The battery service life is five years at 25°C. The service life will be shortened if the battery is used at higher temperatures. Replace the battery within one week after the battery alarm indicator starts blinking. When replacing the battery, install the new battery within five minutes after removing the old one. CPU errors (watchdog timer), I/O verification errors, host link errors, memory errors, battery errors, I/O bus errors, remote I/O errors, etc. Carries out program checks at the beginning of operation for items such as no END instruction, instruction errors, and so on.
105
Page 113
Appendix B
Specifications
Standard I/O Units AC Input Unit C200H-IA121 Rated Input Voltage
100 to 120 VAC 50/60 Hz
Operating Input Voltage
85 to 132 VAC 50/60 Hz
Input Impedance
9.7 kW (50 Hz), 8 kW (60 Hz)
Input Current
10 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Response Time
35 ms max. (at 100 VAC, 25°C)
OFF Response Time
55 ms max. (at 100 VAC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration IN
100 to 120 VAC
IN
0.33 mF 470 W
330 kW COM
Internal Circuit
910 W
Input indicator
Terminal Connections 0 A0 1 2 100 to 120 VAC
3 4 5 6 7 COM
NC
106
A1 A2 A3 A4 A5 A6 A7 A8 A9
Page 114
Appendix B
Specifications
AC Input Unit C200H-IA122/IA122V Rated Input Voltage
100 to 120 VAC 50/60 Hz
Operating Input Voltage
85 to 132 VAC 50/60 Hz
Input Impedance
9.7 kW (50 Hz), 8 kW (60 Hz)
Input Current
10 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Response Time
35 ms max. (at 100 VAC, 25°C)
OFF Response Time
55 ms max. (at 100 VAC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
300 g max./400 g max. (IA122V)
Dimensions
B-shape
Circuit Configuration IN
100 to 120 VAC
IN
0.33 mF 470 W
330 kW COM
Internal Circuit
910 W
Input indicator
Terminal Connections
1 3 5 100 to 120 VAC
7 9 11 13 15 COM
B0 A0 A1 A2 A3
0
B1
2
B2
4
B3
6
B4
8
A4
B5 10
A5
B6 12 B7 14
A6 A7 A8
B8
NC
B9
NC
107
Page 115
Appendix B
Specifications
AC Input Unit C200H-IA221 Rated Input Voltage
200 to 240 VAC 50/60 Hz
Operating Input Voltage
170 to 264 VAC 50/60 Hz
Input Impedance
21 kW (50 Hz), 18 kW (60 Hz)
Input Current
10 mA typical (at 200 VAC)
ON Voltage
120 VAC min.
OFF Voltage
40 VAC max.
ON Response Time
35 ms max. (at 200 VAC, 25°C)
OFF Response Time
55 ms max. (at 200 VAC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
0.15 mF 820 Ω
200 to 240 VAC 680 kW COM
Internal Circuit
910 Ω
Input indicator
Terminal Connections 0 A0 1 2 200 to 240 VAC
3 4 5 6 7 COM
NC
108
A1 A2 A3 A4 A5 A6 A7 A8 A9
Page 116
Appendix B
Specifications
AC Input Unit C200H-IA222/IA222V Rated Input Voltage
200 to 240 VAC 50/60 Hz
Operating Input Voltage
170 to 264 VAC 50/60 Hz
Input Impedance
21 kW (50 Hz), 18 kW (60 Hz)
Input Current
10 mA typical (at 200 VAC)
ON Voltage
120 VAC min.
OFF Voltage
40 VAC max.
ON Response Time
35 ms max. (at 200 VAC, 25°C)
OFF Response Time
55 ms max. (at 200 VAC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
300 g max./400 g max. (IA222V)
Dimensions
B-shape
Circuit Configuration IN
IN
0.15 mF 680 Ω
200 to 240 VAC 680 kW COM
Internal Circuit
910 Ω
Input indicator
Terminal Connections
1 3 5 200 to 240 VAC
7 9 11 13 15 COM
B0 A0 A1 A2 A3
0
B1
2
B2
4
B3
6
B4
8
A4
B5 10
A5
B6 12 B7 14
A6 A7 A8
B8
NC
B9
NC
109
Page 117
Appendix B
Specifications
No-Voltage Contact Input Unit C200H-ID001 Input Voltage Input Impedance
No-voltage contact/NPN output type (negative common) 3 kW
Input Current
7 mA typical
ON Voltage
(14.4 VDC min.)
OFF Voltage
(5.0 VDC max.)
ON Response Time
1.5 ms max. (no-voltage contact, at 25°C)
OFF Response Time
1.5 ms max. (no-voltage contact, at 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration Current
IN
IN
COM
3 kW 0.01 mF
Internal Circuit
1.8 kW
Input indicator
0.3 A 24 VDC Power supply
+ Internal 24-VDC – power supply CPU, Expansion I/O Power Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals. Terminal Connections 0 1 2 3 Current (NPN output)
4 5 6 7 COM NC
110
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
Page 118
Appendix B
Specifications
No-Voltage Contact Input Unit C200H-ID002 Input Voltage Input Impedance
No-voltage contact/PNP output type (positive common) 3 kW
Input Current
7 mA typical
ON Voltage
(14.4 VDC min.)
OFF Voltage
(5.0 VDC max.)
ON Response Time
1.5 ms max. (no-voltage contact, at 25°C)
OFF Response Time
1.5 ms max. (no-voltage contact, at 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
COM
3 kW 0.01 mF
Internal Circuit
1.8 kW
Current
Input indicator
0.3 A 24 VDC
+ Internal 24-VDC – power supply
Power supply
CPU, Expansion I/O Power Supply, Remote I/O Slave Unit
Note The power is supplied to the Input Units from the 24 VDC output of the Power Supply of the CPU, Expansion I/O Unit, or Remote I/O Unit. Never connect 24 VDC output terminals to the input terminals or COM terminals. Terminal Connections 0 1 2 3 Current (PNP output)
4 5 6 7 COM NC
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
111
Page 119
Appendix B
Specifications
DC Input Unit C200H-ID211 Rated Input Voltage
12 to 24 VDC
Operating Input Voltage
10.2 to 26.4 VDC
Input Impedance
2 kW
Input Current
10 mA (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
1.5 ms max. (at 24 VDC, 25°C)
OFF Response Time
1.5 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (8 point/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
2 kW
COM
0.01 mF
Internal Circuit
1.8 kW
12 to 24 VDC
Input indicator
Terminal Connections 0 1 2 3 12 to 24 VDC
4 5 6 7 COM
NC
112
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
Page 120
Appendix B
Specifications
DC Input Unit C200H-ID212 Rated Input Voltage
24 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Input Impedance
3 kW
Input Current
7 mA (at 24 VDC)
ON Voltage
14.4 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
1.5 ms max. (at 24 VDC, 25°C)
OFF Response Time
1.5 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration IN
IN
3 kW
COM
0.01 mF
Internal Circuit
1.8 kW
24 VDC
Input indicator
Terminal Connections
1 3 5 7 24 VDC
9 11 13 15 COM
A0 A1 A2 A3 A4 A5 A6 A7 A8
B0
0
B1
2
B2
4
B3
6
B4
8
B5 10 B6 12 B7 14 B8
NC
B9
NC
113