SYSMAC C200HS Programmable Controllers Installation Guide, pages 81 to 90

Pages 81 to 90 of 221

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 81

Section 5-4

Special I/O Units Cam Positioner Unit

A single C200H-CP114 Cam Positioner Unit is as powerful as 48 mechanical cams because it can complete jobs that normally require 48 mechanical cams. It is possible to set 16-point external output and 32-point internal output as cam output. The 32-point internal output can be retrieved as data by the C200HS. Cam Positioner Unit

Heat/Cool Temperature Control Units

The Heat/Cool Temperature Control Units measure the temperature of an object with a connected temperature sensor (thermocouple or platinum resistance thermometer), and heats and cools according to a preset control mode. Select the control output of the Heat/Cool Temperature Control Unit from the following. Model C200H-TV001 C200H-TV002 C200H-TV003 C200H-TV101 C200H-TV102 C200H-TV103

Temperature sensor input Thermocouple: R, S, K (CA), J (IC), T (CC), E (CRC), B, N, L (IC), U (CC) Platinum resistance thermometer: JPt100, Pt100

Heat/Cool Temperature Control Unit

72

Data Setting Console

Control output Transistor output Voltage output Current output Transistor output Voltage output Current output

Data Setting Console

Page 82

Section 5-6

SYSMAC Support Software (SSS) PID Control Unit

The PID Control Unit scales inputs from connected sensors and then carries out PID control according to preset control mode. Select the control output of the PID Control Unit from the following. Model

Transistor output

C200H-PID02

Voltage output

C200H-PID03

Current output PID Control Unit

5-5

Control output

C200H-PID01

Data Setting Console

Ladder Support Software (LSS) The LSS is a powerful support software package for the OMRON C-series Programmable Controllers (PCs). The LSS runs on an IBM PC/AT or compatible personal computer, and can be use to program, monitor and control PCs. While some PCs require a SYSMAC NET Link Unit, Host Link Unit, or Peripheral Interface Unit to connect the computer running LSS, the C200HS can be connected directly to the LSS via it’s peripheral or RS-232C port. The LSS provides displays of various useful lists when the computer is operated offline and can be used to monitor operating conditions of the PC, and to read and write PC data. PC programs can be developed in a mnemonic or ladder diagram form. When working in ladder diagram form, not only the program is displayed but also other information such as I/O, block, and instruction comments can be input and displayed. Moreover, the LSS allows more than one PC to be connected to and monitored using a single computer. The monitoring speed can be accelerated if the optional S3200-NSB11-E SYSMAC NET NSB is used. For details concerning LSS, refer to the Ladder Support Software Operation Manual (W237).

5-6

SYSMAC Support Software (SSS) The SSS is an advanced software application that runs on IBM PC/AT or compatibles and is used to program, monitor, and otherwise control OMRON SYSMAC C-series PCs and SYSMAC CVM1 PCs. The C200HS can be connected directly to a computer running the SSS in exactly the same way as for the LSS. The SSS can be used with any of the CVM1 PCs and with all of the many C-series PCs. The SSS automatically switches programming styles and other operations between the various PCs when a PC model is set in the SSS’s System Setup. All programs written on the Ladder Support Software or on the CV Support Software can be read and used by the SSS. Programs created for the C2000H or C200HS families of PCs can be converted for use with CVM1 PCs so that existing programs can be used with the newer PCs.

73

Page 83

SYSMAC Support Software (SSS)

Section 5-6

The SSS naturally supports all of the functionality for C-series PCs as the LSS, plus some new functions that facilitate fast, efficient programming and operation.

