The text of a manual · part 4 of 23
SYSMAC C200HS Programmable Controllers Installation Guide, pages 31 to 40
Pages 31 to 40 of 221
The original document is the PDF (2.5 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Omron C200H-OC225 and Omron C200HW-SLK23
Page 31
Section 2-2
CPUs
2-2-3 Power Supply AC Power Supplies:
C200HS-CPU01-E/CPU21-E/CPU31-E
Power fuse: 2 A, 250 V (5.2-dia. x 20) MF51NR
AC Input: Connect to 100 to 120 VAC or 200 to 240 VAC. Voltage selector terminals Short: 100 to 120 VAC Open: 200 to 240 VAC
Terminals for external connections
LG: Ground to 100 Ω or less to increase noise resistance and protect against shock. GR: Ground to 100 Ω or less to protect against shock.
+
24 VDC, 0.3 A output: Use to supply power to DC Input Units RUN output: ON when PC is operating.
C200HS-CPU01-EC/CPU21-EC Conforms to EC directives. Power fuse: 2 A, 250 V (5.2-dia. x 20) MF51NR
AC Input: Connect to 100 to 120 VAC or 200 to 240 VAC. Terminals for external connections
Voltage selector terminals Short: 100 to 120 VAC Open: 200 to 240 VAC NC GR: Ground to 100 Ω or less to protect against shock.
+
24 VDC, 0.3 A output: Use to supply power to DC Input Units RUN output: ON when PC is operating.
20
Page 32
Section 2-2
CPUs DC Power Supplies:
C200HS-CPU23-E/CPU33-E
Power fuse: 5 A, 125 V (5.2-dia. x 20) MF51NR
+
Terminals for external connections
24 VDC input: Connect to 24 VDC.
NC NC LG: Ground to 100 Ω or less to increase noise resistance and protect against shock. GR: Ground to 100 Ω or less to protect against shock. NC NC RUN output: ON when PC is operating.
C200HS-CPU03-E CPUs with lot numbers jjZ5 (Dec. 1995) or later conform to EC directives. Power fuse: 5 A, 125 V (5.2-dia. x 20) MF51NR
+
Terminals for external connections
24 VDC input: Connect to 24 VDC. (See note below)
NC NC Ground to 100 Ω or less to increase noise resistance and protect against shock. Ground to 100 Ω or less to protect against shock. NC NC RUN output: ON when PC is operating. (See note below)
Note Use a 24-VDC power supply with reinforced insulation or double insulation if the EC directives (low-voltage directives) must be satisfied.
21
Page 33
Section 2-2
CPUs
2-2-4 DIP Switch All the DIP switch settings are factory-set to OFF. Set them as required depending on the use. Pin no. 1
Item Memory protect
Setting ON OFF
2
Automatic transfer of Memory Cassette contents (see note 1)
ON
3
Message language
OFF ON OFF
4
Expansion instruction setting
ON
5
Communications conditions (see note 2)
OFF ON
Function Program Memory and read-only DM (DM 6144 to DM 6655) data cannot be overwritten from a Peripheral Device. Program Memory and read-only DM (DM 6144 to DM 6655) data can be overwritten from a Peripheral Device. The contents of the Memory Cassette will be automatically transferred to the internal RAM at start-up. The contents will not be automatically transferred. Programming Console messages will be displayed in English. Programming Console messages will be displayed in Japanese. Expansion instructions set by user. Normally ON when using a host computer for programming/monitoring. Expansion instructions set to defaults. Standard communications parameters (see note) will be set for the following serial communications ports. • Built-in RS-232C port • Peripheral port (only when a connecting cable for a personal computer (for example, the CQM1-CIF01/-CIF02 Cable) is connected) Note 1. Standard communications parameters are as follows: Serial communications mode: Host Link or peripheral bus; start bits: 1; data length: 7 bits; parity: even; stop bits: 2; baud rate: 9,600 bps 2. The CX-Programmer running on a personal computer can be connected to the peripheral port via the peripheral bus using the above standard communications parameters.
OFF
The communications parameters for the following serial communications ports will be set in PC Setup as follows: • Built-in RS-232C port: DM 6645 and DM 6646 • Peripheral port: DM 6650 and DM 6651
6
Expansion TERMINAL mode setting
ON OFF
Note
Note When the CX-Programmer is connected to the peripheral port with the peripheral bus, either set bits 00 to 03 of DM 6650 to 0 Hex (for standard parameters), or set bits 12 to 15 of DM 6650 to 0 Hex and bits 00 to 03 of DM 6650 to 1 Hex (for Host Link or peripheral bus) separately. Expansion TERMINAL mode (when AR 0709 is ON); AR 0712: ON Normal mode; AR 0712: OFF
1. The Memory Cassette is optional. 2. The values shown in the above table for the ON status of the communications conditions apply to CPUs with the lot number “jj75” (July 1995) or those manufactured afterward. The values for CPUs with the lot number “jj65” (June 1995) or those manufactured before then are as follows; stop bit: 1 and baud rate: 2,400 bps.
