Browse
(440) 299-7778
Menu
(440) 299-7778
One-year parts and labor warranty30-day money-back guaranteeContact

The text of a manual · part 8 of 23

SYSMAC C200HS Programmable Controllers Installation Guide, pages 71 to 80

Pages 71 to 80 of 221

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 71

Section 5-1

Programming Console

5-1

Programming Console There are two Programming Console models that can be used with the C200HS: the C200H-PRO27-E and the CQM1-PRO01-E. The following illustration shows how a Programming Console (a C200H-PRO27-E in this case) connects to the C200HS CPU.

C200H-CN222, C200H-CN422, C200HS-CN222, or C200HS-CN422 Connecting Cable

C200H-PRO27-E Programming Console

As indicated in the illustration, the C200H-PRO27-E Programming Console connects to the C200HS CPU with C200H-CN222, C200H-CN422, C200HS-CN222, or C200HS-CN422 Connecting Cable which must be purchased separately. The C200HS-CN222 and C200HS-CN422 Connecting Cables conform to EC directives. An anti-static cover is provided for the C200HS-CN222/CN422 over the connector on the CPU side. The CQM1-PRO01-E Programming Console comes with 2 m of Connecting Cable.

62

Page 72

Section 5-1

Programming Console

5-1-1 Nomenclature The front panel of the Programming Console is shown below, taking the C200H-PRO27-E as an example. C200H-PRO27-E Programming Console LCD area

Mode selector switch

Instruction keys

Numeric keys

Cassette jacks

Operation keys

LCD Area

This window displays the program contents and monitor status.

Mode Selector Switch

PROGRAM MODE: RUN MODE: MONITOR MODE:

Keys

Instruction, numeric, and operation keys are used for inputting the program and data. Note

Used for creating programs. Used for executing the programs. Used for monitoring C200HS status.

1. The operations of C200H-PRO27-E and CQM1-PRO01-E Programming Consoles are the same. 2. The following keys look different but have the same functions. AR HR

SET

RESET

HR

PLAY SET

REC RESET

3. The cassette jacks are not used by the C200HS.

63

Page 73

Section 5-3

Expanding the System

5-2

Checking Initial C200HS Operation After the Programming Console has been connected, it can be used to check initial C200HS operation. Make sure that the Programming Console is properly connected and that the correct power supply is being provided, and then follow the procedure outlined below. 1, 2, 3...

1. Check to be sure that the Programming Console is in PROGRAM mode. MONITOR RUN

PROGRAM

2. Turn on the power to the C200HS and check the CPU indicators. The green POWER indicator should light. 3. Check the Programming Console display and input the password (Clear and then Monitor Keys). If operation is normal, the display should appear as shown below. <PROGRAM> PASSWORD <PROGRAM>

BZ

Indicates the mode set by the mode selector switch.

4. After checking C200HS operation, turn off the power. If operation is not normal, refer to Section 6 Troubleshooting.

5-3

Expanding the System The C200HS System can be expanded to include a Host Link System (SYSMAC WAY), a PC Link System, Optical or Wired Remote I/O Systems (SYSMAC BUS) and SYSMAC NET Link or SYSMAC LINK System (C200HS-CPU31E/CPU33-E only). All of these can be used in common with the C200H. In addition, the following Units can be connected: Interrupt Input Unit, Analog Timer Unit, and B7A Interface Unit. Specifications for all of these Units are provided in Appendix B Specifications.

Host Link System

A maximum of two Host Link Units can be mounted to slots in either the CPU Rack or an Expansion I/O Rack. The following Host Link Units are available: C200H-LK101-PV1 (optical cable) C200H-LK201-PV1 (RS-232C) C200H-LK202-V1 (RS-422) For details, refer to the SYSMAC C-series Rack PCs SYSMAC WAY – Host Link Units System Manual (W143).

SYSMAC LINK Systems

OMRON’s SYSMAC LINK System is a communications network that connects up to 62 nodes to provide data links, data transfers, and datagram services. • Data links provide automatic transfer of up to 918 words of data in the LR and/ or DM Areas. • Data transfers of up to 256 words each can be implemented by programming the NETWORK READ (RECV(98)) and NETWORK WRITE (SEND(90)) instructions in the user program.

64

Page 74

Section 5-3

Expanding the System

• Data transfers via datagrams are also available using a command/response format. The C200HS-CPU31-E or C200HS-CPU33-E must be used to enable application of SYSMAC LINK Systems. The C200H-CE001 and C200H-CE002 Bus Connection Units are used to connect SYSMAC LINK Units to the CPU, and the C200H-APS03 Auxiliary Power Supply Unit is used as a backup power supply for optical SYSMAC LINK Systems. Note Refer to the SYSMAC LINK System Manual (W174) for further information.

