Page 121
Appendix B
Specifications
AC/DC Input Unit C200H-IM211 Rated Input Voltage
12 to 24 VDC
Operating Input Voltage
10.2 to 26.4 VDC
Input Impedance
2 kW
Input Current
10 mA typical (at 24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
15 ms max. (at 24 VDC, 25°C)
OFF Response Time
15 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
200 g max.
Dimensions
A-shape
Circuit Configuration IN
IN
COM
2 kW 0.01 mF
1.8 kW
Internal Circuit
12 to 24 VAC/DC Input indicator
Terminal Connections 0 1 2 3 12 to 24 VAC/DC
4 5 6 7 COM
NC
114
A0 A1 A2 A3 A4 A5 A6 A7 A8 A9
Page 122
Appendix B
Specifications
AC/DC Input Unit C200H-IM212 Rated Input Voltage
24 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Input Impedance
3 kW
Input Current
7 mA typical (at 24 VDC)
ON Voltage
14.4 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
15 ms max. (at 24 VDC, 25°C)
OFF Response Time
15 ms max. (at 24 VDC, 25°C)
No. of Circuits
1 (16 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
B-shape
Circuit Configuration IN
IN
COM
3 kW 0.01 mF
1.8 kW
Internal Circuit
24 VAC/DC Input indicator
Terminal Connections
1 3 5 7
24 VAC/DC
9 11 13 15 COM
B0 A0 A1 A2 A3 A4 A5 A6 A7 A8
0
B1
2
B2
4
B3
6
B4
8
B5 10 B6 12 B7 14 B8
NC
B9
NC
115
Page 123
Appendix B
Specifications
Triac Output Unit C200H-OA121-E Max. switching capacity
1 A 120 VAC, 50/60 Hz (4 A/Unit)
Min. switching capacity Leakage Current
10 mA (resistive load)/40 mA (inductive load) 10 VAC 3 mA (100 VAC) max.
Residual Voltage
1.2 V max.
ON Response Time
1 ms max.
OFF Response Time
1/2 of load frequency or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
140 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration OUT Output LED indicator
OUT
Internal circuit
Fuse
L
L
COM 120 VAC max.
Fuse blowout detection circuit F indicator Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
Note When the fuse blows, F indicator lights and bit 08 turns ON. Bits 08 through15 cannot be used as IR bits. Terminal Connections
L
120 VAC max. (1 A max. 4 A/Unit)
116
0 1 2 3 4 5 6 7
A0 A1 L A2 L A3 L A4 L A5 L A6 L A7 COM A8 NC A9 L
Page 124
Appendix B
Specifications
Triac Output Unit C200H-OA122-E Max. Switching Capacity
1.2 A 120 VAC, 50/60 Hz (4 A/Unit)
Max. Inrush Current
15 A (pulse width: 100 ms) 30 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max.
Min. Switching Capacity Leakage Current Residual Voltage ON Response Time
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to 50 mA) 1 ms max.
OFF Response Time
1/2 of load frequency+1 ms or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
5 A 125 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
E-shape
Circuit Configuration OUT L OUT
Output indicator
L
Internal Circuit
Fuse
COM 120 VAC max.
Fuse blowout detection circuit
F indicator Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal Connections
120 VAC max. (1.2 A max. 4 A/Unit)
L
0
A0
L
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
COM
A8
NC
A9
117
Page 125
Appendix B
Specifications
Triac Output Unit C200H-OA222V Max. Switching Capacity
0.3 A 250 VAC, 50/60 Hz (2 A/Unit)
Min. Switching Capacity Leakage Current
10 mA (resistive load)/40 mA (inductive load) 10 VAC 3 mA (100 VAC) max./6 mA (200 VAC) max.
Residual Voltage
1.2 V max.
ON Response Time
1/2 of load frequency or less.
OFF Response Time
1/2 of load frequency or less.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
200 mA 5 VDC max.
Fuse Rating
3 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
400 g max.
Dimensions
B-shape
Circuit Configuration OUT L Output indicator
OUT L
Internal Circuit
Fuse
COM 250 VAC max.
