SYSMAC C200HS Programmable Controllers Installation Guide, pages 41 to 50

Pages 41 to 50 of 221

The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Omron C200H-OC225 and Omron C200HW-SLK23

Page 41

Section 2-5

I/O Units

2-5-3 High-density I/O Units Classified as Special I/O Units Some High-density I/O Units are classified as Special I/O Units. Up to 10 Special I/O Units can be connected to a PC. The Units have two 24-pin connectors. In general, these Units control 32 I/O points, although some Units can control 128 I/O points when set for dynamic operation. Refer to Appendix B Specifications for detailed specifications and dimensions of the Units. Unit

Specifications

Model Number

Remarks

TTL Input Unit DC Input Unit

5 VDC, 32 inputs 24 VDC; 32 inputs

C200H-ID501 C200H-ID215

8 pts can be set as high-speed inputs.

TTL Output Unit

5 VDC, 32 outputs

C200H-OD501

Can be set for 128 dynamic outputs.

Transistor Output Unit

24 VDC; 32 outputs

C200H-OD215

TTL I/O Unit DC Input/Transistor Output Unit

5 VDC, 16 inputs, 16 outputs 12 VDC; 16 inputs, 16 outputs 24 VDC; 16 inputs, 16 outputs

C200H-MD501 C200H-MD115 C200H-MD215

8 pts can be set as high-speed inputs. Can be set for 128 dynamic inputs.

Note Refer to Optional Products, Appendix A Standard Models for a list of external connectors. Setting the Unit Number

High-density I/O Units are each allocated 10 I/O words in the IR Area (IR 100 to IR 199) by setting the unit number switch on the front of each Unit. The 10 words begin with n, where n = IR 100 + 10 × unit number. For example, a Special I/O Unit with a unit number of 3 would be allocated IR 130 to IR 139. Always turn the PC power off before changing a Unit’s unit number. The new unit number (0 to 9) will not be recognized unless the PC has been turned off.

Setting the DIP Switch

Pin

The operation of High-density I/O Units is controlled by setting the pins of the DIP switch on the back panel. The following table shows the function of each pin and applicable Units.

Function

1

Operating mode

2

High-speed input1

C200H-OD501/OD215

ON 128 dynamic outputs

OFF 32 outputs

C200H-MD501/MD115/MD215

128 dynamic inputs

16 inputs, 16 outputs

C200H-ID501/ID215

Inputs 08 to 15 of CN2 are high-speed inputs. Inputs 08 to 15 of CN2 are high-speed inputs. 4 ms

Normal inputs

15 ms max.

2.5 ms max.

Positive logic

Negative logic

---

---

C200H-MD501/MD115/MD215 3

Setting

Applicable Units

4

High-speed input minimum pulse width2 Input response time3

5

Data output mode4

C200H-ID501/ID215 C200H-MD501/MD115/MD215 C200H-ID501/ID215 C200H-MD501/MD115/MD215 C200H-OD501/OD215

6

Not used.

---

Note

Normal inputs 1 ms

1. Used in the C200H-MD501/MD115/MD215 only when pin 1 is OFF, setting the Unit to static mode. 2. Used in the C200H-ID501/215, C200H-MD501/MD215/MD115/MD215 only when pin 2 is ON, setting the Unit to High-speed input mode. 3. Sets the input response time for normal inputs. When pin 2 is ON, CN2 08 to 15 are pulse-catch inputs. Other inputs can be used as normal inputs.

30

Page 42

Section 2-5

I/O Units

4. Used when pin 1 is ON, setting the C200H-OD501/OD215 to dynamic output mode. I/O Unit lock notch

Nameplate

I/O indicators: Indicate ON/OFF status of points Unit number setting switch

24-pin connectors

31

Page 43

SECTION 3 Installation The term “PC” can refer to a single object, but actually even the simplest PCs are usually composed of several different devices. In fact a PC can be physically spread throughout a building and still be called a single PC. This section describes how to install a PC System, including mounting the various Units and configuring the System. Be sure to follow the instructions carefully during installing. Improper installation can cause the PC to malfunction, resulting in extreme danger. 3-1 3-2 3-3 3-4 3-5 3-6

Installation Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Units to the Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing Racks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I/O Connecting Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installing Memory Cassettes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

34 35 39 40 41 43

33

Page 44

Section 3-1

Installation Environment

3-1

Installation Environment This section details the necessary environmental conditions for installing the PC. ! Caution