74

Page 84

SECTION 6 Troubleshooting The C200HS provides self-diagnostic functions to identify many types of abnormal system conditions. These functions minimize downtime and enable quick, smooth error correction. This section provides information on hardware and software errors that occur during PC operation. It also provides troubleshooting charts for CPU Racks, Expansion I/O Racks, Input Units, and Output Units. 6-1 6-2 6-3 6-4 6-5 6-6 6-7

Alarm Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Programmed Alarms and Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reading and Clearing Errors and Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPU Racks and Expansion I/O Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Input Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

76 76 76 77 81 82 83

75

Page 85

Reading and Clearing Errors and Messages

6-1

Section 6-3

Alarm Indicators The ALM/ERR indicator on the front of the CPU provides visual indication of an abnormality in the PC. When the indicator is ON (ERROR), a fatal error (i.e., ones that will stop PC operation) has occurred; when the indicator is flashing (ALARM), a nonfatal error has occurred. ! Caution

6-2

The PC will turn ON the ALM/ERR indicator, stop program execution, and turn OFF all outputs from the PC for most hardware errors, for certain fatal software errors, or when FALS(07) is executed in the program (see tables on following pages). PC operation will continue for all other errors. It is the user’s responsibility to take adequate measures to ensure that a hazardous situation will not result from automatic system shutdown for fatal errors and to ensure that proper actions are taken for errors for which the system is not automatically shut down. System flags and other system and/or user-programmed error indications can be used to program proper actions.

Programmed Alarms and Error Messages FAL(06), FALS(07), and MSG(46) can be used in the program to provide user-programmed information on error conditions. With these three instructions, the user can tailor error diagnosis to aid in troubleshooting. FAL(06) is used with a FAL number other than 00, which is output to the SR area when FAL(06) is executed. Executing FAL(06) will not stop PC operation or directly affect any outputs from the PC. FALS(07) is also used with a FAL number, which is output to the same location in the SR area when FALS(07) is executed. Executing FALS(07) will stop PC operation and will cause all outputs from the PC to be turned OFF. When FAL(06) is executed with a function number of 00, the current FAL number contained in the SR area is cleared and replaced by another, if more have been stored in memory by the system. When MSG(46) is used a message containing specified data area words is displayed onto the Programming Console or another Programming Device. The use of these instructions is described in detail in the C200HS Operation Manual (W235).

6-3

Reading and Clearing Errors and Messages System error messages can be displayed onto the Programming Console or other Programming Device. On the Programming Console, press the CLR, FUN, and MONTR keys. If there are multiple error messages stored by the system, the MONTR key can be pressed again to access the next message. If the system is in PROGRAM mode, pressing the MONTR key will clear the error message, so be sure to write down all message errors as you read them. (It is not possible to clear an error or a message while in RUN or MONITOR mode; the PC must be in PROGRAM mode.) When all messages have been cleared, “ERR CHK OK” will be displayed. Details on accessing error messages from the Programming Console are provided in the C200HS Operation Manual (W235). Procedures for the LSS are provided in the LSS Operation Manual (W237).

76

Page 86

Section 6-4

Error Messages

6-4

Error Messages There are basically three types of errors for which messages are displayed: initialization errors, non-fatal operating errors, and fatal operating errors. Most of these are also indicated by FAL number being transferred to the FAL area of the SR area. The type of error can be quickly determined from the indicators on the CPU, as described below for the three types of errors. If the status of an indicator is not mentioned in the description, it makes no difference whether it is lit or not. After eliminating the cause of an error, clear the error message from memory before resuming operation. Asterisks in the error messages in the following tables indicate variable numeric data. An actual number would appear on the display.

Initialization Errors

The following error messages appear before program execution has been started. The POWER indicator will be lit and the RUN indicator will not be lit for either of these. The RUN output will be OFF for each of these errors.

Error and message Waiting for Special I/O or Interrupt Input Units

FAL no. None

CPU WAIT'G

Probable cause

Possible correction

A Special I/O Unit or Interrupt Input Unit has not initialized.

Perform the I/O Table Read operation to check unit numbers. Replace Unit if it is indicated by “$” only in the I/O table. (High-density I/O Units will not appear on I/O Table Read display for all peripheral devices.)

Waiting for Remote I/O

None

CPU WAIT'G

Non-fatal Operating Errors

Power to Remote I/O Unit is off or terminator cannot be found.

Check power supply to Remote I/O Units, connections between Remote I/O Units, and terminator setting.

