SYSMAC C200HS Programmable Controllers Installation Guide, pages 61 to 70

Pages 61 to 70 of 221

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 61

Section 4-7

Standard I/O Unit Wiring

Wire the Units so that they can be easily replaced. In addition, make sure that the I/O indicators are not affected by the wiring. Terminal Blocks

Unlock the terminal block of an I/O Unit to remove the terminal block from the I/O Unit. You do not have to remove the lead wires from the terminal block in order to remove it from an I/O Unit.

Locks for terminal block. Unlock to remove the terminal block from the I/O Unit. Make sure the terminal block is locked securely after wiring is complete.

I/O Unit Cover

A C200H-COV11 Cover is provided as an I/O Unit cover for Units that use 10P terminal block connectors. After the I/O wiring has been completed, slide the cover up from the bottom, as shown in the illustration below.

Attach

Remove

Wiring Examples

I/O Unit cover

The following are examples of how to connect I/O devices to I/O Units. During wiring, work slowly and carefully. If an input device is connected to an Output Unit, damage may result. Check all I/O devices to make sure they meet the specifications (refer to Appendix A Specifications).

DC Input Units Contact output

IN

DC input

COM

51

Page 62

Section 4-7

Standard I/O Unit Wiring

When using the NPN-current-output configuration shown below, the sensor and Input Unit should receive their power from the same supply.

NPN current output + Current regulator

IN

Output 7 mA 0V

Sensor Power Supply

DC input

COM

NPN open-collector output +

Sensor Power Supply IN

Output 7 mA

DC input

COM

0V PNP current output +

Sensor Power Supply

Output

IN

7 mA 0V

AC/DC input

COM

0V

The circuit below should be used for I/O devices having a voltage output.

Voltage output + COM Output 0V

IN

DC input

Sensor Power Supply

The circuit below should NOT be used for I/O devices having a voltage output.

Voltage output + Output 0V

52

Sensor Power Supply IN COM

DC input

Page 63

Section 4-8

Input Circuits AC Input Units Contact output

IN

AC input

COM

AC Switching IN Proximity switch main circuit

4-8

AC input

COM

Input Circuits

Input Leakage Current

When two-wire sensors, such as photoelectric sensors, proximity sensors, or limit switches with LEDs, are used for 12/24-VDC input devices, the input bit may be turned ON erroneously by leakage current. In order to prevent this, connect a bleeder resistor across the input as shown below. Input power supply

Bleeder resistor

R

PC

Sensor

If the leakage current is less than 1.3 mA, there should be no problem. If the leakage current is greater than 1.3 mA, determine the resistance and power rating for the bleeder resistor using the following formulas. For standard I/O Units: I = leakage current in mA 7.2 kΩ max. R = –––––– 2.4 x I – 3 2.3 W = ––– W min. R Precautions for Connecting Two-wire Sensors

When two-wire sensors are used for 12/24-VDC input devices, check that the following conditions are satisfied. Failure to do so may result in faulty operation. Relationship between ON Voltage (VON) of the PC and Residual Voltage of the Sensor (VR) VON x VCC – VR Relationship between ON Current (ION) of the PC and Control Output (Load Current) of the Sensor (IOUT) IOUT (min) x ION x IOUT (max) ION = (VCC – VR – 1.5 [PC’s internal residual voltage])/RIN If ION is less than IOUT (min), connect bleeder resistance R. Obtain the constant for the bleeder resistance according to the following formula. R x (VCC – VR)/(IOUT (min) – ION) Power W y (VCC – VR)2 R × 4 [tolerance]

53

Page 64

Section 4-9

Output Circuits

Relationship between OFF Current (IOFF) of the PC and Leakage Current of the Sensor (Ileak) IOFF y Ileak For details, refer to sections providing precautions on leakage current. The value of IOFF will vary depending on the on the Unit. However, the value for Input Units for which OFF current specifications are not listed will be 1.3 mA.

DC Input Unit Two-wire sensor

VR

R

RIN

VCC

VCC: Power supply voltage VON: PC ON voltage ION: PC ON current IOFF: PC OFF current RIN: PC input impedance

4-9

VR: output residual voltage in the sensor IOUT: control output of the sensor (load current) Ileak: leakage current of the sensor R: bleeder resistance

Output Circuits When wiring outputs, take the following points into consideration.

Output Short-circuit Protection

If a load connected to the output terminals is short-circuited, output elements and printed boards may be damaged. To guard against this, incorporate a fuse in an external circuit.

Transistor Output Residual Voltage

When connecting TTL circuits to transistor Output Units, it is necessary to connect a pull-up resistor and a CMOS IC between the two. This is because of the residual voltage left on the transistor output after the output turns OFF.

Output Leakage Current

If there is a possibility of leakage current causing a transistor or triac to malfunction, connect a bleeder resistor across the output as shown below. OUT

L

R Load power supply

PC Bleeder resistor COM

Determine the value and rating for the bleeder resistor using the following formula. R

Where Eon = ON voltage of the load in V I = leakage current in mA R = bleeder resistance in kΩ

54

Eon ––– I

Page 65

Section 4-9

Output Circuits Output Surge Current

When connecting a transistor or triac Output Unit to an output device having a high surge current (such as an incandescent lamp), care must be taken to avoid damage to the Output Unit. The transistor and triac Output Units are capable of withstanding a surge current of ten times the rated current. If the surge current for a particular device exceeds this amount, use the circuit shown below to protect the Output Unit.