C200HS CPU C200HS-CPU31-E or C200HS-CPU33-E

SYSMAC LINK Unit C200HW-SLK13/SLK14 (optical) C200HW-SLK23/SLK24 (coaxial cable)

SYSMAC-series PC

SYSMAC NET Link Systems

OMRON’s SYSMAC NET Link System is an FA-oriented limited-area network that connects up to 126 nodes to provide datagram services, data transfers, and data links. • Data transfers via datagrams are implemented using a command/response format. • Data transfers can also be implemented for up to 990 words each by programming the NETWORK READ (RECV(98)) and NETWORK WRITE (SEND(90)) instructions in the user program. • Data links provide automatic transfer of up to 32 words of data in the LR Area and/or up to 99 words of data in other data areas. The C200HS-CPU31-E or C200HS-CPU33-E must be used to enable application of SYSMAC NET Link Systems. The C200H-CE001 and C200H-CE002 Bus Connection Units are used to connect SYSMAC NET Link Units to the CPU, and the C200H-APS01 and C200H-APS02 Power Supply Adapters are used to connect to a central power supply (and must be mounted in the slot immediately to the left of the SYSMAC NET Link Unit).

65

Page 75

Section 5-3

Expanding the System

Note Refer to the SYSMAC NET Link System Manual (W178) for further information.

SYSMAC NET Link Unit C200HS-SNT32

C200HS CPU C200HS-CPU31-E or C200HS-CPU33-E

Line server

Central power supply

FA computer

SYSMAC-series PC

PC Link System

A PC Link System can be used to transfer data between PCs by means of LR 0000 through LR 6315. A maximum of two C200H-LK401 PC Link Units can be mounted to slots in either the CPU Rack or an Expansion I/O Rack. For details, refer to the PC Link System Manual (W135).

Remote I/O Systems

A maximum of two Optical or Wired Remote I/O Master Units can be mounted to slots in either the CPU Rack or an Expansion I/O Rack. A maximum total of five Slave Racks, each with a single Slave Unit, can be connected. C500 Slave Racks can be used, but each C500 Slave Rack must be counted as two Racks in calculating the total. For details, refer to the SYSMAC C-series Rack PCs Wired Remote I/O System Manual (W120) or SYSMAC C-series Optical Remote I/O System Manual (W136). Optical Systems Optical and Wired Units cannot be mixed. A maximum total of 64 (32 words) Optical I/O Units can be connected in an optical system. Note

1. The number of Slave Racks is not related to the number of Master Units. 2. If the number of Optical I/O Units exceeds 32, a B500-RPT01(-P) Repeater Unit is required. Wired Systems A maximum total of 32 I/O Interface Terminals and I/O Relay Terminals can be connected in a wired system. The number is unrelated to the number of Master Units mounted.

Special I/O Units

66

All of the Special I/O Units usable with the C200H can be used in common with the C200HS. A maximum of ten Special I/O Units (including PC Link Units) can be mounted to slots in either the CPU Rack, Expansion I/O Racks, or Slave Racks. For details, refer to the individual Special I/O Unit manuals and the following information.

Page 76

Section 5-4

Special I/O Units

5-4

Special I/O Units It is possible to connect a variety of Special I/O Units to the C200HS in the same way as the C200H.

5-4-1 Required Mounting Conditions A maximum of 10 Special I/O Units including PC Link Units can be mounted to any slot of CPU, Expansion I/O, and Slave Racks. I/O word numbers 100 to 199 and DM 1000 to DM 1999 are allocated to each Special I/O Unit. High-density I/O Units can be mounted Remote I/O Slave Units only when the Remote I/O Slave Units are connected to C200H-RM001-PV1 or C200HRM201 Remote I/O Master Units. The number of Special I/O Units used with a Slave Rack is limited by data transmission considerations, as shown in the table below. The numbers in the table indicate the maximum number of Units of groups A, B, C, or D which can be used with a single Slave Rack. A

B

C

High-speed Counter Units Position Control Units (NC111/112) ASCII Units Analog I/O Units ID Sensor Units Fuzzy Logic Units

High-density and Mixed I/O Units Temperature Control Units Cam Positioner Units Heat/Cool Temperature Control Unit PID Control Unit

Temperature Sensor Units Voice Units

Position Control Units (NC211)

4 units max.

8 units max.

6 units max.

2 units max.

Note

D

1. When a combination of Units from groups A, B, C, and D is used, the number from each group must satisfy both the following equations: 3A + B + 2C + 6D ≤ 12 A+B+C+D≤8 2. Other Units can be added until the total number of Units reaches ten. If PC Link Units are used, the number of Units including the PC Link Units must not exceed ten.

5-4-2 Special I/O Units and Functions Refer to page 103 for the specifications of each Special I/O Unit. High-density I/O Units (Special I/O Units)

The TTL Input Unit, DC Input Unit, TTL Output Unit, Transistor Output Unit, TTL I/O Unit, and DC Input/Transistor Output Unit are High-density I/O Units. The C200H-ID501, C200H-OD501, and C200H-MD501 are I/O Units for the TTL Unit. Eight input points each of the C200H-ID501, C200H-ID215, C200H-MD501, C200H-MD115, and C200H-MD215 can be set for pulse input. A High-density I/O Unit can retrieve pulse input, which is shorter in length than that of the High-density I/O Unit cycle time, as an input signal when the Highdensity I/O Unit is set for pulse input.

