Page 121

Appendix B

Specifications

AC/DC Input Unit C200H-IM211 Rated Input Voltage

12 to 24 VDC

Operating Input Voltage

10.2 to 26.4 VDC

Input Impedance

2 kW

Input Current

10 mA typical (at 24 VDC)

ON Voltage

10.2 VDC min.

OFF Voltage

3.0 VDC max.

ON Response Time

15 ms max. (at 24 VDC, 25°C)

OFF Response Time

15 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (8 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

200 g max.

Dimensions

A-shape

Circuit Configuration IN

IN

COM

2 kW 0.01 mF

1.8 kW

Internal Circuit

12 to 24 VAC/DC Input indicator

Terminal Connections 0 1 2 3 12 to 24 VAC/DC

4 5 6 7 COM

NC

114

A0 A1 A2 A3 A4 A5 A6 A7 A8 A9

Page 122

Appendix B

Specifications

AC/DC Input Unit C200H-IM212 Rated Input Voltage

24 VDC

Operating Input Voltage

20.4 to 26.4 VDC

Input Impedance

3 kW

Input Current

7 mA typical (at 24 VDC)

ON Voltage

14.4 VDC min.

OFF Voltage

5.0 VDC max.

ON Response Time

15 ms max. (at 24 VDC, 25°C)

OFF Response Time

15 ms max. (at 24 VDC, 25°C)

No. of Circuits

1 (16 points/common)

Internal Current Consumption

10 mA 5 VDC max.

Weight

250 g max.

Dimensions

B-shape

Circuit Configuration IN

IN

COM

3 kW 0.01 mF

1.8 kW

Internal Circuit

24 VAC/DC Input indicator

Terminal Connections

1 3 5 7

24 VAC/DC

9 11 13 15 COM

B0 A0 A1 A2 A3 A4 A5 A6 A7 A8

0

B1

2

B2

4

B3

6

B4

8

B5 10 B6 12 B7 14 B8

NC

B9

NC

115

Page 123

Appendix B

Specifications

Triac Output Unit C200H-OA121-E Max. switching capacity

1 A 120 VAC, 50/60 Hz (4 A/Unit)

Min. switching capacity Leakage Current

10 mA (resistive load)/40 mA (inductive load) 10 VAC 3 mA (100 VAC) max.

Residual Voltage

1.2 V max.

ON Response Time

1 ms max.

OFF Response Time

1/2 of load frequency or less.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

140 mA 5 VDC max.

Fuse Rating

5 A 125 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

250 g max.

Dimensions

A-shape

Circuit Configuration OUT Output LED indicator

OUT

Internal circuit

Fuse

L

L

COM 120 VAC max.

Fuse blowout detection circuit F indicator Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)

Note When the fuse blows, F indicator lights and bit 08 turns ON. Bits 08 through15 cannot be used as IR bits. Terminal Connections

L

120 VAC max. (1 A max. 4 A/Unit)

116

0 1 2 3 4 5 6 7

A0 A1 L A2 L A3 L A4 L A5 L A6 L A7 COM A8 NC A9 L

Page 124

Appendix B

Specifications

Triac Output Unit C200H-OA122-E Max. Switching Capacity

1.2 A 120 VAC, 50/60 Hz (4 A/Unit)

Max. Inrush Current

15 A (pulse width: 100 ms) 30 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max.

Min. Switching Capacity Leakage Current Residual Voltage ON Response Time

1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to 50 mA) 1 ms max.

OFF Response Time

1/2 of load frequency+1 ms or less.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

180 mA 5 VDC max.

Fuse Rating

5 A 125 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

300 g max.

Dimensions

E-shape

Circuit Configuration OUT L OUT

Output indicator

L

Internal Circuit

Fuse

COM 120 VAC max.

Fuse blowout detection circuit

F indicator Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)

Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal Connections

120 VAC max. (1.2 A max. 4 A/Unit)

L

0

A0

L

1

A1

L

2

A2

L

3

A3

L

4

A4

L

5

A5

L

6

A6

L

7

A7

COM

A8

NC

A9

117

Page 125

Appendix B

Specifications

Triac Output Unit C200H-OA222V Max. Switching Capacity

0.3 A 250 VAC, 50/60 Hz (2 A/Unit)

Min. Switching Capacity Leakage Current

10 mA (resistive load)/40 mA (inductive load) 10 VAC 3 mA (100 VAC) max./6 mA (200 VAC) max.

Residual Voltage

1.2 V max.

ON Response Time

1/2 of load frequency or less.

OFF Response Time

1/2 of load frequency or less.

No. of Circuits

1 (12 points/common)

Internal Current Consumption

200 mA 5 VDC max.

Fuse Rating

3 A 250 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

400 g max.

Dimensions

B-shape

Circuit Configuration OUT L Output indicator

OUT L

Internal Circuit

Fuse

COM 250 VAC max.

