Page 51
Section 3-5
Mounting Requirements
3-5
Mounting Requirements Each Rack must be mounted vertically, that is with the printing on the front panels oriented as it would normally be read. The Racks should be mounted one above the other with the CPU Rack uppermost as shown below.
CPU Rack
These connectors are not used. Cover them with caps.
Expansion Rack
Expansion Rack
The C200HS is approved by Underwriters Laboratories under the condition that, “The device must be mounted vertically for ventilation purposes.” DIN Track Mounting
The PC may be mounted using DIN track if desired. This type of mounting is not required, and the PC may be directly mounted to any sturdy support meeting the environmental specifications (refer to Appendix B Specifications). If you want to mount the PC on DIN track, you can order a DIN Track from OMRON (refer to Appendix B Standard Models). DIN Tracks come in the two heights shown below.
7.3-mm Height
16-mm Height
41
Page 52
Section 3-5
Mounting Requirements DIN Track Mounting Bracket
The DIN Track Mounting Bracket shown below is necessary for mounting the PC to the DIN Track.
Item DIN Track Mounting Bracket DIN
Specification
Model
One set (two brackets)
C200H-DIN01
50 cm long, 7.3 mm high 1 m long, 7.3 mm high 1 m long, 16 mm high
PFP-50N PFP-100N PFP-100N2
Procedure 1, 2, 3...
1. The following diagram is a view of the back of the Backplane. Attach one Mounting Bracket to the left and right sides of the Backplane as shown below. Backplane
DIN Track Mounting Bracket There are two Backplane mounting screws each on the left and right sides of the Backplane. Use these screws to attach the DIN Track Mounting Brackets to the Backplane.
2. Mount the Backplane to the DIN Track so that the claws on the Mounting Brackets fit into the upper portion of the DIN Track as shown below. This claw fits into the DIN Track
DIN Track
Backplane DIN Track Mounting Bracket
42
Page 53
Section 3-6
Installing Memory Cassettes
3. Loosen the screws attaching the Mounting Brackets to the Backplane. Slide the Backplane upward as shown below so that the Mounting Bracket and Backplane clamp securely onto the DIN Track. Tighten the screws.
23
DIN Track Mounting Bracket
DIN Track
Hold-down bracket Projections
3-6
Slide this screw to the top of the projection and then tighten it.
Installing Memory Cassettes An optional Memory Cassette can be installed in the C200HS. (The C200H Memory Unit cannot be used with the C200HS.) The two types of Memory Cassettes are described in 2-2-6 Memory Cassettes. To install a Memory Cassette, follow the procedure outlined below. ! Caution
Be careful to always turn the power off before inserting or removing a Memory Cassette. If a Memory Cassette is inserted into or removed from the CPU with the power on, it may cause the CPU to malfunction or cause damage to the memory.
1, 2, 3...
1. Set the DIP switch. For an EEPROM Memory Cassette, set pin no. 1 (write protect) to either ON or OFF. Setting it to ON will protect the program in the memory from being overwritten. Setting it to OFF will allow the program to be overwritten. (The factory setting is OFF.) For an EPROM Memory Cassette, set pin no. 1 (ROM Type Selector) according to the type of ROM that is to be mounted. Even if a 27512-type chip is mounted, the usable capacity is still only 16 KB. Pin no. 1
ROM type
Model
Capacity
Access speed
OFF
27256
ROM-JD-B
16 KB
150 ns
ON
27512
ROM-KD-B
32 KB
150 ns
2. Write to EPROM (if using an EPROM Memory Cassette). Using a PROM Writer, write the program to EPROM. Then mount the EPROM chip to the Memory Cassette, with the notched end facing upwards as shown in the illustration below. Notch
43
Page 54
Installing Memory Cassettes
Section 3-6 3. Remove the bracket from the Memory Cassette, as shown in the illustration below.
Metal bracket
4. Check that the connector side goes in first and that the Cassette’s circuit components face right and then insert the Cassette into the CPU. The Cassette slides in along a track in the CPU.
5. Replace the Memory Cassette bracket over the Cassette and tighten the screw that holds the bracket.
44
Page 55
SECTION 4 Wiring This section provides the information necessary to wire a C200HS System. 4-1 Power Supply Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 AC Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3 DC Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 RUN Output Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 Backplane Insulation Plate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 Standard I/O Unit Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8 Input Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9 Output Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10 External Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11 System Design and Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11-1 Power Supply System and Emergency Stop Circuit . . . . . . . . . . . . . . . . . . . . . . . 4-11-2 Interlock Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11-3 Programmable Controller Power Interruptions . . . . . . . . . . . . . . . . . . . . . . . . . . .
