Page 91

Section 6-6

Input Units

6-6

Input Units

Error Indicator lights are turned off, and no inputs turn ON.

Indicator lights are turned ON, but no inputs turn ON. All inputs remain ON, and will not turn OFF. Inputs do not turn ON for particular Relay numbers.

Inputs do not turn OFF for particular Relay numbers. Inputs are turning ON and OFF irregularly.

Malfunctioning Relays are in groups of eight.

Operation is normal, but the input indicator does not light.

82

Probable cause

Possible correction

No external input power supply is provided. The external input voltage is low. Terminal screws are loose. Terminal block connectors are making poor contact. The input circuit is defective.

Provide a power supply.

The input circuit is defective.

Replace the Unit.

An input device is defective. Input wiring is disconnected. Terminal screws are loose. Terminal block connectors are making poor contact. The ON time for external inputs is too short. The input circuit is defective. An input bit address is used for an OUT instruction in the program. The input circuit is defective. An input bit address is used for an OUT instruction in the program. The external input voltage is low. There is malfunctioning due to noise.

Replace the input device. Check the input wiring. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Adjust the input device.

Terminal screws are loose. Terminal block connectors are making poor contact. Common terminal screws are loose. Terminal block connectors are making poor contact. The CPU is defective. The LED is defective.

Supply the rated voltage. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Replace the Unit.

Replace the Unit. Correct the program. Replace the Unit. Correct the program. Supply the rated voltage. Apply noise countermeasures such as installing a surge suppressor, installing an isolation transformer, and using shielded cables. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Replace the CPU. Replace the Unit.

Page 92

Section 6-7

Output Units

6-7

Output Units

Error No outputs turn ON.

Outputs all fail to turn OFF. Indicators do not light, and the outputs for particular Relay numbers do not turn ON.

Indicators light, but the outputs for particular Relay numbers do not turn ON.

Indicator lights are off, but the outputs for particular Relay numbers do not turn OFF. Indicators light, and the outputs for particular Relay numbers do not turn OFF. Outputs are turning ON and OFF irregularly.

Malfunctioning Relays are in groups of eight.

Operation is normal, but the output indicator does not light.

Probable cause

Possible correction

A load power supply is not provided. The load power supply voltage is low. Terminal screws are loose. Terminal block connectors are making poor contact. A fuse is blown. I/O bus connectors are making poor contact. The output circuit is defective. The output circuit is defective.

Provide the power supply. Provide the rated voltage. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Replace the fuse. Replace the Unit.

The output ON time is too short.

Correct the program.

The output circuit is defective.

Replace the Unit.

The program’s OUT instruction bit addresses overlap. An output device is defective. Output wiring is disconnected. Terminal screws are loose. Terminal block connectors are making poor contact. Output Relays are defective. The output circuit is defective. Output Relays are defective. There is faulty restoration due to leakage current or residual current. The output circuit is defective. The program’s OUT instruction bit addresses overlap. The load power supply voltage is low.

Correct the program.

The program’s OUT instruction bit addresses overlap. There is malfunctioning due to noise.

Correct the program.

Terminal screws are loose. Terminal block connectors are making poor contact. Common terminal screws are loose. Terminal block connectors are making poor contact. A fuse is blown. The CPU is defective. The LED is defective.

Replace the Unit. Replace the Unit.

Replace the output device. Check the output wiring. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Replace the Relays. Replace the Unit. Replace the Relays. Replace the external load or add a dummy resistor. Replace the Unit. Correct the program. Supply the rated voltage.

Apply noise countermeasures such as installing a surge suppressor, installing an isolation transformer, and using shielded cables. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Tighten the terminal screws. Securely lock the connectors, or replace them if necessary. Replace the fuse. Replace the CPU. Replace the Unit.

83

Page 93

SECTION 7 Inspection and Maintenance Certain consumable items in a PC (such as fuses, relays, and batteries) need occasional replacement. This section explains how to replace these items. Always keep spare items on hand so that they can be used as immediate replacements when needed. 7-1 7-2 7-3 7-4

CPU and Power Supply Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Unit Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Unit Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Batteries . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

86 86 87 90

85

Page 94

Section 7-2

Output Unit Fuses

7-1

CPU and Power Supply Fuses

Turn counterclockwise to remove, clockwise to attach

Standard screwdriver

To replace a fuse, follow the steps below. 1, 2, 3...

1. Turn OFF the power to the PC. 2. Remove the fuse holder by turning it approximately 50° counterclockwise with a standard screwdriver. 3. Remove the fuse from the holder. 4. Insert a new fuse. 5. Reattach the fuse holder by turning it approximately 50° clockwise with a standard screwdriver.

7-2

Output Unit Fuses To replace a fuse, follow the steps below. Use only UL/CSA certified replacement fuses. Fuse Specifications (5.2-dia.x20) Model

1, 2, 3...

C200H-OD411

F indicator (fuse blowout detection circuit) Yes

Rating

C200H-OD211

No

C200H-OD212

No

C200H-OD213

Yes

C200H-OA121-E

Yes

C200H-OA122-E

Yes

C200H-OA221

Yes

5 A 250 V

C200H-OA222V

No

3 A 250 V

C200H-OA223

Yes

5 A 250 V

C200H-OA224

No

3.15 A 250 V

5 A 125 V 8 A 125 V 5 A 125 V

1. Turn OFF the power to the PC. 2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block.

86

Page 95

Section 7-3

Output Unit Relays

3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.

4. Using a Phillips screwdriver, remove the screw from the top of the Unit. 5. Using a flat-blade screwdriver, detach the case from the Unit.

