SYSMAC C200HS Programmable Controllers Installation Guide, pages 131 to 140

Pages 131 to 140 of 221

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 131

Appendix B

Specifications

Contact Output Unit C200H-OC224 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (16 A/Unit) 10 mA 5 VDC

Relay

G6B-1174-P-FD-US (24 VDC) w/socket

Service Life of Relay

Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

10 ms max.

OFF Response Time

10 ms max.

No. of Circuits

8 independent contacts

Internal Current Consumption Weight

10 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 300 g max.

Dimensions

B-shape

Circuit Configuration

Output indicator OUT L Internal Circuit OUTc 250 VAC 24 VDC max.

Terminal Connections c0 c1

B0 A0 A1 c2

A2 c3

250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (16 A/Unit)

A3 c4

A4 c5

A5 c6

A6 c7

A7 NC

124

A8

B1 B2 B3 B4 B5 B6 B7

0 1 2 3 4 5 6 7

B8 NC B9 NC

L L L L L L L L

Page 132

Appendix B

Specifications

Contact Output Unit C200H-OC225 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC

Relay

G6B-1174P-FD-US (24 VDC) w/socket

Service Life of Relay

Electrical: 500,000 operations (resistive load)/ 100,000 operations (inductive load) Mechanical: 50,000,000 operations

ON Response Time

10 ms max.

OFF Response Time

10 ms max.

No. of Circuits

Weight

1 (16 points/common) 8 points max. can be ON simultaneously. 50 mA 5 VDC max. 75 mA 26 VDC (8 points ON simultaneously.) 400 g max.

Dimensions

B-shape

Internal Current Consumption

Circuit Configuration OUT L Output indicator OUT L Internal Circuit

COM 250 VAC 24 VDC max.

Terminal Connections 0 B0 A0 2 3 A1 B1 L 4 B2 5 A2 L 6 B3 7 A3 L 8 B4 9 A4 L 10 11 A5 B5 L B6 12 13 A6 L 14 15 A7 B7 L B8 NC A8 COM B9 NC L

1

L L L L L L L L

250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)

Note 1. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane. 2. This Unit might overheat if more than 8 output points are turned ON simultaneously.

125

Page 133

Appendix B

Specifications

Contact Output Unit C200H-OC222V Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC

Relay

G6R-1 (24 VDC) w/socket

Service Life of Relay ON Response Time

Electrical: 300,000 operations Mechanical: 10,000,000 operations 15 ms max.

OFF Response Time

15 ms max.

No. of Circuits

Weight

1 (12 points/common) 8 points max. can be ON simultaneously. 8 mA 5 VDC max. 90 mA 26 VDC (8 points ON simultaneously.) 400 g max.

Dimensions

B-shape

Internal Current Consumption

Circuit Configuration OUT L

Output indicator OUT

L Internal Circuit

COM 250 VAC 24 VDC max.

Terminal Connections

1 L L L

3 5 7

L

9 L

11 L

B0 A0 A1 A2 A3 A4 A5

NC

A6

NC

A7

COM

A8

0

L

B1

2

L

B2

4

L

B3

6

B4

8

B5 10 B6

L L L

NC

B7

NC

B8

NC

B9

NC

250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)

126

Page 134

Appendix B

Specifications

Contact Output Unit C200H-OC226 Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (8 A/Unit) 10 mA 5 VDC

Relay

G6R-1 (24 VDC) w/socket

Service Life of Relay ON Response Time

Electrical: 300,000 operations Mechanical: 10,000,000 operations 15 ms max.

OFF Response Time

15 ms max.

No. of Circuits

Weight

1 (16 points/common) 8 points max. can be ON simultaneously. 30 mA 5 VDC max. 90 mA 26 VDC (8 points ON simultaneously.) 500 g max.

Dimensions

Extended B-shape

Internal Current Consumption

Circuit Configuration OUT L Output indicator OUT L Internal Circuit

COM 250 VAC 24 VDC max.

Terminal Connections 0 B0 A0 2 3 A1 B1 L 4 5 A2 B2 L 6 B3 7 A3 L 8 B4 9 A4 L 10 B5 11 A5 L B6 12 13 A6 L 14 15 A7 B7 L B8 NC A8 COM B9 NC L

1

L L L L L L L L

250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (8 A/Unit)

127

Page 135

Appendix B

Specifications

Contact Output Unit C200H-OC224V Max. Switching Capacity Min. Switching Capacity

2 A 250 VAC (cosf = 1), 2 A 250 VAC (cosf = 0.4), 2 A 24 VDC (16 A/Unit) 10 mA 5 VDC

Relay

G6R-1 (24 VDC) w/socket

Service Life of Relay ON Response Time

Electrical: 300,000 operations Mechanical: 10,000,000 operations 15 ms max.