46 46 47 48 48 49 50 53 54 57 57 57 58 59
45
Page 56
Section 4-2
AC Power Supply
4-1
Power Supply Wiring Pay attention to the following points when wiring the power supply. • Be sure to mount the CPU and the I/O Power Supply Unit in their proper positions. • Provide power to the CPU and the I/O Power Supply Unit from the same power source. If different power sources are provided, then the CPU and the Programming Console will not operate whenever power is not turned on to the I/O Power Supply Unit. • When a DC power supply is used, be sure to properly connect the plus and minus terminals. • Securely lock removeable terminal blocks. • Wire the Units with the top-surface labels still in place, and then remove the labels after the wiring is completed.
4-2
AC Power Supply The C200HS-CPU01-E, C200HS-CPU01-EC, C200HS-CPU21-E, C200HSCPU21-EC and C200HS-CPU31-E CPUs, and the C200H-PS221 and C200H-PS221-C I/O Power Supply Units use an AC power supply. Provide either 100 to 120 VAC or 200 to 240 VAC, with an allowable fluctuation range of 85 to 132 VAC or 170 to 264 VAC respectively.
C200HS-CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E Screw (3.5 mm head with self-raising pressure plate)
Breaker 1:1 isolation transformer
Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC + Short-circuit these terminals with the shorting – bracket supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC 24-VDC output leave them open. C200H-PS221/PS221-C Screw (3.5 mm head with self-raising pressure plate) Voltage selector Short: 100 to 120 VAC Open: 200 to 240 VAC + Short-circuit these terminals with the shorting bracket – supplied as an accessory to select 100 to 120 VAC supply voltage. For 200 to 240 VAC, leave them open.
Isolation transformer • Noise between the PC and ground can be significantly reduced by connecting a 1-to-1 isolation transformer. Do not ground the secondary coil of the transformer. Power line • Use AWG 14 twisted pair cable (cross-sectional area of 2 mm2 min).
AC power source
• Supply 100 to 120 or 200 to 240 VAC • Keep voltage fluctuations within the specified range (refer to Appendix B Specifications) Note: The LG markings of the C200HS-CPUjj-E and C200HS-CPUjj-EC are different from each other. Note: The LG markings of the C200HS-PS221 and C200HS-PS221-C are different from each other.
24-VDC output
Note The C200HS-CPU01-EC CPU, C200HS-CPU21-EC CPU, and C200H-PS221-C I/O Power Supply Unit do not have an LG terminal. 24-VDC Output
Use these terminals as the power supply for 24-VDC Input Units. Note DC Power Supply Units do not have these terminals.
Crimp Terminals
46
When wiring, use crimp terminals. Do not connect power lines that have only been twisted together directly to the terminal blocks.
Page 57
Section 4-3
DC Power Supply Tighten terminal block screws with a torque of 0.8 N-m.
Use crimp terminals suitable for M3.5 screws that have the following dimension.
7 mm max.
! Caution
Tighten power supply terminal screws with a torque of 0.8 N-m. Not tightening the screws securely may result in a fire or faulty operation.
Note
1. Be sure to use the same circuits when supplying power to the Power Supply Units. 2. Check the settings for the power supply voltage switching terminals. 3. After the wiring has been completed, be sure to remove the top-surface label in order to allow heat radiation.
4-3
DC Power Supply The C200HS-CPU03-E, C200HS-CPU23-E, and C200HS-CPU33-E CPUs, and the C200H-PS211 I/O Power Supply Unit use a 24-VDC power supply with an allowable fluctuation range of 20.4 to 26.4 VDC.
C200H-CPU03-E/CPU23-E/CPU33-E Screw (3.5 mm head with self-raising pressure plate) +
Breaker fluctuations within the specified range (refer to Appendix B Specifications)
–
C200H-PS211
Screw (3.5 mm head with self-raising pressure plate) + –
• Supply 24 VDC • Keep voltage
Power line • Use AWG 14 twisted pair cable (cross-sectional area of 2 mm2 min).