6. Pull out the printed circuit board. 7. Insert a new fuse. A spare fuse is provided inside the rear of the case when the Unit is delivered. 8. Reassemble in reverse order of assembly. Note

7-3

1. Use UL or CSA approved fuses if the UL or CSA standards must be satisfied. For further details, consult the fuse manufacturer. 2. Fuses in High-density I/O Units cannot be replaced by the user. Refer to your OMRON dealer for service.

Output Unit Relays The following Output Units provide relay sockets that allow the Relays to be replaced if they should go bad. Use the Relay listed in the table. Unit C200H-OC221

Relay G6B-1174P-FD-US, 24 VDC

C200H-OC222 C200H-OC223 C200H-OC224 C200H-OC225 C200H-OC222V

G6R-1, 24 VDC

C200H-OC224V C200H-OC226

87

Page 96

Section 7-3

Output Unit Relays To replace a Relay, follow the steps below: 1, 2, 3...

1. Turn OFF the power to the PC. 2. Detach the terminal block by unlocking the lock levers at the top and bottom of the terminal block. 3. While pushing down the lock lever on the Backplane with a screwdriver as shown below, remove the Output Unit.

4. Using a Phillips screwdriver, remove the screw from the top of the Unit. 5. Using a flat-blade screwdriver, detach the case from the Unit.

6. Pull out the printed circuit board. The Relays are placed on the PC boards of individual Units as shown in the figures below. OC221/OC224

0 1 2 3 4 5 6 7

88

Page 97

Section 7-3

Output Unit Relays OC222

0 1 2 3 4 6 8 10

5 7 9 11

OC223

0 1 2 3 4

OC225

1 0 3 2 5 4 7 6 9 8 11 10 13 12 15 14

OC222V 0 2 4

1 3 5 7 8 9 10 11

6

OC224V

0 1 2 3 4 5 6 7

89

Page 98

Section 7-4

Batteries OC226

1 3 5 7 9 11 13 15

0 2 4 6 8 10 12 14

7. A Relay puller is provided inside the rear of the case when the Unit is delivered. Use the Relay puller to pull out the Relay as shown below. Insert a new Relay. Relays for the C200H-OC222V/OC224V/OC226V can be replaced without using the Relay puller.

Relay puller Using the Relay puller, pull the Relay up and out of the socket.

Printed circuit board

8. Reassemble in reverse order of assembly. ! Caution

7-4

Check the pin arrangement before inserting a new Relay into the socket. Pins can only be inserted one way, so do not try to force them if they do not go in easily. Applying too much force can bend the pins and render them unusable.

Batteries !

DANGER

Batteries can burn, explode, or leak. Absolutely do not short-circuit across the terminals, attempt to recharge batteries, or take them apart, heat them, or expose them to fire. When the battery is nearly discharged, the ALARM indicator blinks and the message “BATT FAIL” appears on the Programming Console. When this occurs, replace the battery within one week to avoid loss of data. The normal battery service life is five years at 25°C. The service life will be shorten if used at temperatures higher than that. The Battery Fail Flag is allocated to 25308 for the C200HS. The battery comes together with its connector as a set. To replace the Battery Set (C200H-BAT09), follow the steps below. The entire replacement must be completed within five minutes to ensure that the data will not be lost.

1, 2, 3...

90

1. Turn OFF the power to the PC. (If the power was not already ON, turn the power ON for at least one minute before turning the power OFF.)

Page 99

Section 7-4

Batteries

2. Remove the cover from the battery compartment of the CPU Unit. 3. Remove the old Battery Set. 4. Install the new Battery Set as shown in the following diagram.

Connector

CPU01-E/03-E/01-EC Battery

5. Replace the cover of the battery compartment. 6. Press CLR, FUN, MONTR, MONTR or just turn the power to the PC OFF and then ON again to clear the error message on the Programming Console.

91

Page 100

Appendix A Standard Models C200HS Racks Name Backplane (same for all Racks)

CPU Rack

CPU

Specifications 10 slots 8 slots 5 slots 3 slots

C200H-BC101-V2 C200H-BC081-V2 C200H-BC051-V2 C200H-BC031-V2

100 to 120/200 to 240 VAC w/built-in --power supply Conforms to EC directives (see note) RS-232C port

C200HS-CPU01-E

24 VDC w/built-in power supply

Memory Cassette

Expansion I/O Racks

I/O Power Supply Unit

I/O Connecting Cable (max. total length: 12 m)

Slave Racks

Remote I/O Slave Unit

Model number

C200HS-CPU01-EC C200HS-CPU21-E

RS-232C port and conforms to EC directives

C200HS-CPU21-EC

RS-232C port and SYSMAC NET/ SYSMAC LINK supported

C200HS-CPU31-E

Conforms to EC directives (see note) RS-232C port RS-232C port and SYSMAC NET/ SYSMAC LINK supported

C200HS-CPU03-E C200HS-CPU23-E C200HS-CPU33-E

EPROM Chip; 27256; 150 ns

ROM-JD-B

EPROM Chip; 27512; 150 ns

ROM-KD-B

EEPROM; 16K words

C200HS-ME16K

EPROM; 16K words

C200HS-MP16K

100 to 120/200 to 240 VAC (switchable) Conforms to EC directives 24 VDC Conforms to EC directives (see note) 30 cm 70 cm 2m 5m 10 m 100 to 120/200 to 240 VAC (switchable) APF/ PCF 24 VDC

C200H-PS221 C200H-PS221-C

100 to 120/200 to 240 VAC (switchable) Wired Conforms to EC directives 24 VDC

C200H-PS211 C200H-CN311 C200H-CN711 C200H-CN221 C200H-CN521 C200H-CN131 C200H-RT001-P C200H-RT002-P C200H-RT201 C200H-RT201-C C200H-RT202

Note: Units with lot numbers jjZ5 (Dec. 1995) or later.