The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will continue after one or more of these errors have occurred. For each of these errors, the POWER and RUN indicators will be lit and the ALM/ERR indicator will be flashing. The RUN output will be ON.

Error and message

FAL no.

Probable cause

Possible correction

01 to 99

FAL(06) has been executed in program. Check the FAL number to determine conditions that would cause execution (set by user).

Correct according to cause indicated by FAL number (set by user).

8A

An error occurred in data transfer between the Interrupt Input Unit and the CPU.

Replace the Interrupt Input Unit.

FAL error

SYS FAIL FAL**

Interrupt Input Unit error

SYS FAIL FAL8A

77

Page 87

Section 6-4

Error Messages Error and message

FAL no. 8B

Interrupt subroutine error

SYS FAIL FAL8B

Probable cause

Possible correction

Interrupt subroutine containing Special I/O Unit refresh was too long.

Check the interrupt subroutine and PC Setup.

Cyclic Special I/O Unit refreshing was not disabled for interrupt subroutine refresh. 9A

An error occurred in data transfer between a High-density I/O Unit and the CPU.

Check AR 0205 to AR 0214 to identify the Unit with a problem, replace the Unit, and restart the PC.

9B

An error has been detected in the PC Setup. This error will be generated when the setting is read or used for the first time.

Check an correct PC Setup settings.

9D

An error has occurred during data transmission between UM and a Memory Cassette because:

Make sure that the PC is in PROGRAM mode.

High-density I/O Unit error

SYS FAIL FAL9A

PC Setup error

SYS FAIL FAL9B

Memory Cassette Transfer error

SYS FAIL FAL9D

Not in PROGRAM Mode. UM or Memory Cassette is read-only. Insufficient capacity in UM or Memory Cassette. A checksum error occurred in the Memory Cassette

Make sure that the Memory Cassette is not write-protected. Make sure that the UM and Memory Cassette capacity is sufficient. Make sure the SYSMAC NET data link is not operating and transfer again (SR 27011 will be ON). Transfer the data again.

Cycle time overrun

F8

Watchdog timer has exceeded 100 ms.

Program cycle time is longer than recommended. Reduce cycle time if possible.

E7

Unit has been removed or replaced by a different kind of Unit, making I/O table incorrect.

Use I/O Table Verify Operation to check I/O table and either connect dummy Units or register the I/O table again.

B0 or B1

Error occurred in transmissions between Remote I/O Units.

Check transmission line between PC and Master and between Remote I/O Units.

D0

Error has occurred in PC Link Unit, Remote I/O Master Unit, between a Host Link, SYSMAC LINK, or SYSMAC NET Link Unit and the CPU, or in refresh between Special I/O Unit and the CPU.

Determine the unit number of the Unit which caused the error (AR 00), correct the error, and toggle the appropriate Restart Bit in AR 01, SR 250, or SR 252. If the Unit does not restart, replace it.

F7

Backup battery is missing or its voltage has dropped.

Check battery, and replace if necessary.

CYCLE TIME OVER

I/O table verification error

I/O VER ERR

Remote I/O error

REMOTE ERR Remote I/O Master Unit number

Special I/O Unit error

*

SIOU ERR

Battery error

BATT LOW

78

Page 88

Section 6-4

Error Messages Communications Errors

The COMM or COMM 1 indicator will go out for errors in communications between the peripheral port and a peripheral device and COMM 2 will will go out for errors in communications between the RS-232C port and a peripheral device. If an error is indicated, check the communications path and the C200HS program. The ports can be reset using the Peripheral Port Reset Bit (SR 25208) and the RS-232C Port Reset Bit (SR 25209).

Fatal Operating Errors

The following error messages appear for errors that occur after program execution has been started. PC operation and program execution will stop and all outputs from the PC will be turned OFF when any of the following errors occur. No CPU indicators will be lit for the power interruption error. For all other fatal operating errors, the POWER and ALM/ERR indicators will be lit. The RUN output will be OFF.

Error and message Power interruption

FAL no.

Check power supply voltage and power lines. Try to power-up again.

None

Watchdog timer has exceeded maximum setting (default setting: 130 ms).