67

Page 77

Section 5-4

Special I/O Units

The C200H-MD501, C200H-MD115, and C200H-MD215 can each be set for 128 dynamic input points (64 points x two circuits) and the C200H-OD501 and C200H-OD215 can each be set for 128 dynamic output points (64 points x two circuits).

High-speed Counter Units

The High-speed Counter Units have the following six operation modes. Linear, circular, preset, gate, latch, and sampling operation modes The High-speed Counter Units, which have a counting speed of 50 kcps, can be used for phase-difference pulse input, adding and subtracting pulse input, and pulse and direction input. The High-speed Counter Units have eight-point output per single axis.

Rotary Encoder

Position Control Units

The Position Control Units have pulse-train output, thus enabling connection to stepping motor drivers or servomotor drivers. The C200H-NC111 and C200H-NC112 are for a single axis, and the C200HNC211 is for two axes.

Stepping motor driver or servomotor driver with pulse-train input.

Stepping motor or servomotor 5-V power supply

68

Page 78

Section 5-4

Special I/O Units Analog I/O Units

The Analog Input (A/D) Units retrieve analog inputs and the Analog Output (D/A) Unit sends analog outputs. The following Analog I/O Units are available: C200H-AD001 with 4-point analog input, C200H-AD002 with 8-point analog input, C200H-DA001 with 2-point analog output, and C200H-DA002 with 4-point analog output The Analog Input (AD) Unit is used. Analog input

Preamplifier transducer

Sensor

Analog output

Servomotor controller variable adjuster

Motor

The Analog Output (DA) Unit is used.

Temperature Sensor Units

The following table lists Temperature Sensor Unit models and available temperature sensors. Only one kind of temperature sensor can be connected to the C200H-TS001 or C200H-TS002. Each Temperature Sensor Unit connects to a maximum of four temperature sensor inputs. Model

Connectable temperature sensor

C200H-TS001

K (CA)/K (IC)

C200H-TS002

K (CA)/L (Fe-CuNi) (available for DIN)

C200H-TS101

JPt 100 Ω

C200H-TS102

Pt 100 Ω (available for DIN/1989JIS)

Thermocouple: K (CA), J (IC), L (Fe-CuNi) Platinum resistance thermometer: JPt100 Ω, Pt100 Ω

ASCII Unit

BASIC programs can be input to the ASCII Unit via its port 1 from any personal computer in terminal mode if the personal computer incorporates an RS-232C interface. It is possible to write BASIC programs with an IBM PC/AT or compatible.

Port 1 (RS-232C) Port 1/2

BASIC Program: Personal computer Input: Bar code reader Output: Printer and plasma display

69

Page 79

Section 5-4

Special I/O Units Voice Unit

Voice messages can be input from dynamic microphones or cassette tape recorders and output from loudspeakers or headsets via the Voice Unit. The Voice Unit incorporates a sentence function and word combination function, either of which can be selected to record voice messages for 64 seconds maximum. Voice can be saved on floppy disks with an IBM PC/AT or compatible. Voice input

Voice output

Voice saving/Re-input

Microphone or cassette tape player

Headset or speaker

Personal computer, or PROM Writer

C200H-CN224 Connecting Cable (2 m long with 6- and 25-pin connectors)

ID Sensor Units

The ID Sensor Units are used to construct non-contact information recognition systems. By connecting a R/W Head or R/W Antenna to an ID Sensor Unit, data can be written to the Data Carrier attached to each moving object and the data of the Data Carrier can be read by the C200HS. The following models of ID Sensor Units are available. Electromagnetic induction model: C200H-IDS01-V1 Microwave model: C200H-IDS21

C200H-PRO27-E Programming Console

R/W Head R/W Antenna

70

Data Carrier

Page 80

Special I/O Units

Section 5-4

Fuzzy Logic Unit

The C200H-FZ001 Fuzzy Logic Unit incorporates a high-functional fuzzy Logic processor and allows high-speed fuzzy logic. A personal computer can be connected to the Fuzzy Logic Unit via RS-232C cables for software development and monitoring. Use the C500-SU981-E Fuzzy Support Software for IBM PC/AT or compatible personal computers.

Temperature Control Units

Thermocouples or platinum resistance thermometers connect to the Temperature Control Unit. With the built-in selector of the Temperature Control Unit, ten kinds of thermocouples or two kinds of platinum resistance thermometers can be selected. Select the control output of the Temperature Control Unit from the following. Model C200H-TC001 C200H-TC002 C200H-TC003 C200H-TC101 C200H-TC102 C200H-TC103

Temperature sensor input Thermocouple: R, S, K (CA), J (IC), T (CC), E (CRC), B, N, L (IC), U (CC) Platinum resistance thermometer: JPt100, Pt100

Temperature Control Unit

Control output Transistor output Voltage output Current output Transistor output Voltage output Current output

Data Setting Console

71