Fuse: 3 A 250 V (5.2-dia.x20) MQ4 (SOC)
Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections
1 L
3 L L L
5 7 9
L
11 L
250 VAC max. (0.3 A max., 2 A/Unit)
A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM
118
B0
A8
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
NC
B7
NC
B8
NC
B9
NC
L L L L L L
Page 126
Appendix B
Specifications
Triac Output Unit C200H-OA223 Max. Switching Capacity
1.2 A 250 VAC, 50/60 Hz (4 A/Unit)
Max. Inrush Current
15 A (pulse width: 100 ms) 30 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max./3 mA (240 VAC) max.
Min. Switching Capacity Leakage Current Residual Voltage ON Response Time
1.5 VAC max. (50 to 1,200 mA)/ 5 VAC max. (10 to 50 mA) 1 ms max.
OFF Response Time
1/2 of load frequency+1 ms or less.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
180 mA 5 VDC max.
Fuse Rating
5 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
E-shape
Circuit Configuration OUT L OUT
Output indicator
L
Internal Circuit
Fuse
COM 250 VAC max.
Fuse blowout detection circuit
F indicator Fuse: 5 A 250 V (5.2-dia.x20) HT (SOC)
Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal Connections
250 VAC max. (1.2 A max. 4 A/Unit)
L
0
A0
L
1
A1
L
2
A2
L
3
A3
L
4
A4
L
5
A5
L
6
A6
L
7
A7
COM
A8
NC
A9
119
Page 127
Appendix B
Specifications
Triac Output Unit C200H-OA224 Max. Switching Capacity
0.5 A 250 VAC, 50/60 Hz (2 A/Unit)
Max. Inrush current
10 A (pulse width: 100ms) 20 A (pulse width: 10 ms) 100 mA 10 VAC/50 mA 24 VAC/10 mA 100 VAC min. 1.5 mA (120 VAC) max./3 mA (240 VAC) max.
Min. Switching Capacity Leakage Current Residual Voltage ON Response Time
1.5 VAC max. (50 to 500 mA)/5 VAC max. (10 to 50 mA) 1 ms max.
OFF Response Time
1/2 of load frequency + 1 ms or less.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
270 mA 5 VDC max.
Fuse Rating
3.15 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
300 g max.
Dimensions
B-shape
Circuit Configuration OUT L OUT
Output indicator
L
Internal Circuit
Fuse
COM 250 VAC max.
Fuse: 3.15 A 250 V (5.2-dia.x20) MT4 (SOC)
Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections
1 L
3 L L L
5 7 9
L
11 L
250 VAC max. (0.5 A max., 2 A/Unit)
A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM
120
B0
A8
0
B1
2
B2
4
B3
6
B4
8
B5
10
B6
NC
B7
NC
B8
NC
B9
NC
L L L L L L
Page 128
Appendix B
Specifications
Contact Output Unit C200H-OC221 Max. Switching Capacity Min. Switching Capacity
2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC
Relay
G6B-1174P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption Weight
10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 250 g max.
Dimensions
A-shape
Circuit Configuration OUT L Output indicator OUT L Internal Circuit COM 250 VAC 24 VDC max.
Terminal Connections 0 L
A0 1 A1
L
2 A2
L
3 A3
L
4 A4
L
5 A5
L
6 A6
L
7 A7
L COM
NC
A8 A9
250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)
121
Page 129
Appendix B
Specifications
Contact Output Unit C200H-OC222 Max. Switching Capacity Min. Switching Capacity
2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC
Relay
G6B-1174P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
Weight
1 (12 points/common) 8 points max. can be ON simultaneously. 10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 300 g max.
Dimensions
B-shape
Internal Current Consumption
Circuit Configuration OUT L
Output indicator OUT
L Internal Circuit
COM 250 VAC 24 VDC max.
Terminal Connections
1 L L L
3 5 7
L
9 L
11 L
B0 A0 A1 A2 A3 A4 A5
NC
A6
NC
A7
COM
A8
0
L
B1
2
L
B2
4
L
B3
6
B4
8
B5 10 B6
NC
B7
NC
B8
NC
B9
NC
L L L
250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)
122
Page 130
Appendix B
Specifications
Contact Output Unit C200H-OC223 Max. Switching Capacity Min. Switching Capacity
2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (10 A/Unit) 10 mA 5 VDC
Relay
G6B-1174-P-FD-US (24 VDC) w/socket
Service Life of Relay
Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations
ON Response Time
10 ms max.
OFF Response Time
10 ms max.
No. of Circuits
5 independent contacts
Internal Current Consumption Weight
10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 250 g max.
Dimensions
A-shape
Circuit Configuration
Output indicator OUT L Internal Circuit
OUTc 250 VAC 24 VDC max.
Terminal Connections L
0 c0
L
1 c1 2
L
250VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (10 A/Unit)
c2 L
3 c3 4
A0 A1 A2 A3 A4 A5 A6 A7 A8
L c4
A9
123