Restart system in PROGRAM mode and check program. Reduce cycle time or reset watchdog timer if longer time required. (Consider effects of longer cycle time before resetting.)

F1

SR 27211 ON:

Check the PC Setup.

A checksum error has occurred in the PC Setup (DM 6600 to DM 6655). SR 27212 ON:

Check the program.

No message.

Memory error

Possible correction

Power has been interrupted for at least 10 ms.

No message.

CPU error

Probable cause

00

MEMORY ERR

A checksum error has occurred in the program, indicating an incorrect instruction. SR 27213 ON A checksum error has occurred in an expansion instruction change. SR 27214 ON: Memory Cassette was installed or removed with the power on. SR 27215 ON: Autoboot error. F0

No END(01) instruction

NO END INST

I/O bus error

I/O BUS ERR

*

Rack no.

END(01) is not written anywhere in program.

C0 to C2 Error has occurred in the bus line between the CPU and I/O Units.

Install the Memory Cassette correctly.

Check whether the CPU memory is protected or a checksum error occurred in the Memory Cassette. Write END(01) at the final address of the program.

The rightmost digit of the FAL number will indicate the number of the Rack where the error was detected. Check cable connections between the I/O Units and Racks.

79

Page 89

Section 6-4

Error Messages Error and message Too many Units

FAL no. E1

I/O UNIT OVER

Probable cause

Possible correction

Two or more Special I/O Units are set to the same unit number

Perform the I/O Table Read operation to check unit numbers, and eliminate duplications. (High-density I/O Units other than Group-2 are Special I/O Units, too.)

Two or more Group-2 High-density I/O Units or B7A Interface Units are set to the same I/O number or I/O word. The I/O number of a 64-pt Group-2 High-density I/O Unit is set to 9.

Set unit numbers of 64-pt Group-2 Units to numbers other than 9. Correct the settings. Mount only one Interrupt Unit.

SYSMAC NET or SYSMAC LINK systems are using duplicate settings (CPU31/33-E only). More than one Interrupt Unit is mounted. Input-output I/O table error

E0

Input and output word designations registered in I/O table do no agree with input/output words required by Units actually mounted.

Check the I/O table with I/O Table Verification operation and check all Units to see that they are in correct configuration. When the system has been confirmed, register the I/O table again.

01 to 99 or 9F

FALS has been executed by the program. Check the FAL number to determine conditions that would cause execution (Set by user or by system).

Correct according to cause indicated by FAL number. If FAL number is 9F, check watchdog timer and cycle time, which may be to long. 9F will be output when FALS(07) is executed and the cycle time is between 120 and 130 ms.

I/O SET ERROR

FALS error

SYS FAIL FALS**

80

Page 90

Section 6-5

CPU Racks and Expansion I/O Racks Other Error Messages

6-5

A number of other error messages are detailed within this manual. Errors in program input and debugging and errors in cassette tape operation are detailed in the C200HS Operation Manual (W235). Information on error flags is also contained in the C200HS Operation Manual (W235).

CPU Racks and Expansion I/O Racks Error

POWER indicator does not light. Fuses are frequently blown.

RUN indicator does not light.

RUN indicator is lit, but RUN output does not turn on. Relays do not operate from a particular number onwards. Outputs (or inputs) turn ON for particular Relay numbers. All the bits from a particular Unit turn ON.

Probable cause

Possible correction

A fuse is blown.

Replace the fuse.

The voltage selector terminal setting is wrong. Pattern short-circuiting or damage from fire The program has an error (no END instruction). The voltage selector terminal setting is wrong. A power supply line is defective. Special I/O Units are assigned overlapping unit numbers. A Slave Unit’s power supply is turned off, or no Unit is set as the terminator. The power circuit is defective.

Correct the voltage selector terminal setting. Replace the CPU or Power Supply Unit. Correct the program.

The I/O bus is defective.

Replace the Backplane.

Correct the voltage selector terminal setting. Replace the CPU. Correct the unit number assignments. Turn on the power to the Slave Unit, or set a Unit as the terminator. Replace the CPU.

81