L

OUT

+ R COM

Another way of protecting the Output Unit lets the load draw a small current (about one third the rated current) while the output is OFF, significantly reducing the surge current. This circuit (shown below) not only reduces the surge current, but also reduces the voltage across the load at the same time. R OUT

L

+ COM

Electrical Noise

Whenever possible, place I/O signal lines and power lines in separate ducts or tubes. If placing them together cannot be avoided, use shielded cable to minimize the effects, and connect the shielded end to the GR terminal.

55

Page 66

Section 4-9

Output Circuits Inductive Load Surge Suppressor

When an inductive load is connected to an I/O Unit, it is necessary to connect a surge suppressor or diode in parallel with the load as shown below. This is so that the back EMF generated by the load will be absorbed. IN

L

Diode

DC input

COM OUT

L

Contact Output Unit Triac Output Unit Surge suppressor COM OUT

L

+

Contact Output Unit Transistor Output Unit Diode COM

Use surge suppressors and diodes with the following specifications. Surge Suppressor Resistance: 50 Ω Capacitor: 0.47 µF Voltage: 200 V Diode Leading-edge peak inverse voltage: At least 3 times load voltage Average rectified current: 1A

56

Page 67

Section 4-11

System Design and Safety Considerations

4-10 External Wiring If power cables must be run alongside the I/O wiring (that is, in parallel with it), at least 300 mm must be left between the power cables and the I/O wiring as shown below.

Low current cable 1 300 mm min. Control cable 2

Power cable

300 mm min.

3

Class-3 ground

Where:

1 = I/O wiring 2 = General control wiring 3 = Power cables

If the I/O wiring and power cables must be placed in the same duct (for example, where they are connected to the equipment), they must be shielded from each other using grounded metal plates. Metal plate (iron) 200 mm min. 1

2

3

Class-3 ground

Where:

1 = I/O wiring 2 = General control wiring 3 = Power cables

4-11 System Design and Safety Considerations When designing a C200HS system, be sure to consider the following points: • Power supply system wiring and emergency stop circuit • Interlock circuit • Programmable Controller power interruptions

4-11-1 Power Supply System and Emergency Stop Circuit The power section, control section, PC System, and the DC I/O system should all be wired separately.

57

Page 68

Section 4-11

System Design and Safety Considerations

An external relay should be used to form an emergency stop circuit that turns the power to the PC OFF in the event of an emergency. An emergency stop routine in the PC program is not sufficient to ensure safety. The circuit shown below is an example of an emergency stop circuit. Incorporate the PC RUN output terminal into an external relay circuit (CR1 in the diagram below) so that a PC breakdown or malfunction will not affect the entire system. MCB1 Power section

MCB2

CR1 Control section

Transformer or noise filter PC Twisted

DC voltage regulator PC RUN output

+ –

DC input/output

CR1

Surge suppressor

4-11-2 Interlock Circuit When the PC controls an operation such as the clockwise and counterclockwise operation of a motor, provide an external interlock such as the one shown below to prevent both the forward and reverse outputs from turning ON at the same time.

Interlock circuit

00501

MC2 MC1 Motor clockwise

PC 00502

MC1 MC2 Motor counterclockwise

This circuit prevents outputs MC1 and MC2 from ever both being ON at the same time. Even if the PC is programmed improperly or malfunctions, the motor is protected.

58

Page 69

Section 4-11

System Design and Safety Considerations

4-11-3 Programmable Controller Power Interruptions A sequential circuit is built into the PC to handle power interruptions. This circuit prevents malfunctions due to momentary power loss or voltage drops. A timing diagram for the operation of this circuit is shown below. The PC ignores all momentary power failures if the interruption lasts no longer than 10 ms. If the interruption lasts between 10 and 25 ms, the interruption may or may not be detected. If the supply voltage drops below 85% of the rated voltage for longer that 25 ms (less for the DC Power Supply), the PC will stop operating and the external outputs will be automatically turned OFF. Operation is resumed automatically when the voltage is restored to more than 85% of the rated value. The diagram below shows the timing of PC operation and stopping during a power interruption. The time it takes to detect the power failure is shorter when the power supply is DC. Power interrupted

Power restored

Power supply Power failure detection signal

Time lapse until detection

+5 V CPU operating voltage Power supply reset Output during operation

1s

59

Page 70

SECTION 5 Peripheral Devices and System Expansion A Programming Console or IBM PC/AT running Ladder Support Software (LSS) or SYSMAC Support Software (SSS) can be used to program and monitor the C200HS PCs. This section provides general information about the Programming Console, LSS, SSS, and ways in which the C200HS System can be expanded for more versatility. For descriptions of new Programming Console operations, refer to the C200HS Operation Manual (W235). For details concerning LSS and SSS, refer to the Ladder Support Software Operation Manual (W237) and the SYSMAC Support Software Operation Manuals (Basics: W247; C-series PCs: W248) respectively. 5-1 5-2 5-3 5-4

5-5 5-6

Programming Console . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1-1 Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Checking Initial C200HS Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Expanding the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Special I/O Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4-1 Required Mounting Conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4-2 Special I/O Units and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Ladder Support Software (LSS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . SYSMAC Support Software (SSS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

62 63 64 64 67 67 67 73 73

61