2-2-5 Peripheral Device Connector A Programming Console (C200H-PRO27-E or CQM1-PRO01-E) or IBM PC/AT running LSS can be used to program and monitor the C200HS PCs. They can be connected by opening the cover and connecting a cable to the peripheral device connector.
22
Page 34
Section 2-2
CPUs
Use the following cables to connect the respective Peripheral Devices. Programming Console: C200H-CN222/CN422 C200HS-CN222/CN422 (Conforms to EC directives) IBM PC/AT: CQM1-CIF02 (The C200H-CN222 Connecting Cable is included with the CQM1-PRO01-E Programming Console.) Note Peripheral Devices can be mounted directly to C200H PCs, but not to C200HS PCs.
2-2-6 Operation Modes The operation modes when the C200HS is powered up are shown in the table below. If a Peripheral Device is connected when the C200HS power is already on, the mode status prior to connecting the Peripheral Device will be retained. PC Setup (DM 6600) status Mode according to status of Programming Console keys (DM 6600 = 0000)
Mode retained from before power interruption (DM 6600 = 0100) Mode according to PC Setup DM 6600 = 0200: PROGRAM DM 6600 = 0201: MONITOR DM 6600 = 0202: RUN
Peripheral Device connected None Programming Console Device other than Programming Console None Programming Console Device other than Programming Console None Programming Console Device other than Programming Console
C200HS mode at power up Automatically goes into RUN mode. Goes into mode set by Programming Console selector switch. Automatically goes into PROGRAM mode. Goes into mode that was in effect prior to power interruption.
Goes into mode set by PC Setup (bits 00 to 07 of DM 6600).
2-2-7 Memory Cassettes The C200HS comes equipped with a built-in RAM for the user’s program, so a normal program be created even without installing a Memory Cassette. An optional Memory Cassette, however, can provide greater speed and flexibility. There are two types of Memory Cassette available, each with a capacity of 16K words. For instructions on installing Memory Cassettes, refer to Section 3 Installation. The following table shows the Memory Cassettes which can be used with the C200HS PCs. These Memory Cassettes cannot be used in C200H PCs. Memory
Capacity
Model number
EEPROM
16K words
C200HS-ME16K
---
Comments
EPROM
16K words
C200HS-MP16K
The ROM chip is not included with the Memory Cassette; it must be purchased separately.
Note Memory Cassettes for the C200HS cannot be used with the C200H, and Memory Units for the C200H cannot be used with the C200HS.
C200HS-ME16K (EEPROM)
When a Memory Cassette is installed in the CPU, reading and writing of the user memory (UM) and I/O data is made possible. There is no need for a
23
Page 35
Section 2-3
Expansion I/O Racks backup power supply. The Memory Cassette can be removed from the CPU and used for storing data.
C200HS-MP16K (EPROM)
The program is written using a PROM Writer. The ROM is mounted to the Memory Casette and then installed in the CPU. I/O data cannot be stored. Notch
2-3
Expansion I/O Racks The Backplane used to construct a CPU Rack is also used to construct an Expansion I/O Rack. An Expansion I/O Rack is identical to a CPU Rack, except the CPU is replaced with a Power Supply. Two Expansion I/O Racks can be connected to a CPU Rack. The number of I/O Units and Special I/O Units that can be connected to an Expansion I/O Rack is determined by the number of slots on the Rack.
24
Page 36
Section 2-4
Power Supply Unit
The parts of an Expansion I/O Rack are shown in the following diagram. I/O Connecting Cable Connector: Connects Expansion I/O Rack to preceding Expansion I/O Rack or to CPU.
Power Supply
Backplane
I/O Connecting Cable Connector: Connects Expansion I/O Rack to next Expansion I/O Rack. When not used, cover with a cap.
2-4
I/O Units Backplane mounting screws (four, with 4-mm dia. heads)
Power Supply Unit The Power Supply used for Expansion I/O Racks is available in three models. Two run on 100 to 120 or 200 to 240 VAC, and the other runs on 24 VDC. Also, one of the AC Power Supply Units conforms to EC directives. Be very careful not to provide an AC power supply to a DC-type Unit.