47
Page 58
Section 4-5
Grounding
4-4
RUN Output Terminals
Emergency stop circuit
To system control circuit
RUN output
Screw (3.5 mm head with self-raising pressure plate)
RUN Output
These terminals are short-circuited during PC operation. Use them to receive PC RUN signals, for purposes such as emergency stop circuits. Maximum switching capacity: 250 VAC, 2 A (cos ∅ = 1) 250 VAC, 0.5 A (cos ∅ = 0.4) 24 VDC, 2 A Note
4-5
1. I/O Power Supply Units do not have these terminals. 2. For the C200H-CPU03-E, use a DC power supply provided with reinforced insulation or double insulation if the EC directives (low-voltage directives) must be satisfied.
Grounding To avoid electrical shock, attach a grounded (earth ground) AWG 14 wire (crosssectional area of at least 2 mm2) to the GR terminal. The resistance to ground must be less than 100 Ω. Do not use a wire longer than 20 m. Care must be taken, because ground resistance is affected by environmental conditions such as soil composition, water content, time of year, and the length of time since the wire was laid underground. The Line Ground (LG) terminal is a noise-filtered neutral terminal that does not normally require grounding. If electrical noise is a problem, however, this terminal should be connected to the Ground (GR) terminal. PC operation may be adversely affected if the ground wire is shared with other equipment, or if the ground wire is attached to the metal structure of a building.
48
Page 59
Section 4-6
Backplane Insulation Plate
When using an Expansion I/O Rack, the Rack must also be grounded to the GR terminal. The same ground can be used for all connections. C200HS-CPU01-E/CPU01-EC/CPU03-E/CPU21-E/CPU21-EC/CPU31-E/CPU23-E/CPU33-E
Screw (3.5 mm head with self-raising pressure plate)
C200H-PS221/PS221-C/PS211 I/O Power Supply Unit Screw (3.5 mm head with self-raising pressure plate) Ground wire (2 mm2 or larger)
Note The LG terminal is not provided for the C200HS-CPU01-EC CPU and C200H-PS221-C I/O Power Supply Unit.
4-6
Backplane Insulation Plate If there is an electric potential difference between grounds when devices are wired separately, then use a Backplane Insulation Plate. There are four models available, corresponding to the number of slots in the Backplane. The dimensions at locations A, B, C, D, and E are shown below in millimeters for each Backplane Insulation Plate model. Specifications
Dimensions (mm)
Model
For 3 slots
C200H-ATT31
E 261
D 210
C ---
B ---
A 246
For 5 slots
C200H-ATT51
331
280
---
---
316
For 8 slots
C200H-ATT81
436
385
---
---
421
For 10 slots
C200H-ATTA1
506
455
227.5
270.5
491
M4 screws for mounting to PC (4/5 places)
5-dia. holes for mounting Base Insulation Plate (4/6 places)
(B)
6 12 dia.
5 dia.
135 (118) 110
C D (A) E
10
49
Page 60
Section 4-7
Standard I/O Unit Wiring
4-7
Standard I/O Unit Wiring ! Caution
Check the I/O specifications for the I/O Units, and consider the following points. • For the I/O Units, use a DC power supply provided with reinforced insulation or double insulation if the EC directives (low-voltage directives) must be satisfied. • Do not apply a voltage that exceeds the input voltage for Input Units or the maximum switching capacity for Output Units. Doing so may result in breakdown, damage or fire. • When the power supply has positive and negative terminals, be sure to wire them correctly.
Electric Wires
The following electric wires are recommended. Electric Wire Size Terminal Block Connector 10-terminal AWG 22 to 18 (0.33 to 0.82 mm2) 19-terminal AWG 22 (0.33 mm2) Larger sizes than these can be used for common lines. Note The allowable current capacity electric wire differs depending on factors such as ambient temperature, insulation thickness, etc., so be sure to take these factors into account when selecting electric wire. The terminals have screws with 3.5-mm diameter heads and self-raising pressure plates. Connect the lead wires to the terminals as shown below. Tighten the screws with a maximum torque of 0.8 NSm.
Crimp Terminals
If you wish to attach solderless type terminals to the ends of the lead wires, use terminals having the dimensions shown below.
7 mm max.
Wiring
7 mm max.
Be sure that each Unit is securely mounted. In order to prevent wire scraps and other objects from getting inside of the Unit, keep the top-surface label on while wiring the Unit. After the wiring has been completed, be sure to remove the label in order to allow heat radiation. During wiring
After wiring Remove the label.
50