Ambient Conditions

Static electricity can damage PC components. Your body can carry an electrostatic charge, especially when the humidity is low. Before touching the PC, be sure to first touch a grounded metallic object, such as a metal water pipe, in order to discharge any static build-up. Do not install the PC in any of the following locations. Doing so will affect PC life and may affect operating performance. • Locations subject to ambient temperatures lower than 0°C or higher than 55°C, or 0°C to 45°C when a Programming Console is used. • Locations subject to drastic temperature changes or condensation. • Locations subject to ambient humidity lower than 10% or higher than 90%. • Locations subject to corrosive or flammable gases. • Locations subject to excessive dust (especially iron dust) or chloride. • Locations that would subject the CPU to direct shock or vibration. • Locations that would subject the PC to water, oil, or chemical reagents. • Locations exposed to direct sunlight.

Cooling

There are two points to consider in order to ensure that the PC does not overheat. The first is the clearance between the Racks, and the second is installation of a cooling fan.

Clearance between Racks

The Racks need to have sufficient room between each other to allow for I/O wiring, and additional room to ensure that the I/O wiring does not hamper cooling. The Racks must also be mounted so that the total length of the Connecting Cable between all Racks in a given series does not exceed 12 m. As a general rule, about 70 to 120 mm should be left between any two Racks. Consider factors such as the width of the wiring duct, wiring length, ventilation, and ease of access to Units, when determining the spacing between Racks. Greater space is required between Racks when using certain CPU Bus and Special I/O Units. Refer to the operation manuals for the Units you are using for details.

Cooling Fan

A cooling fan is not always necessary, but may be needed in some installations. Try to avoid mounting the PC in a warm area or over a source of heat. A cooling fan is needed if the ambient temperature may become higher than that specified. If the PC is mounted in an enclosure, install a cooling fan, as shown in the following diagram, to maintain the ambient temperature within specifications. Fan

PC

Louver

34

Page 45

Section 3-2

Mounting Units to the Backplane Noise

Do not mount the PC in a control panel in which high-power equipment is installed, or near high heat-producing devices such as heaters, transformers, or large-capacity resistors. To avoid noise, make sure the point of installation is at least 200 mm away from power lines as shown in the following diagram. Ensure that the plate to which the PC is mounted is grounded. Power lines

200 mm min. PC 200 mm min.

3-2

Mounting Units to the Backplane There is no single Unit that can be said to constitute a Rack PC. To build a Rack PC, we start with a Backplane. The C200H Backplane (used for the C200HS PC) is shown below.

C200H Backplane

The Backplane is a simple device having two functions. The first is to provide physical support for the Units to be mounted to it. The second is to provide the connectors and electrical pathways necessary for connecting the Units mounted to it. The core of the PC is the CPU. The CPU contains the program consisting of the series of steps necessary for the control task. The CPU has a built-in power supply, and fits into the rightmost position of the Backplane.

35

Page 46

Section 3-2

Mounting Units to the Backplane

The CPU of the C200HS has no I/O points built in. So, in order to complete the PC it is necessary to mount one or more I/O Units to the Backplane. Mount the I/O Unit to the Backplane by locking the top of the I/O Unit into the slot on the Backplane and rotating the I/O Unit downwards as shown in the following diagram.

Hook

Backplane

Lock lever

Press down on the yellow lock lever at the bottom of the slot, press the I/O Unit firmly into position, and then release the yellow lock lever.

(To remove a Unit, hold down the lock lever with an implement such as a screwdriver.)

36

Page 47

Section 3-2

Mounting Units to the Backplane

CPUs, I/O Power Supply Units and Slave Units must have two screws on the bottom tightened with a Phillips screwdriver. The screwdriver must be held at a slight angle, so be sure to leave enough space below each Rack.

Duct 20 mm min. Phillips screwdriver

CPU Backplane I/O Power Supply Unit Remote I/O Rack 20 mm min. Duct

The mounting height of CPU Racks, Expansion I/O Racks, or Slave Racks is 118 mm or 143 mm depending on the type of I/O Units mounted. If Peripheral Devices or connection cables are attached, the additional dimensions must be taken into account. Allow sufficient clearance in the control panel in which the PC is mounted.

D C

CPU C200HS-CPU01-E/CPU01-EC 118 /CPU03-E C200HS-CPU21-E/CPU21-EC 143 /CPU23-E/CPU31-E/CPU33-E

D (mm)

C (mm) Approx. 180 to 200 Approx. 200 to 220

The figure below shows one I/O Unit mounted directly to the left of the CPU.