OFF Response Time

15 ms max.

No. of Circuits

8 independent contacts

Internal Current Consumption Weight

10 mA 5 VDC max. 90 mA 26 VDC (8 points ON simultaneously.) 350 g max.

Dimensions

B-shape

Circuit Configuration

Output indicator OUT L Internal Circuit OUTc 250 VAC 24 VDC max.

Terminal Connections c0 c1

B0 A0 A1 c2

A2 c3

250 VAC 24 VDC max. (inductive load: 2 A resistive load: 2 A) (16 A/Unit)

A3 c4

A4 c5

A5 c6

A6 c7

A7 NC

128

A8

B1 B2 B3 B4 B5 B6 B7

0 1 2 3 4 5 6 7

B8 NC B9 NC

L L L L L L L L

Page 136

Appendix B

Specifications

Life Expectancy of Contact Output Unit The C200H-OC221/222/223/224/225 Contact Output Unit uses OMRON’s G6B-1174P-FD-US Relay. The life of the G6B-1174P-FD-US Relay varies with the contact current and ambient temperature. Refer to the following graphs to calculate this value.

30 VDC, L/R = 40 ms OMRON’s H3BA (electromagnetic valve) Timer (200 VAC) OMRON’s MA415A Contactor (200 VAC)

250 VAC, cosφ = 0.4 30 VDC, L/R = 7 ms (HK, MM, and MY Hinge-type Relay) 250 VAC, cosφ = 130 VDC, L/R = 0

OMRON’s MY4 Relay (200 VAC) Electromagnetic valve (250 VAC, cosφ = 0.08 to 0.1)

Contact current (normal current) (A)

Ambient Temperature vs. Life Expectancy Conditions Switching frequency: 1,800 times/hour max.

Life expectancy (x 10 4 operations)

Life expectancy (x 10 4 operations)

Contact Current vs. Life Expectancy Conditions Switching frequency: 1,800 times/hour max. Ambient temperature: 23°C

2 A at 250 VAC, resistive load 2 A at 30 VDC, resistive load

1 A at 250 VAC, resistive load 1 A at 30 VDC, resistive load

1 A at 250 VAC, inductive load (cosφ = 0.4) 1 A at 30 VDC, inductive load (L/R = 7 ms)

2 A at 250 VAC, inductive load (cosφ = 0.4) 2 A at 30 VDC, inductive load (L/R = 7 ms)

Ambient temperature (°C)

Note 1. If the Contact Output Unit is panel-mounted, the temperature inside the panel represents the ambient temperature. 2. The life of the Relay at an ambient temperature of 55°C is one-fifth the life of the Relay at room temperature (0° to 40°C). Inductive Load The life of the Relay varies with the load inductance. If any inductive load is connected to the Contact Output Unit, use an arc killer with the Contact Output Unit using an inductive load. Be sure to connect a diode in parallel with every DC inductive load that is connected to the Contact Output Unit. Contact Protection Circuit Arc killers are used with the Contact Output Unit in order to prolong the life of each Relay mounted to the Contact Output Unit, prevent noise, and reduce the generation of carbide and nitrate deposits. Note Arc killers used with the Contact Output Unit can delay the resetting time required by each Relay mounted to the Contact Output Unit.

129

Page 137

Appendix B

Specifications Arc killer circuit examples are listed in the following table. Circuit

Current

Power supply

Power supply

Power supply

Inductive load

Varistor method

The capacitance of the capacitor must be 1 to 0.5 µF per contact current of 1 A and resistance of the resistor must be 0.5 to 1 Ω per contact voltage of 1 V. These values, however, vary with the load and the characteristics of the relay. Decide these values from experiments, and take into consideration that the capacitance suppresses spark discharge when the contacts are separated and the resistance limits the current that flows into the load when the circuit is closed again. The dielectric strength of the capacitor must be 200 to 300 V. If the circuit is an AC circuit, use a capacitor with no polarity. The reversed dielectric strength value of the diode must be at least 10 times as large as the circuit voltage value. The forward current of the diode must be the same as or larger than the load current. The reversed dielectric strength value of the diode may be two to three times larger than the supply voltage if the arc killer is applied to electronic circuits with low circuit voltages.

AC

DC Yes

If the load is a relay or solenoid, there is a time lag between the moment the circuit is opened and the moment the load is reset. If the supply voltage is 24 or 48 V, insert the arc killer in parallel with the load. If the supply voltage is 100 to 200 V, insert the arc killer between the contacts.

No

Yes

The diode connected in parallel with the load changes energy accumulated by the coil into a current, which then flows into the coil so that the current will be converted into Joule heat by the resistance of the inductive load. This time lag, between the moment the circuit is opened and the moment the load is reset, caused by this method is longer than that caused by the CR method.