Fuse: 3 A 250 V (5.2-dia.x20) MQ4 (SOC)

Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections

1 L

3 L L L

5 7 9

L

11 L

250 VAC max. (0.3 A max., 2 A/Unit)

A0 A1 A2 A3 A4 A5

NC

A6

NC

A7

COM

118

B0

A8

0

B1

2

B2

4

B3

6

B4

8

B5

10

B6

NC

B7

NC

B8

NC

B9

NC

L L L L L L

Page 126

Appendix B

Specifications

Triac Output Unit C200H-OA223 Max. Switching Capacity

1.2 A 250 VAC, 50/60 Hz (4 A/Unit)

Max. Inrush Current

15 A (pulse width: 100 ms) 30 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max./3 mA (240 VAC) max.

Min. Switching Capacity Leakage Current Residual Voltage ON Response Time

1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to 50 mA) 1 ms max.

OFF Response Time

1/2 of load frequency+1 ms or less.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

180 mA 5 VDC max.

Fuse Rating

5 A 250 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

300 g max.

Dimensions

E-shape

Circuit Configuration OUT L OUT

Output indicator

L

Internal Circuit

Fuse

COM 250 VAC max.

Fuse blowout detection circuit

F indicator Fuse: 5 A 250 V (5.2-dia.x20) HT (SOC)

Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal Connections

250 VAC max. (1.2 A max. 4 A/Unit)

L

0

A0

L

1

A1

L

2

A2

L

3

A3

L

4

A4

L

5

A5

L

6

A6

L

7

A7

COM

A8

NC

A9

119

Page 127

Appendix B

Specifications

Triac Output Unit C200H-OA224 Max. Switching Capacity

0.5 A 250 VAC, 50/60 Hz (2 A/Unit)

Max. Inrush current

10 A (pulse width: 100ms) 20 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max./3 mA (240 VAC) max.

Min. Switching Capacity Leakage Current Residual Voltage ON Response Time

1.5 VAC max. (50 to 500 mA)/5 VAC max. (10 to 50 mA) 1 ms max.

OFF Response Time

1/2 of load frequency + 1 ms or less.

No. of Circuits

1 (12 points/common)

Internal Current Consumption

270 mA 5 VDC max.

Fuse Rating

3.15 A 250 V (5.2-dia.x20)

Power for External Supply

N/A

Weight

300 g max.

Dimensions

B-shape

Circuit Configuration OUT L OUT

Output indicator

L

Internal Circuit

Fuse

COM 250 VAC max.

Fuse: 3.15 A 250 V (5.2-dia.x20) MT4 (SOC)

Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections

1 L

3 L L L

5 7 9

L

11 L

250 VAC max. (0.5 A max., 2 A/Unit)

A0 A1 A2 A3 A4 A5

NC

A6

NC

A7

COM

120

B0

A8

0

B1

2

B2

4

B3

6

B4

8

B5

10

B6

NC

B7

NC

B8

NC

B9

NC

L L L L L L

Page 128

Appendix B

Specifications

Contact Output Unit C200H-OC221 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC

Relay

G6B-1174P-FD-US (24 VDC) w/socket

Service Life of Relay

Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

10 ms max.

OFF Response Time

10 ms max.

No. of Circuits

1 (8 points/common)

Internal Current Consumption Weight

10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 250 g max.

Dimensions

A-shape

Circuit Configuration OUT L Output indicator OUT L Internal Circuit COM 250 VAC 24 VDC max.

Terminal Connections 0 L

A0 1 A1

L

2 A2

L

3 A3

L

4 A4

L

5 A5

L

6 A6

L

7 A7

L COM

NC

A8 A9

250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)

121

Page 129

Appendix B

Specifications

Contact Output Unit C200H-OC222 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC

Relay

G6B-1174P-FD-US (24 VDC) w/socket

Service Life of Relay

Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

10 ms max.

OFF Response Time

10 ms max.

No. of Circuits

Weight

1 (12 points/common) 8 points max. can be ON simultaneously. 10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 300 g max.

Dimensions

B-shape

Internal Current Consumption

Circuit Configuration OUT L

Output indicator OUT

L Internal Circuit

COM 250 VAC 24 VDC max.

Terminal Connections

1 L L L

3 5 7

L

9 L

11 L

B0 A0 A1 A2 A3 A4 A5

NC

A6

NC

A7

COM

A8

0

L

B1

2

L

B2

4

L

B3

6

B4

8

B5 10 B6

NC

B7

NC

B8

NC

B9

NC

L L L

250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)

122

Page 130

Appendix B

Specifications

Contact Output Unit C200H-OC223 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (10 A/Unit) 10 mA 5 VDC

Relay

G6B-1174-P-FD-US (24 VDC) w/socket

Service Life of Relay

Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

10 ms max.

OFF Response Time

10 ms max.

No. of Circuits

5 independent contacts

Internal Current Consumption Weight

10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 250 g max.

Dimensions

A-shape

Circuit Configuration

Output indicator OUT L Internal Circuit

OUTc 250 VAC 24 VDC max.

Terminal Connections L

0 c0

L

1 c1 2

L

250VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (10 A/Unit)

c2 L

3 c3 4

A0 A1 A2 A3 A4 A5 A6 A7 A8

L c4

A9

123