I/O Units are where the control connections are made from the PC to all the various input devices and output devices. As you can see from the figure above,

37

Page 48

Mounting Units to the Backplane

Section 3-2 there is still some space available on the left side of the Backplane. This space is for any additional I/O Units that may be required.

The figure above shows a total of eight I/O Units mounted to the Backplane. When using 16-point Output Units (models C200H-OC225/OD212/OD21A) mount them to a C200H-BCjj1-V1/V2 Backplane. If a Backplane other than this model is used, the Units will not operate properly. Interrupt Input Units must be mounted to a C200H-BCjj1-V2 Backplane to operate properly. Only one Interrupt Input Unit can be mounted per PC. Backplanes are available in different lengths (three, five, eight, ten slots), and can hold a different number of I/O Units accordingly (refer to Appendix B Specifications for dimensions). Of course, not all I/O Units look exactly alike, but the ones in the figure show their typical appearance. This configuration of Backplane, CPU, and I/O Units is called a CPU Rack. This term refers to the Backplane and all the Units mounted to it. However, if we want to include more than eight I/O Units in our configuration we can add an additional Backplane. This Backplane has I/O Units mounted to it, but it has no CPU of its own. The additional Backplane must also have an Expansion I/O Power Supply mounted to its rightmost position. This configuration of additional Backplane, Expansion I/O Power Supply, and I/O Units is called an Expansion I/O Rack.

The CPU Rack and Expansion I/O Rack shown above are connected by a Connecting Cable (the length of Cable between individual Racks can be up to 10 m, but the total length of Cable between all Racks must be within 12 m). Remember that this whole configuration is still referred to as one PC. It is possible to add up to two Expansion I/O Racks and five Remote I/O Slave Racks to one CPU Rack. When installing I/O Connecting Cables, cover any unused connectors with the caps provided.

38

Page 49

Section 3-3

Installing Racks

3-3

Installing Racks The following figures show two side views, each consisting of a mounted CPU and two Expansion I/O Racks. Provide a space of 20 mm minimum on the upper and lower sides of each duct for ventilation and Unit replacement purposes. C200HSCPU01-E/CPU01-EC/ CPU03-E

30 mm

30 mm

C200HS-CPU21-E/CPU21-EC/ CPU23-E/CPU31-E/CPU33-E

118 mm

143 mm

CPU

CPU

Duct

30 mm

I/O 40 mm

30 mm

Duct I/O

Duct I/O

30 mm

Duct I/O

Each Rack must be mounted vertically, that is, with the printing on the front panels oriented as it would normally read. Racks may be directly mounted to any sturdy support meeting the environmental specifications. Whenever possible, use wiring conduit to hold the I/O wiring. Standard wiring conduit should be used, and it should be long enough to completely contain the I/O wiring and keep it separated from other cables. ! Caution

Racks must be mounted horizontally so that the Units are upright (i.e., not upside down or lying on their backs).

39

Page 50

Section 3-4

I/O Connecting Cable

The duct work shown in the following diagram is not used for mounting the Racks. Although optional, this duct work can be used to house the wires from the I/O Units that run along the sides of the Racks, keeping the wires from becoming entangled. This figure illustrates the correct way to mount the Racks. Input duct

Power duct

Output duct

200 mm min.

CPU Rack

Breakers, fuses

I/O Connecting Cable

Expansion I/O Rack Power equipment such as transformers and magnetic relays

Fuses, relays, timers, etc. (NOT heat-generating equipment, power equipment, etc.)

3-4

Terminal blocks for PC

Terminal blocks for power equipment

I/O Connecting Cable Up to 10 meters of I/O connecting cable can be used in one place only, and the maximum total length of connecting cable that can be used is 12 meters. Do not place I/O connecting cable in the same ducts used for I/O lines and power lines. Insert the cable firmly in the CPU Rack and Expansion I/O Rack connectors, and be sure to secure it by firmly tightening the two screws. ! Caution

If an I/O connecting cable connector comes loose, an I/O bus error will be generated and operation will stop. If I/O connecting cable is to be passed through a hole, a diameter of at least 53 mm is required. If the upper cover is removed, it can be passed through a hole with a diameter of 33 mm or larger. Then, at the time of installation, put it back together and be sure to fasten the screws. The tensile strength of the cable is 4.9 N (5 kgf). Do not subject the cable to a force greater than that.