Yes

Yes

The varistor method prevents the imposition of high voltage between the contacts by using the constant voltage characteristic of the varistor. There is time lag between the moment the circuit is opened and the moment the load is reset. If the supply voltage is 24 or 48 V, insert the varistor in parallel with the load. If the supply voltage is 100 to 200 V, insert the varistor between the contacts.

Inductive load

Diode method

Required element

Yes

Inductive load

CR method

Characteristic

---

Power supply

130

Inductive load

Note Do not connect a capacitor as an arc killer in parallel with an inductive load as shown in the following diagram. This arc killer is very effective for preventing spark discharge at the moment when the circuit is opened. However when the contacts are closed, the contacts may be welded due to the current charged in the capacitor. DC inductive loads can be more difficult to switch than resistive loads. If appropriate arc killers are used, however, DC inductive loads will be as easy to switch as resistive loads.

Page 138

Appendix B

Specifications

Transistor Output Unit C200H-OD211 Max. Switching Capacity

0.3 A 24 VDC +10%/–15% (2 A/Unit)

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

1.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

1 (12 points/common)

Internal Current Consumption

160 mA 5 VDC max.

Fuse Rating

5 A 125 V (5.2-dia.x20)

Power for External Supply

25 mA 24 VDC +10%/–15% min.

Weight

300 g max.

Dimensions

B-shape

Circuit Configuration OUT L +V Output indicator OUT L Internal Circuit

24 VDC Fuse

COM

Fuse: GGS (Nagasawa) 5 A 125 V 5.2-dia 20

Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections

L L L

24 VDC (0.3 A max., 2 A/Unit)

L L L

1 3 5 7 9 11

A0 A1 A2 A3 A4 A5

NC

A6

NC

A7

COM (OV)

A8

B0

0

L

B1

2

L

B2

4

L

B3

6

B4

8

B5 10

L L L

B6

NC

B7

NC

B8

NC + 24 VDC

B9

Note Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF.

131

Page 139

Appendix B

Specifications

Transistor Output Unit C200H-OD212 Max. Switching Capacity

0.3 A 24 VDC +10%/–15% (4.8 A/Unit)

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

1.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

1 (16 points/common)

Internal Current Consumption

180 mA 5 VDC max.

Fuse Rating

8 A 125 V (5.2-dia.x20)

Power for External Supply

35 mA 24 VDC +10%/–15% min.

Weight

350 g max.

Dimensions

B-shape

Circuit Configuration OUT L +V Output indicator OUT L Internal Circuit

24 VDC Fuse

COM

Fuse: UL-TSC-8A-N1 (Nagasawa) 8 A 125 V 5.2-dia 20

Note 1. No blown fuse detector circuit is provided. 2. Check the fuse when there is no output. Terminal Connections

L L L

24 VDC (0.3 A max )

L

1 3 5 7 9

A0 A1 A2 A3 A4

B0

0

L

B1

2

L

B2

4

L

B3

6

B4

8

L L

B5 10 L 11 A5 L B6 12 L 13 A6 L B7 14 L 15 A7 L B8 NC A8 + 24 VDC COM (OV) B9 L

Note 1. Be sure to supply power to B9; otherwise current will leak through the load while the output is OFF. 2. This Unit must be mounted to a C200H-BCjj1-V1/V2 Backplane.

132

Page 140

Appendix B

Specifications

Transistor Output Unit C200H-OD213 Max. Switching Capacity

2.1 A 24 VDC +10%/–15% (5.2 A/Unit) NPN output

Min. Switching Capacity

None

Leakage Current

0.1 mA max.

Residual Voltage

1.4 V max.

ON Response Time

0.2 ms max.

OFF Response Time

0.3 ms max.

No. of Circuits

1 (8 points/common)

Internal Current Consumption

140 mA 5 VDC max.

Fuse Rating

8 A 125 V (5.2-dia.x20)

Power for External Supply

30 mA 24 VDC +10%/–15% min.

Weight

250 g max.

Dimensions

A-shape

Circuit Configuration OUT L +V Output indicator

Internal Circuit

OUT L 24 VDC Fuse Fuse blowout detection circuit

COM

Fuse: UL-TSC-8A-N1 (Nagasawa) 8 A 125 V 5.2-dia 20

F indicator

Note When the fuse blows, the F indicator lights and bit 08 turns ON. Bits 08 through 15 cannot be used as IR bits. Terminal Connections L L L

24 VDC (2.1 A max., 5.2 A/Unit)

L L L L L

0 1 2 3 4 5 6 7

A0 A1 A2 A3 A4 A5 A6 A7

COM (OV)

A8

24 VDC

A9

Note Be sure to supply power to A9; otherwise current will leak through the load while the output is OFF.

133