AC Power Supply Unit: POWER indicator (green): Lights when power is supplied to Power Supply
C200H-PS221 Power fuse: 2 A, 250 V (5.2-dia. x 20) MF51NR
AC Input Voltage selector terminals Short: 100 to 120 VAC Open: 200 to 240 VAC
Terminals for external connections
LG GR +
24 VDC, 0.3 A output NC NC
25
Page 37
Section 2-5
I/O Units C200H-PS221-C Conforms to EC directives. POWER indicator (green): Lights when power is supplied to Power Supply
Power fuse: 2 A, 250 V (5.2-dia. x 20) MF51NR
AC Input Terminals for external connections
Voltage selector terminals Short: 100 to 120 VAC Open: 200 to 240 VAC NC
+
24 VDC, 0.3 A output NC NC
DC Power Supply Unit POWER indicator (green): Lights when power is supplied to Power Supply
C200H-PS211 Units with lot numbers jjZ5 (Dec. 1995) or later conform to EC directives. Power fuse: 5 A, 125 V (5.2-dia. x 20) MF51NR
+
Terminals for external connections
24 VDC
NC NC
NC NC NC NC
2-5
I/O Units I/O Units are divided into three groups based on the way that I/O words they use are allocated. Standard I/O Units are allocated I/O words according to the Unit’s
26
Page 38
Section 2-5
I/O Units location on the CPU or Expansion I/O Rack. Group-2 High-density I/O Units are allocated I/O words according to I/O number set on each Unit. High-density I/O Units classified as Special I/O Unit are allocated I/O words according to the unit number set on each Unit.
2-5-1 Standard I/O Units Standard I/O Units come in three shapes; A-shape, B-shape, and E-shape. Refer to Appendix B Specifications for the dimensions of each Unit. A-shape I/O Unit (10-terminal Terminal Block) I/O Unit lock notch
Nameplate I/O indicators: Indicate ON/ OFF status of points
10-terminal terminal block
B-shape I/O Unit (19-terminal Terminal Block) I/O Unit lock notch
Nameplate I/O indicators: Indicate ON/ OFF status of points
19-terminal terminal block
Note The C200H-OC226 is an extended B-shape I/O Unit and its dimensions are different from those of the Unit shown above.
27
Page 39
Section 2-5
I/O Units E-shape I/O Unit (10-terminal Terminal Block)
I/O Unit lock notch
Nameplate I/O indicators Indicate ON/ OFF status of points
10-terminal terminal block
2-5-2 Group-2 High-density I/O Units Group-2 High-density I/O Units come in two varieties; C-shape and D-shape. The shape of the two varieties is the same, but C-shape Units have only one connector, while the D-shape Units have two. C-shape Units have 32 I/O points and D-shape Units have 64 I/O points. Unit DC Input Unit
Transistor Output Unit
Specifications 12 VDC; 64 pts
Shape
24 VDC; 32 pts
D C
24 VDC; 64 pts
D
4.5 VDC,16 mA to 26.4 VDC,100 mA; 32 pts 4.5 VDC,16 mA to 26.4 VDC,100 mA; 64 pts
C D
Model C200H-ID111 C200H-ID216 C200H-ID218 C200H-ID217 C200H-ID219 C200H-OD218 C200H-OD219 C200H-OD21B
Note Refer to Optional Products, Appendix A Standard Models for a list of external connectors. Group-2 High-density I/O Units are allocated I/O words in the IR Area (IR 030 to IR 049) by setting the I/O number switch on the front of each Unit. C-shape Units are allocated 2 words and D-shape Units are allocated 4 words beginning with m, where m = IR 030 + 2 × I/O number. For C-shape Units the 16 I/O bits in m are allocated to the A side of the connector, and the I/O bits in m+1 are allocated to the B side of the connector. For D-shape Units the I/O bits in m are allocated to the A side of connector 1, the I/O bits in m+1 are allocated to the B side of connector 1, the I/O bits in m+2 are allocated to the A side of connector 2, the I/O bits in m+3 are allocated to the B side of connector 2. Refer to the C200HS Operation Manual (W235) for more details on I/O word allocation.
28
Page 40
Section 2-5
I/O Units
Always turn the PC power off before changing a Unit’s I/O number. The new I/O number will not be recognized unless the PC has been turned off. Do not set more than one Unit to the same I/O number or set I/O numbers so that the same I/O word is allocated to more than one Unit, e.g., if you set a 64-point Unit to I/O number 0, you cannot use I/O number 1 for any Unit. Refer to Appendix B Specifications for the specifications and dimensions of the Units. C-shape Units (32-point Units)
I/O Unit lock notch
Nameplate I/O indicators: Indicate ON/OFF status of points I/O number setting switch
40-pin connector
D-shape Units (64-point Units) I/O Unit lock notch
Nameplate I/O indicators: Indicate ON/OFF status of I/O points I/O number setting switch Indicator switch: Determines whether the status of connector 1 or connector 2 I/O points are indicated by the I/O indicators. 40-pin connectors
29